Sir We are facing one problem in VLT2800 VFD It is first goes in fault mode error 14 after .we are reset the fault .checked all parameters .now VFD out put is not caming still.If you are having some trouble shooting remidi pl send me
Error 14 is earth fault. Check the earth wire connection on the vfd.check the motor winding of any earth leakage . Check the motor wire for any short circuits. ...
@@EASYPLCTRAINING Sir We traced there is no any short circuit between motor and VFD in local mode motor is running but in remote mode it is not getting ON
good video, question where did you buy the speed control kit & housing?
thank you for that wonderful information sir, I appreciate it.
Great the video...speacking very clear and easy to understand
Thanks
Great video useful for damping motor thanks
This can be used to run a 3 horsepower motor?
Thanks a lot
Thank you 👍
Sir
We are facing one problem in VLT2800 VFD It is first goes in fault mode error 14 after .we are reset the fault .checked all parameters .now VFD out put is not caming still.If you are having some trouble shooting remidi pl send me
Error 14 is earth fault. Check the earth wire connection on the vfd.check the motor winding of any earth leakage . Check the motor wire for any short circuits. ...
@@EASYPLCTRAINING
Sir
We traced there is no any short circuit between motor and VFD in local mode motor is running but in remote mode it is not getting ON
@@EASYPLCTRAINING Spare one VFD also replaced parameters settings done. From remote motor is not running