Concept of leakage current and earth leakage
HTML-код
- Опубликовано: 6 фев 2025
- #short circuit #water leak #grounding #neutral wire #electrical practice #electric #electricallecture #RUclips
In this video, we will learn about the concepts of earth leakage and leakage current.
A circuit breaker with 380 volts flowing through it
Connect the 220 volt power to the washing machine through the earth leakage circuit breaker.
The 3(A) current that enters the L3 phase of the washing machine is after the washing machine starts working.
A current of 3(A) should return to the neutral wire again.
At this time, when 1(A) flows through the ground in the washing machine,
This leaked current is leakage current, and this phenomenon is
You could say there was a short circuit.
부스바가 갈흑회청 색갈이 맞나요?
내컴에서는 적흑회청으로 보이는군요
그럼 세탁기의 외함이랑 어디를 찍어보면 외부로 빠져나가는지 확인이 가능할까요?
수고많으셔요 ^^
누전이 되는지 안되는지를 측정할렴
메거(절연저항계)로 차단기2차측에 적색단자를 세탁기 외함(녹없는 금속부분에) 흑색단자(찝게단자)를 대어보면 절연저항값이 나오는대 2~3메가옴 나오면 괜찮습니다. 수치가 크면 클수록 좋은것이고요 만일 절연저항값이 1메가옴 이하로 나오면 누전이 생기는것이니 누전되는곳을 찾아서 수선해야됩니다.
그냥두면 전기요금도 조금더 나오고 감전의 우려가 있습니다. 물론 누전이 점점 심해지면 누전차단기가 동작해서 떨어지겠지만요
@@김현호-d7k 감사합니다~~~
@@김규복-x1v 차단기 2차측에 대어도 되지만 세탁기 전원플러거에 적색단자를 대는게 좀 편합니다.