Fixing 3 Military Generators I Bought At a Government Auction

Поделиться
HTML-код
  • Опубликовано: 17 дек 2024

Комментарии • 146

  • @brendonsanders192
    @brendonsanders192 10 часов назад +10

    Hey man you’ve got an awesome channel! Keep it up! You’re not afraid to just figure out how to do something and share the mistakes you make with us, and that’s what makes it so enjoyable to watch. Your humility doesn’t go unnoticed. Hope this encourages you. I pray God blesses you and your family!

  • @yostusoda
    @yostusoda 11 часов назад +38

    The fuel system bleeds itself with the switch in prime...the one you turn to start it, just leave it for a few minutes with the fuel pump clicking. You don't need to loosen the injector lines. To get voltage when you start it, hold the start switch on start for 10 seconds after the engine starts and the oil pressure builds you will see the voltage come up. The little knob is for fine tuning the voltage output. DO not turn the Output switch or phase lever while it's running, you will melt everything. There is an outlet breaker switch inside the drop panel. When you test for voltage go to neutral not ground. That fuel filter is the mother of all PITA....They are always stuck. The second genset you plugged in the stop solenoid with the wires reversed is why it is turning off instead of on. The black knob for frequency adjust changes the engine speed so you can set the HZ output.

    • @Alex-dz6if
      @Alex-dz6if 8 часов назад +3

      I think my original comment got deleted due to including the tm numbers for reference, but please read back up on the tm as some of this information is incorrect.
      Such as
      Bleeding the fuel lines-use the engine manual.
      Theory of operation- based off rpm not oil pressure. Use the 24 level manual
      Measuring output lugs - neutral and ground are bonded
      The output breaker switch is a GFCI.

    • @gerry-p9x
      @gerry-p9x 6 часов назад

      ​@@Alex-dz6ifpdf file available on net for these

  • @philipx2
    @philipx2 8 часов назад +13

    As a retired military generator technician I was yelling at you but you can't hear me. LOL

    • @hvguy
      @hvguy 7 часов назад +2

      Same 😭 it was painful.

  • @gerechoppers
    @gerechoppers 16 часов назад +43

    I recently found your channel. I’ve gone back through your play list and have watched all but a couple of them from start to finish. I appreciate your sense of humor, your work ethic and your love for God. You are a great example for others. You don’t have to cuss to make a great video and I really appreciate that. Keep up the good work. I’m looking forward to your channel blowing up and becoming huge.

  • @joelmead4299
    @joelmead4299 13 часов назад +12

    At that relay was the issue with the first one! I did 6 years in the Army and had these out at every field exercise we did. 5ks, 10ks, and some 30ks. Find you a distro box and some pigtails that plug into them they are universal to all the generators. They are bulletproof will run in any conditions. Keep diesel fuel in them is the hardest part.

  • @45acp
    @45acp 14 часов назад +15

    I used to run those when I was in the Marine Corps. The frequency adjuster can be fine tuned just by turning the handle or push the center button and pull for quick major adjustments. The 2 brass bullet looking things are for multiple ground rods. Copper threaded rods screw into them for a deeper ground rod.

    • @45acp
      @45acp 14 часов назад +2

      Also, all military equipment use Optima batteries.

  • @Boga217
    @Boga217 10 часов назад +4

    Yep onan diesel and gas generator systems usually incorporate some kind of low oil and low fuel shut off. In rvs and buses, it usually has to have 1/4 tank minimum to run. It was to prevent people from being stranded and harm to engine and pumps plus priming issues.

  • @hvguy
    @hvguy 7 часов назад +2

    The injector shut off solenoid has ground, pull and hold. The pull function usually runs off the starter solenoid and holds with the other wire.

  • @hvguy
    @hvguy 7 часов назад +3

    Also, 😂 battle short bypasses all the safeties. So itll run without oil, or if a sensor is bad, and you really need the generator; you can run it in battle short to just get the job done.

  • @Ronl53
    @Ronl53 9 часов назад +3

    You need to check the frequency as well. It should be 60hz. Most multimeters have a hz test setting for that. That is what the frequency adjustment knob is for. Great video!

