Never clear sight glass until box is at temp. If sight glass is clear adjust the valve to lower that S/H Can’t charge refrigeration by superheat You are overcharged big time
It’s always going to flash when the box is so warm. The TXV is wide open trying to catch the load Never evaluate charge until box is at temp Just saying
I hope you took a picture of that disconnect the company that turned it off needs to be held responsible for that product loss and any loss of business
How cool was the ambient temp? That headmaster low ambient valve was likely bypassing the condenser to maintain head pressure. You’ll see bubbles in the sight glass, discharge gas pushing through liquid. Food for thought. Great videos btw 👍
I feel like that light fell over and hit the disconnext. Do you use copeland mobile app to identify compressors? Sight glass bubbles from heavy load. Thank you for the video buddy
Hey, I know you found a disconnect off, but it could’ve been that somebody turned it off because it was making noise or when the defrost and they thought they might’ve been helping out by turning the breaker off because of the noise I think I’ll have to think that one over a while first Before I got some full sucker fired anyway I doubt they’ll find out who did it so good to me I’d be probably some something would do with the fuses in the tightening of electrical or some of that nature but anyway hey, I’m just an old Tallahassee boy my name, Fred I’ll check in with you later
I was surprised the king valve on the discharge line wasn't leaking. Every Heatcraft unit I've came across is leaking there.
Yep, I expected the LP control bellow to be leaking too.
Never clear sight glass until box is at temp. If sight glass is clear adjust the valve to lower that S/H
Can’t charge refrigeration by superheat
You are overcharged big time
Never cleared
Great video. Thank you for sharing. Stay safe out there
Thanks , you too Zekenzy !
It’s always going to flash when the box is so warm. The TXV is wide open trying to catch the load
Never evaluate charge until box is at temp
Just saying
Thanks for the comments
3 comments from randomrefrigeration4564... all saying the same thing. Was one not enough? 🙄
Box is at 38F today .
@@subcoolHVAC I'm sure that will still be wrong in their eyes 😂
I hope you took a picture of that disconnect the company that turned it off needs to be held responsible for that product loss and any loss of business
I made a video instead 👍
@@subcoolHVAC Yes sir you made a great video and yup about that disconnect.. Nobody knows nothing
im curious if the falling light pole kicked off the condenser, it was close enough to do so
If it did, it picked itself up and rested parallel to the switch to cover its tracks 😂
Those sneaky light poles😮@@subcoolHVAC
Great video!
Thanks CC 🙌
Good work
Thanks Victor 👊
How cool was the ambient temp? That headmaster low ambient valve was likely bypassing the condenser to maintain head pressure. You’ll see bubbles in the sight glass, discharge gas pushing through liquid. Food for thought. Great videos btw 👍
Good question, 74 when it was raining mid 80’s without rain .
I feel like that light fell over and hit the disconnext.
Do you use copeland mobile app to identify compressors?
Sight glass bubbles from heavy load.
Thank you for the video buddy
There was no base for that light, It is suspicious being there though 🤔 I usually check through the website. Thanks for checking it out!
Hey, I know you found a disconnect off, but it could’ve been that somebody turned it off because it was making noise or when the defrost and they thought they might’ve been helping out by turning the breaker off because of the noise I think I’ll have to think that one over a while first Before I got some full sucker fired anyway I doubt they’ll find out who did it so good to me I’d be probably some something would do with the fuses in the tightening of electrical or some of that nature but anyway hey, I’m just an old Tallahassee boy my name, Fred I’ll check in with you later
If they did turn it off for noise they sure didn’t inform the kitchen manager.
You are the reason the condenser needs to changed 😂Ion know how you guys make it for so long 😂
Not sure where you’re headed with that comment but Thanks for watching!
Wrong wrong wrong
Love you HVAC videos but refrigeration is different all together
30 yrs I’ve been doing it
Damn you overcharged way over
Don’t forget condenser is corroded out causing my high CP, I’m sure you agree it’s time for new equipment