Assalamualykum sir. If i set the riser of sprinkler far from the stair. And set the zone controll at the middle side of the building. Is that issue ase per nfpa?
Standpipe system's hose connections, hose cabinets or hose compartments are required in landings of staircase and exit or entry doors therefore mostly riser pipes are installed on the staircase side. You can install a riser pipe in the middle of the building but pipes connection may be difficult/
@@TanweerAhmed Good, Expected answer, In a combined system (sprinkler &FHC) from where we start fire hose connection, normally FHC line will start just before zcv na? If no zcv, from where we start fhc line ?
@@habeebrk as per your case as it is combine system you can take fhc individual connection from main sprinkler line but with isolation valve after each connection to control fhc.
If 8 bar = 116 psi pressure of pump then water move up side to floor then gradually pressure decrease in height therefore I also suggest to no need PRV with ZCV (standard recommend working pressure 50 to 75psi but should be under pressure of sprinklers design) if our sprinklers design pressure is 150 to 175psi then no need to install PRV with ZCV
السلام علیکم سر،زبردست ڈیٹیل دے دیا آپ نے شکریہ۔ لیکن سر یہ اسمبلی وال میں جو کیبل ہیں وہ mov کیلئے ہیں یااور کوئی کنٹرول ؟ اسکا تھوڑا سا اکسپلین کرلیں ۔ شکریہ
The requirement for a check valve to be included as part of the connection to the sprinkler system is to permit the standpipe riser to be drained and refilled in a limited amount of time should repair be necessary to any portion of the standpipe riser, fire department hose valves, pipe, and fittings, etc.
The check valve arrangements in ZCV assembly permit the standpipe system to be drained while allowing the sprinkler pipe to remain water filled. In general, the check valve between the two systems maintains the water volume supplied within the sprinkler piping, thereby limiting the drain and refill time of the overall combination standpipe/sprinkler system. In addition, when combination risers are cross connected (loop or dual feed), the check valves will limit the flow to the appropriate floor where sprinklers have activated and limit circulation of water throughout multiple levels of the building.
Because if sprinkler glass break then when have to replace sprinkler after drain pipelines. Moreover, if you drain valve without sprinkler glass break then ACV activate in pump room and FACP panel inform about zone activation
OS&Y valve with tempering switch will be supervisory valve. Also Supervisory Butterfly valve available. Here both function will be same but physical structure change.
W.salam, No need NRV in ZCVA because NRV is installed in Pump room. In firefighting standard used supervisory valve because this valve give ON/OFF status on FACP & also physically status, while gate valve does not provide this information.
Bro, I have a light hazard building with 12000m2 area, Can I Provide Fire water supply with Single riser with single Alarm Check valve and multiple Zone control valves? Or 3 riser with 3 Alarm check valve is must? (Bcs asper nfpa single riser can serve 4000m2 area only)
High rise building me water pressure top par kitna hoga and overhead tank aur booster pump ke case me pressure distribution kaise kaam karte he please explain.
Vaiya please Help me. NFPA As a rule how to calculated fire centrifugal pump water pressure bar and bar to galleon to pound. How to calculation. Please Help me vaiya.
Riser means standpipe: this pipe is installed vertically for water flow upward to building, while hydrant are installed outside of building at ground floor (Note: no hydrants are installed inside of building, these are called landing valve or standpipe hose connection with or without cabinet and hose reel)
@@TanweerAhmed thanks to reply our header is 6 inch and hydrant are out side building My question is that we will take two connection from header one for riser and one for out side hydrant or only one connection for riser and than from riser we will take a connection for hydrants. Thanks for your valuable input
As per NFPA 13:2019, 4.5.1 The maximum floor area on any one floor to be protected by sprinklers supplied by anyone sprinkler system riser or combined system riser shall be as follows: (1) Light hazard - 52,000 ft2 (4830 m2) (2) Ordinary hazard - 52,000 ft2 (4830 m2). Therefore on any one floor, you can install one Zone Control Valve Assembly and sprinklers quantity to be calculated according to hazard recommended area.
hi sir, thanks for your videos. i have seen lots of youtube video but nothing is clear as like yours. Even in firefighting course the teach like this.
Thank you
Watch my this video, then ZCV concept will be more clear:
ruclips.net/video/QUjPHz_R6Mw/видео.html
@@TanweerAhmed Thanks alot too you .. brother...
Mashallah very Nice video & knowledge shearing. 🌟🌟🌟🌟🌟
Thanks
Best Chanel for fire fighting...
Thank you sir.
Welcome
Your all videos are in so much details and depth. Even non technical person also understand. Thank you very much sir for all the knowledge you share. Really Appreciate
Thank you for your kind words
Behtareen video hy.
Thanks
Nice video sir video banane ke liye thanks
Welcome
I saw this videos I got good knowledge thank you sir
Welcome 😊
Knowledge ke alawa you have very good explanatory skills.. Great job
Thank you
thank you so much for such unique live information
Welcome
Hi sir, please sharing videos related to fire fighting system. Very helpful information.
I will continue upload videos about firefighting in future. Thanks for your interest
Behtreen video
Thank you
Good knowledge
Thanks
Sir thank you very much for site recording. Thanks thanks thanks
Welcome
Zabardast video
مھرباني ...
I'm from unilever pakistan.....thanks for video
Welcome
Thanks Mr tanweer
Most welcome
Good work bro
Thank you
Very nice bro...