  • @garylaviolette5853
    @garylaviolette5853 13 часов назад +4

    The thing with military equipment, either it's lightly used or beat on like a rented mule. Just the nature of the beast.

  • @LaLaLand.Germany
    @LaLaLand.Germany 10 часов назад +5

    Your "random diesel oil" was actually just the right stuff. Rotella 15W40 is what I´d put in any older diesel. I think You made a good catch although the 4cyl sounds like one is missing.
    do all the headers warm up? And Dude: get Yourself a Fluke meter. They are expensive but You can still service it in 30ys, still. They are just reliable. Treat Yourself to a better meter.
    Uni-T is another good brand I know of. And get the Service Manuals for these. There´s all and more to know in these. Army used to be good at writing manuals.
    I think You was lucky: if anything unknown in the genny sections was to be wrong they could arc flash or grenade. I´d make shure that they don´t go up to full rpm´s when 1st trying.
    Kind Regards, Merry Christmas! Please stay alive, this was fun to watch

  • @carllockpick6179
    @carllockpick6179 3 часа назад +1

    In cold weather, prime it first then preheat.

  • @1RellieRell1
    @1RellieRell1 9 часов назад +3

    2500 for all? What site?
    Glad someone posting new material on these. I have 2

  • @missilex
    @missilex 9 часов назад +2

    The generator with no power, hold the switch in the start position. The fancy looking relay disconnects the starter above 900 rpms and enables you to use the field flash relay.
    You get this fault on these generators that are really easy to start and have sat for a while

  • @dennissarver1963
    @dennissarver1963 14 часов назад +14

    Check your voltage to neutral, not ground !

    • @joshuagalvan681
      @joshuagalvan681 9 часов назад

      @@blablablaqwdhe doesn’t. He’ll make his money back from views alone I’m sure. I’m betting that’s why he bought em

    • @Dacer54
      @Dacer54 9 часов назад

      ​@@blablablaqwdIt's almost like there was a warning at the start of the video or something

    • @drummerdude476
      @drummerdude476 9 часов назад +1

      @@joshuagalvan681 you are severely inflating what RUclips pays people lmao. Don’t be so cynical

    • @roadrunner8574
      @roadrunner8574 4 часа назад

      @@blablablaqwdyou are free to buy ohne yourself! 😂

  • @GrandsonofKong
    @GrandsonofKong 15 часов назад +5

    Be careful.....one guy I followed worked on these(much bigger power usually) and he found only what he called "sabotage", bare copper wiring tossed in the wiring panel (shorts and sparks) screws tossed in the intake, etc a few times. So he checked everything before trying to start and power it up.

    • @BradenBuildz
      @BradenBuildz  15 часов назад +4

      Wouldn’t have thought of that

  • @dannyl2598
    @dannyl2598 9 часов назад +1

    In the storage box was a bare ground wire that would connect to a ground rod that has a little auger on the tip and a "T" handle to screw it in and out. Those two things are for coupling one section of 3/4 or 5/8 ground rod to another.

  • @DarkMageGuy
    @DarkMageGuy 15 часов назад +2

    Hope the mrs enjoyed her fancy dinner. You hit the jackpot with these id say.

  • @farmingsmallkubota1783
    @farmingsmallkubota1783 14 часов назад +2

    Dead crank is not for starting just to turn the motor over after oil changes, the Technical manuals give you all the info needed to work on these units, Square Facet pumps are notorious for not working even though they sound like it. no need to crack the injectors just let it pump

  • @billyhaddock5540
    @billyhaddock5540 2 часа назад

    BB, congrats on finding ur three Generators, two that works great. sell the big one to get some of ur money back.

  • @woozleboy
    @woozleboy 10 часов назад +1

    Looks like you just need a cutoff solenoid and a few minor bits and you'll have 3 operational gensets. You could make $4-5k profit while still keeping one for yourself!

  • @garyfrombarry1
    @garyfrombarry1 38 минут назад

    Hey from across the pond. I'm a noob to this channel (but, I'll be watching you now). You say your not electricaly minded, but boy, you can wrench. Love your way of figuring thigs out. I was a spanner jockey for 40 yeaer but had to give it up to ill heath. (got sick of the boss lol). All the best, and thanks for keeping us old spanner jockeys entertained.

