How to change the elements on a Megaflo unvented cylinder | Training Tuesday | Troubleshooting Guide

Поделиться
HTML-код
  • Опубликовано: 9 окт 2024
  • In this edition of Training Tuesday, James explains how to change the elements on a Megaflo unvented cylinder.
    Please note: This video is intended for competent heating and hot water engineers only, for example must be Gas Safe registered if working with gas, or have the Unvented Hot Water Qualification (G3) and is subject to our full video disclaimer which can be found here: www.baxi.co.uk...
    For more information on the Megaflo range, head here: www.heatraesad...
    #cylinder #cylinders #trainingtuesday
    #Baxi #boilertraining #boilertroubleshooting #boiler #boilerbreakdown #boilerrepair

Комментарии • 17

  • @edoz3279
    @edoz3279 Год назад +5

    You said 8.5 ohms by mistake instead of 18.5 the first time you said it - Great video 🫡

  • @waynecartwright7276
    @waynecartwright7276 Год назад +2

    Great video thanks , thinking i need a spare immersion as it will never go if i buy one LOL

  • @b1h2u3p4
    @b1h2u3p4 Год назад +1

    Nice proper instructor

  • @DavidKneale
    @DavidKneale 7 месяцев назад

    I Want to know how to change the Megaflo floating baffle. Exactly! You can't! I've seen so many disintegrate with no explanation from the manufacturer.

  • @mrbaza8793
    @mrbaza8793 2 года назад +2

    Brilliant 🔧👍🏾

  • @David-bl1bt
    @David-bl1bt Год назад

    My new build house has a condensate pump fitted to the safety discharge pipe, is this permitted? There is no mention of this scenario in either the manufacturers instructions or G3 specs.

  • @simonmander4314
    @simonmander4314 8 месяцев назад

    I assume that the black washer sits behind the element flange?

  • @howardbeer5214
    @howardbeer5214 Год назад +4

    You forgot to say that you need to turn of the water supply to the cylinder before you drain it ????

  • @ewelinagergont5740
    @ewelinagergont5740 Год назад

    Can you please explain how I switch it off (leaving home for 2 weeks)? I searched whole internet... Not a word...

  • @njwareing6408
    @njwareing6408 2 года назад

    Do all mega flo's drain down the same way, do you not have to get air in the tank for the water to flow on an unvented tank?

    • @BaxiBoilersUK
      @BaxiBoilersUK  2 года назад +1

      Yes you do, it can be done by opening a hot water tap that is above the level of the top of the cylinder or/and open the T&P Valve this will help with draining the cylinder.

  • @bsaunder359
    @bsaunder359 Год назад

    Nice video

  • @eltonolldashi8349
    @eltonolldashi8349 Год назад

    Fantastisc work and yesss safety first, great instructions.

  • @AhmadMoghaddam-tu8iz
    @AhmadMoghaddam-tu8iz Год назад +1

    hi dear,i have megaflo 170 L direct ,i want change element, i want speake to you,can i call you ? thanks

  • @chriswright9819
    @chriswright9819 9 месяцев назад

    Don't agree with this Better to test for the system being powered first and switch off and see the power die away then you know the tester is working and the power has gone after switching it off

    • @jackhall6812
      @jackhall6812 8 месяцев назад +1

      Checking with a two pole indicator and proving unit is the safest way. If you have a reverse polarity on the line and neutral conductors you'll get a shock from the neutral and would have just assumed it was safe to work on..