Configuring VLT Micro Drive FC51 for Two wire start/stop with Multi-setup (Auto/manual) || DIGICON
HTML-код
- Опубликовано: 12 сен 2024
- Configuring VLT Micro Drive FC51 for Two wire start/stop with Multi-setup (Auto/manual) system || Digicon Automation
Auto Mode: Reference from PLC (Programmable Logic Controller)
Manual Mode: Reference from POT (Potentiometer)
Parameter No. Parameter name Set-up 1 (Auto) Set-up 2 (Manual)
0-10 Active Set-up [ 9 ] Multi Set-up [ 9 ] Multi Set-up
0-11 Edit Set-up [ 1 ] Set-up 1 [ 2 ] Set-up 2
0-12 Link setups [ 20 ] Linked [ 20 ] Linked
1-20 Motor Power As per motor data As per motor data
1-22 Motor Voltage As per motor data As per motor data
1-23 Motor Frequency As per motor data As per motor data
1-24 Motor Current As per motor data As per motor data
1-25 Motor Nominal Speed As per motor data As per motor data
3-15 Reference Resource 1 [ 2 ] Analog Input 60 [ 1 ] Analog Input 53
3-16 Reference Resource 2 [ 0 ] No function [ 0 ] No function
3-17 Reference Resource 3 [ 0 ] No function [ 0 ] No function
3-41 Ramp 1 Up Time As per Requirement As per Requirement
3-42 Ramp 1 Down Time As per Requirement As per Requirement
4-10 Motor Speed Direction [ 0 ] Clockwise [ 0 ] Clockwise
4-14 Motor Speed High Limit 50Hz 50Hz
4-16 Torque Limit Motor Mode 150% 150%
4-17 Torque Limit Generator Mode 100% 100%
5-10 Terminal 18 Digital Input [ 8 ] Start [ 8 ] Start
5-11 Terminal 19 Digital Input [ 0 ] No function [ 0 ] No function
5-12 Terminal 27 Digital Input [ 0 ] No function [ 0 ] No function
5-13 Terminal 29 Digital Input [ 0 ] No function [ 0 ] No function
5-15 Terminal 33 Digital Input [ 23 ] Set-up select bit [ 23 ] Set-up select bit
5-40 Function Relay (Relay 1) [ 5 ] Running [ 5 ] Running
6-10 Terminal 53 Low Voltage - 0.00 V
6-11 Terminal 53 High Voltage - 10.00 V
6-19 Terminal 53 mode - [ 0 ] Voltage mode
6-22 Terminal 60 Low Current 4.00 mA -
6-23 Terminal 60 High Current 20.00 mA -
Very useful sir , great keep it up ,now our m/c running ☺️☺️
Sir ABB VFD par v video baneye .apke video sa hame bhut knowledge mile ha vfd par.Thanks a lot!
Actually we are authorized channel partner of danfoss, so can't make a video on ABB
Thanks thanks and thanks a lot for this video. Problem resolved.
GREAT VIDEO
Thanks sir.....very helpful
Most welcome
Great sir.
good explan sir
Keep watching
Super
Sir danfoss 360 ko synchronisation kaise kre or external source kliye parameters kya h
Gazab hai
Please add vedio with complete installations with on off switch or frequency up and down
I'm already uploaded on my channel..
Where do I get the switch set for this project?
क्या इस ड्राइव को सोलर इनपुट से चला सकते हैं। मुझे 1 hp का submersible pump chala hain। Abhi 8 panels hain।
I don't see a switch between Hand and Auto. Your A/M toggle switch alternates between 2 setups (1 and 2). Is there a possibility to control HAND, AUTO, OFF remotely through digital input or modbus command?
NO, for Hand control u have to press button on LCP display.
@@DIGICONAUTOMATION What about for AUTO? Is there anyway to link that to a Dig.In contact or through Modbus?
@@daveal3d NO, it's not possible to control hand, auto using modbus or digital input, we have to operate these function manually....
@@DIGICONAUTOMATION For some reason some of my signle phase drives go back to OFF after a trip (8: Undervoltage DC bus). Even though in the parameters i set to infinitely reset trips/alarms, it still goes to OFF. Any advice?
@@daveal3d I'm recently uploaded a video on that topic, so hope u get help from that video....ruclips.net/video/wcmCiJTLroo/видео.html
Ye kaise malum padega ki ye parameter Torque ,reference current 4 ml, reference pot 10 volt,motor name plate etc..... Ke hi h.
Iske liye aapko vlt guide download karni hogi jisme aapko sabhi parameters ka no. and name diya hoga...
Motor thermistor kaise connect karenge isme
Sir, please tell me can be supply DC input from solar to the drive to generate triple phase 415 V
No you need power inverter for that.
It’s have AC input AC output.
sir vsd off mode also colling fan running. vsd no have silant mode. have any advice . fc 51
sir selecter switch off mode also vsd coolling fan running. running sound coming.
See parameter 14-52 fan control mode .
Set on auto , not always run
i am used 12,18,42,53,55 terminal. i want to know 42 parameter setup. can u help me sir
Sir soft starter par v auto menul video bania
where terminal 33 defined in program?
Ghalti se auto on ka button press hoo gaya ab woh start nahi hoo rha
do bar menu dabane par pw aa ja to kia ki ya jia ya do bar menu daba ne par passord magane par kiya kare
modbus communication??
Sir alarm red show kar raj hai our display par AL13 aa rah hai please help
ruclips.net/video/gwkSmxpki80/видео.html
Tnq sir
@@DIGICONAUTOMATION sir mere drive me kuch problem hai, please sir number de do jo ki me aap se sahi se samajh saku.
मुझे मेरे ड्राइव मे प्रॉब्लर्म आ रही है मे आपै बट कर सकता हु