  • @45acp
    @45acp 14 часов назад +1

    Those are auxiliary fuel pumps you heard running. The hose you found earlier is to run on a huge auxiliary fuel tank.

  • @1112223333111
    @1112223333111 36 минут назад

    56:00 when you take the filters off always make sure the oring is still on the filter. especially the oil

  • @riley4545
    @riley4545 37 минут назад

    Get a big ratchet strap with a hook type ending and connect it to your bent corner and then wrap it over the genset and connect the other end to the bottom on the other side and ratchet to pull up on the bent corner.

  • @rigmaster1
    @rigmaster1 15 часов назад +1

    Awesome content here. I've been casually watching some of the MEP military generators being sold on govplanet, but seems like many of them sell for way too much, and others that seem to bring reasonable prices have missing parts or are sold "not running". Guess I'm gonna have to not be skeered and bite the bullet and hope it's just something simple. thanks!

  • @NewBeRVer
    @NewBeRVer 14 часов назад

    Dude! I'm impressed! Not only are you smart af, but you have your hands into many diff projects! WoW!

  • @robharvey8418
    @robharvey8418 11 часов назад +1

    ground is for Earth. L0 is blue for Negative. and L1 L2AndL3 are all live Brown for positive, depending on which voltage you are running them on

    • @MrThisIsMeToo
      @MrThisIsMeToo 10 часов назад

      Newsflash, there is no negative or positive here. Very dangerous someone like yourself handing out uneducated advice.

  • @johnwsinkankas6043
    @johnwsinkankas6043 7 часов назад

    Very impressive....You are a heck of a good mechanic....You have the quality most of them don't have...and that is
    Instinctive diagnostic skills !! Keep up the good work. I will start following you, JWS

  • @rude252
    @rude252 Час назад

    If im not mistaken those look like Lister Petter engines rebranded as onan. Very good reliable diesel engines, will do in excess of 20k hours.

  • @McLivin410
    @McLivin410 10 часов назад

    Thank you for keeping me entertained during my 2 Hour Dr. in traffic much appreciated

  • @MisterrJmark
    @MisterrJmark 5 часов назад

    I can't tell you how exciting it was to see ol girl fire up!

  • @TMTRentals
    @TMTRentals 13 часов назад +1

    Best upcoming RUclips channel I watch every single one of your videos and every minute of your videos. If you are ever thinking of stopping pls don’t because a lot of us look forward to watching your videos!!

  • @1RellieRell1
    @1RellieRell1 8 часов назад

    As you discover more oil pressure just above 40 is good. Under heavy load as low as 20 is acceptable per spec

  • @1112223333111
    @1112223333111 41 минуту назад

    52:20 ground goes to a ground rod in the ground. you want to use neutral and L1 L2 L3 for volts. on 120 its neutral and L1 on 240 its L1 and L2 and 208 its all 3

  • @dadzilla13
    @dadzilla13 54 минуты назад

    Way to go Sir. And yes the video length was just fine.

  • @sherriaaberts8253
    @sherriaaberts8253 16 часов назад

    Heck yes Braden getting it done ! Way to go!

  • @jeremybrown6894
    @jeremybrown6894 9 часов назад

    Loved these videos! I would love to see the other generators getting fixed in your next vid

  • @ryanhouck452
    @ryanhouck452 9 часов назад

    Love the videos, keep them coming! Would love to see more videos like the Kubota compact tractor series.

  • @jtoddk98
    @jtoddk98 10 часов назад

    For the second generator, you need to flip the ac circuit interrupter to closed, not open. That’s why it wasn’t making any power

  • @osoulojs
    @osoulojs 9 часов назад

    Those copper couplers are for grounding stacks at 5:01

  • @greggkiest1069
    @greggkiest1069 14 часов назад

    Enjoyed every minute. Keep them coming.

  • @Earthling418
    @Earthling418 8 часов назад

    Fluke meters came out with a 40 dollar model. I got one and it's good for me for most stuff.

  • @berra5739
    @berra5739 2 часа назад

    Seems like those engines are pretty easy to work on

  • @CordellCorreia
    @CordellCorreia 8 часов назад

    When you test 120 ac. You dont test off ground you would use the common/neutral lug.

