Walk In Cooler Not Having A Good Day… Looking For Answers..

Поделиться
HTML-код
  • Опубликовано: 4 фев 2025
  • Got a work order for a walk in cooler blowing hot air, food has gone bad… here’s what I found #refrigeration #hvacrepair #cooler

Комментарии • 32

  • @topher8634
    @topher8634 4 месяца назад +7

    I was surprised the king valve on the discharge line wasn't leaking. Every Heatcraft unit I've came across is leaking there.

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад +3

      Yep, I expected the LP control bellow to be leaking too.

  • @randomrefrigeration4564
    @randomrefrigeration4564 4 месяца назад +4

    Never clear sight glass until box is at temp. If sight glass is clear adjust the valve to lower that S/H
    Can’t charge refrigeration by superheat
    You are overcharged big time

  • @zekenzy6486
    @zekenzy6486 4 месяца назад

    Great video. Thank you for sharing. Stay safe out there

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад

      Thanks , you too Zekenzy !

  • @randomrefrigeration4564
    @randomrefrigeration4564 4 месяца назад +4

    It’s always going to flash when the box is so warm. The TXV is wide open trying to catch the load
    Never evaluate charge until box is at temp
    Just saying

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад +2

      Thanks for the comments

    • @alex13902
      @alex13902 4 месяца назад

      3 comments from randomrefrigeration4564... all saying the same thing. Was one not enough? 🙄

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад +1

      Box is at 38F today .

    • @alex13902
      @alex13902 4 месяца назад

      @@subcoolHVAC I'm sure that will still be wrong in their eyes 😂

  • @DanT271
    @DanT271 4 месяца назад +5

    I hope you took a picture of that disconnect the company that turned it off needs to be held responsible for that product loss and any loss of business

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад +7

      I made a video instead 👍

    • @DanT271
      @DanT271 4 месяца назад +3

      ​@@subcoolHVAC Yes sir you made a great video and yup about that disconnect.. Nobody knows nothing

  • @Paul-IE-Repairs
    @Paul-IE-Repairs 4 месяца назад +1

    im curious if the falling light pole kicked off the condenser, it was close enough to do so

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад +2

      If it did, it picked itself up and rested parallel to the switch to cover its tracks 😂

    • @MrJujubean
      @MrJujubean Месяц назад

      Those sneaky light poles😮​@@subcoolHVAC

  • @ccthepope
    @ccthepope 4 месяца назад +1

    Great video!

  • @thesilentonevictor
    @thesilentonevictor 4 месяца назад +1

    Good work

  • @jacobeagy7526
    @jacobeagy7526 4 месяца назад +2

    How cool was the ambient temp? That headmaster low ambient valve was likely bypassing the condenser to maintain head pressure. You’ll see bubbles in the sight glass, discharge gas pushing through liquid. Food for thought. Great videos btw 👍

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад +1

      Good question, 74 when it was raining mid 80’s without rain .

  • @Ericbakereb1
    @Ericbakereb1 4 месяца назад +2

    I feel like that light fell over and hit the disconnext.
    Do you use copeland mobile app to identify compressors?
    Sight glass bubbles from heavy load.
    Thank you for the video buddy

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад

      There was no base for that light, It is suspicious being there though 🤔 I usually check through the website. Thanks for checking it out!

  • @jewellhirsch1694
    @jewellhirsch1694 4 месяца назад +2

    Hey, I know you found a disconnect off, but it could’ve been that somebody turned it off because it was making noise or when the defrost and they thought they might’ve been helping out by turning the breaker off because of the noise I think I’ll have to think that one over a while first Before I got some full sucker fired anyway I doubt they’ll find out who did it so good to me I’d be probably some something would do with the fuses in the tightening of electrical or some of that nature but anyway hey, I’m just an old Tallahassee boy my name, Fred I’ll check in with you later

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад

      If they did turn it off for noise they sure didn’t inform the kitchen manager.

  • @anthonyriddick9842
    @anthonyriddick9842 4 месяца назад

    You are the reason the condenser needs to changed 😂Ion know how you guys make it for so long 😂

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад +1

      Not sure where you’re headed with that comment but Thanks for watching!

  • @randomrefrigeration4564
    @randomrefrigeration4564 4 месяца назад +2

    Wrong wrong wrong
    Love you HVAC videos but refrigeration is different all together
    30 yrs I’ve been doing it
    Damn you overcharged way over

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад +4

      Don’t forget condenser is corroded out causing my high CP, I’m sure you agree it’s time for new equipment