New Yorker Gas Boiler Flame Roll Out & Cleaning
HTML-код
- Опубликовано: 10 мар 2018
- During this "no heat" service call, we found that the roll out switch was out caused by severe flame roll out. We disassembled the boiler and scrubbed the carbon clean between the cast iron sections.
#newyorker
#boiler
#testo
#combustion
#service
#heating Хобби
Great job! What did you use to reseal the cover?
Very well done. All too often I have seen recommendations to just swap out the boiler rather than give it a good cleaning. I have also found 2 things to hep - an air gun/compressor to blow out any carbon stragglers and borascope to search down the sections to make sure that nothing was missed.
Have you found any cleaning solutions for getting the top layer off or melting the carbon from the sections?
@@PipeDoctor Thanks. I was also thinking of modifying one of my brushes to attach to a drill.
How much is a job like this and replace roll out switch also, average cost for cleaning ?
I would like an answer to.
@@gyver471 it takes several hours to complete this service -it took 4 hours for mine. Depending on your location - the $/hour will vary but the time should be in that range.
Great job! How can one know if the heat exchanger is cracked? Will a bad damper cause this?
Fill the boiler with water and check for leaks or perform a visual inspection. No, a bad damper will not cause a HX to crack
@@PipeDoctor will a bad damper cause flame roll out? I changed the roll out sensor and it happened again Thanks
What causes a boiler to get carbonized like this?
Improper fuel to air mixture
so i see there is no cost or estimate given for a job like this. . Anybody have an idea of the cost
We typically don’t discuss pricing on this channel.
I cleaned ours and it started doing it the next day
Anyone who does this service in CNY? Oswego ny?
check out heatinghelp.com