  • @VorlonFrog
    @VorlonFrog 11 часов назад

    Batting a thousand, baby!! Congratulations on fixing the simple issues these units had. Glad to know the wife will enjoy a good meal. LOL

  • @burgeraldo
    @burgeraldo 11 часов назад

    this is just amazing man, ngl your videos are additive.

  • @Djkyle65
    @Djkyle65 10 часов назад

    SO Lucky! I been trying to find just 1 for years and you found 3 wow!

  • @akshonclip
    @akshonclip 10 часов назад

    Don’t condemn a head gasket just because there is a little oil in the radiator. Could be a bad heat exchanger or just contaminated coolant. A cooling system pressure test will tell you what’s wrong. You can borrow them from the auto parts store.

  • @robertlemoine3500
    @robertlemoine3500 10 часов назад

    Merry Christmas 😊

  • @Stonecoldou
    @Stonecoldou 14 часов назад

    Thank you for another awesome video Braden. You are so talented. I absolutely love your channel.

  • @Williamxmr
    @Williamxmr 12 часов назад +1

    Your meter probably has an auto range and was reading 200mV (.2V) not 200 volts when you checked the dead battery.

  • @MyChannel-u2w
    @MyChannel-u2w 13 часов назад

    Another awesome video my friend! Very well done!

  • @mrMacGoover
    @mrMacGoover 10 часов назад

    19:30 Is the dog food "human grade" because it contains real humans? 😂 just kidding.

  • @jonlyons3376
    @jonlyons3376 12 часов назад

    I love that your posting more

  • @murymih
    @murymih 8 часов назад

    You don't have to crack off all injector lines in order to prime the injectors.....one or two are enough. Once the engine starts, it self primes the rest ✌️✌️🇰🇪🇰🇪

  • @Sl8er-the_gator
    @Sl8er-the_gator 16 часов назад

    It’s a miracle! He’s wearing boots instead of the crocs!

  • @truckergare
    @truckergare 12 часов назад

    Don’t forget to put dates and hrs on your filters.

  • @dlbrdb
    @dlbrdb 10 часов назад

    👏🏾👏🏾👏🏾 bravo brother

  • @bradbusch9585
    @bradbusch9585 15 часов назад

    I would say that you scored Great job brother

  • @hvguy
    @hvguy 7 часов назад

    And dont measure voltage from ground. Measure from neutral and between phases.

  • @glennschlorf1285
    @glennschlorf1285 10 часов назад

    You really need to get some advice from veterans over these... in particular army 52D they work with them

  • @sherzadhatem96
    @sherzadhatem96 14 часов назад

    Great job my friend 👍🏻💯

  • @Kuwaitin08
    @Kuwaitin08 29 минут назад

    It's dual fuel. It can run on either.

  • @StevenGentry-h3h
    @StevenGentry-h3h 15 часов назад

    Epic video sir enjoy all of your content.

  • @mrMacGoover
    @mrMacGoover 10 часов назад

    Wow... the first one fired right up! 😮 they just didn't understand how to flick the right switches to start it! Their stupidity...your gain!

  • @1112223333111
    @1112223333111 59 минут назад

    31:15 ya but are you on auxillary fuel or main fuel?

  • @MacacoHidraulico
    @MacacoHidraulico 16 часов назад

    Greetings from Brazil, we love your videos 😎

  • @cadthunkin
    @cadthunkin 11 часов назад

    Once you get them running, please donate back to Texas to electrify the wall!

  • @Boxey_green
    @Boxey_green 5 часов назад

    I have watch every single video u have 😊

  • @kpdvw
    @kpdvw 10 часов назад +1

    get the appropriate FM for these things...

  • @osoulojs
    @osoulojs 9 часов назад

    What is that engine for behind you at 18:52

  • @OMGitzEDD
    @OMGitzEDD 2 часа назад

    all 3 times im shouting at my monitor when you're testing the 3phase terminals on the ground lug that's meant for earthing the actual unit . probe the lo terminal that will be your neutral

  • @Tomshuski350
    @Tomshuski350 14 часов назад +3

    With the first unit you said it had 817 hours it actually has 81.7 hours the number in the white is 1/10 th of an hour
    Edit: i was wrong i didnt see there was an extra 8 on the hour metre so it is on 881.7 hours 😅

    • @BradenBuildz
      @BradenBuildz  13 часов назад +2

      It’s 882-4/10

    • @Tomshuski350
      @Tomshuski350 13 часов назад +1

      @@BradenBuildzyou are correct my bad mate i didnt see the extra 8 but i love your content man keep it up

  • @1RellieRell1
    @1RellieRell1 8 часов назад

    You scored big time...youll find the 5kw is more like 6250...

  • @medicman4444
    @medicman4444 25 минут назад

    OMFG a sponsor that's not a VPN XD what is this wizardry

  • @rodneyhudgins2977
    @rodneyhudgins2977 11 часов назад

    You're not the only one bro

  • @MrNeverseeme
    @MrNeverseeme 9 часов назад

    Pay attention to the "IDIOT-LIGHTS" there the simplest and basic to trouble shooting.

  • @allenanthony9798
    @allenanthony9798 12 часов назад

    Nice job keep up good work

  • @Monkey11124
    @Monkey11124 11 часов назад

    I have recently had to put my black German shepherd to sleep. She/he looks just like my dog.

  • @AsharIsaak
    @AsharIsaak 11 часов назад

    I'm pretty sure you just used 3 years of good luck.

  • @Scruffy001
    @Scruffy001 10 часов назад

    circuit interrupter needs to be closed to make power

  • @Crashing310
    @Crashing310 11 часов назад

    Fuel line is for aux fuel feed

  • @davekeehn8388
    @davekeehn8388 10 часов назад

    There’s tight and then there’s army tight.

  • @kristoffermangila
    @kristoffermangila 8 часов назад

    #WaldosWorld bought a military genset similar to your trio. Might check out his video about it.

  • @SupremeShuckle
    @SupremeShuckle 15 часов назад

    I would bet any amount of money in the world that “hours run counter” is rolled over

    • @BradenBuildz
      @BradenBuildz  15 часов назад

      It’s possible but some of these generators see little to no usage. In my own opinion I think the 800 hour one is actual and so is the 9000 hour one. Not sure about the 2800 hour one it could be rolled over

  • @getonlygotonly
    @getonlygotonly 4 часа назад

    yeah buddy. who cares whats inside long as its got good paint on the outside. grab the baling wire and duck tape, it'll be fine

  • @StevenGentry-h3h
    @StevenGentry-h3h 15 часов назад

    How has the v10 bmw going sir?

  • @JeremyCarlsten
    @JeremyCarlsten 15 часов назад

    @28:53... I'm sorry what kind of can is that?

  • @bretmartin2826
    @bretmartin2826 10 часов назад

    What part of Ky do you live in I’m in Magoffin county

  • @rogerghiardi7723
    @rogerghiardi7723 10 часов назад

    Maybe you need to charge the batteries 🤯

  • @gordonwilloughby8793
    @gordonwilloughby8793 7 часов назад

    They probably didn't put oil on the seal on the filter that was too tight.

    • @BradenBuildz
      @BradenBuildz  7 часов назад

      They did a little more than just not putting oil on the seal

  • @Stonecoldou
    @Stonecoldou 14 часов назад

    Thanks!

  • @edcochran714
    @edcochran714 9 часов назад

    Do you sell them???

  • @1112223333111
    @1112223333111 54 минуты назад

    antifreeze these days leaves a milky chauk behind when it dries it may not be oil

  • @WaterMalone42
    @WaterMalone42 13 часов назад

    Bear did not clean the plate.

  • @Lilred14
    @Lilred14 14 часов назад

    They all have the same manual q

  • @danielcovel6236
    @danielcovel6236 9 часов назад

    Great videos …sure wish you had ear plugs ….😊

  • @silverwoodcabinetry4631
    @silverwoodcabinetry4631 15 часов назад +1

    I wonder if that hose you found is for running the generator on propane? I am sure it's probably multi fuel maybe?

    • @BradenBuildz
      @BradenBuildz  15 часов назад +1

      It’s for running off an auxiliary tank. Only diesel

    • @blablablaqwd
      @blablablaqwd 11 часов назад

      No, it is a diesel engine, not petrol.