Thanks
Important video
Thank you
Excellent
Thank you
Excellent sir g
Thanks
@@TanweerAhmed Which video is suitable to learn basic about ducting?
Visit my HVAC playlist, almost all videos are about basics including ducting
@@TanweerAhmed thk ha thanks sir
Welcome
Kammmmmmmallll love
Thanks
Please make a vedio over water storage tank designing and pipe sizing methods at branch
I will.... insha'Allah
Assalamualykum sir.
If i set the riser of sprinkler far from the stair. And set the zone controll at the middle side of the building. Is that issue ase per nfpa?
Standpipe system's hose connections, hose cabinets or hose compartments are required in landings of staircase and exit or entry doors therefore mostly riser pipes are installed on the staircase side. You can install a riser pipe in the middle of the building but pipes connection may be difficult/
GREAT
Thanks
Bro, I have a single zone wet sprinkler system, Does it required both alarm check valve and zone control valve or alarm Check valve only ?
Single zone means one zone therefore no need ZCV assembly and only required Alarm check valve assembly which will fulfill the NFPA requirements
@@TanweerAhmed Good, Expected answer,
In a combined system (sprinkler &FHC) from where we start fire hose connection, normally FHC line will start just before zcv na?
If no zcv, from where we start fhc line ?
@@habeebrk ZCV is not used in fire hose connection because we use manually fire hose and ZCV is required in auto sprinkler system
@@TanweerAhmed I mean for combined system
@@habeebrk as per your case as it is combine system you can take fhc individual connection from main sprinkler line but with isolation valve after each connection to control fhc.
AoA sir kya sprinkler 175 psi k pressure pr design nhi hte?
Max design pressure of sprinkler is 150 to 175 psi
But working recommend pressure is 50 to 75 psi
@@TanweerAhmed sir aik jagah zcv me contractor prv nahi laga raha hai kyu pump 8bar ka pressure deraha hai kehta hai zarurat nahi hai prv ki zcv me
If 8 bar = 116 psi pressure of pump then water move up side to floor then gradually pressure decrease in height therefore I also suggest to no need PRV with ZCV (standard recommend working pressure 50 to 75psi but should be under pressure of sprinklers design) if our sprinklers design pressure is 150 to 175psi then no need to install PRV with ZCV
السلام علیکم سر،زبردست ڈیٹیل دے دیا آپ نے شکریہ۔
لیکن سر یہ اسمبلی وال میں جو کیبل ہیں وہ mov کیلئے ہیں یااور کوئی کنٹرول ؟
اسکا تھوڑا سا اکسپلین کرلیں ۔ شکریہ
I will make video about control wiring of ZCV
@@TanweerAhmed thanks sir, we will wait Insha Allah
Thanks for your nice videos. Could you make a video for sprinkler hydraulic calculation method!
insha'Allah in future
Why check valve is providing in combined sprinkler riser ZCV Assembly . Please explain.
The requirement for a check valve to be included as part of the connection to the sprinkler system is to permit the standpipe riser to be drained and refilled in a limited amount of time should repair be necessary to any portion of the standpipe riser, fire department hose valves, pipe, and fittings, etc.
The check valve arrangements in
ZCV assembly permit the standpipe system to be drained while allowing the sprinkler pipe to remain water filled. In general, the check valve between the two systems maintains the water volume supplied within the sprinkler piping, thereby limiting the drain and refill time of the overall combination standpipe/sprinkler system. In addition, when combination risers are cross connected (loop or dual feed), the check valves will limit the flow to the appropriate floor where sprinklers have activated and limit circulation of water throughout multiple levels of the building.
Thank you👍🏻👍🏻
Sir I have a godown of Confectionery of 300 square yard. What fire fighting system we should install. Please guide
Wet fire sprinkler system
Sir why we use test drain valve?
Because if sprinkler glass break then when have to replace sprinkler after drain pipelines. Moreover, if you drain valve without sprinkler glass break then ACV activate in pump room and FACP panel inform about zone activation
Assalamualaikum wr.please let me know for how much area one zcv will be considered.
As per std 8.2.1 on NFPA 13 it indicates an area of 3720m^2 per control valve, this works out to be 400 sprinklers per control valve
@@TanweerAhmed jazakaallah bhai...
@@TanweerAhmed what will be the main line pipe size if 3720m^2 and 400 sprinkles can be served ,is there any limitations of pipe size .
Kindly watch my video of pipe schedule method regarding pipe size & number of sprinklers. Also another video pipe schedule method for Standpipe
Sir os& y valve and supervisory valve me kya difference hai
OS&Y valve with tempering switch will be supervisory valve. Also Supervisory Butterfly valve available. Here both function will be same but physical structure change.
Aoa bro why there isn't nrv in zcva?
And if I use gate valve instead of supervisory valve ?
W.salam, No need NRV in ZCVA because NRV is installed in Pump room. In firefighting standard used supervisory valve because this valve give ON/OFF status on FACP & also physically status, while gate valve does not provide this information.
I worked at Doha metro and we used NRV in zcva
If you are away from pump Room or no access in pump Room then you can use NRV. But NFPA-13 allow NRV with ZCV
Bro, I have a light hazard building with 12000m2 area, Can I Provide Fire water supply with Single riser with single Alarm Check valve and multiple Zone control valves?
Or 3 riser with 3 Alarm check valve is must? (Bcs asper nfpa single riser can serve 4000m2 area only)
your second option
Sir aap Pakistan se ho 👍I'm from India thanks to information
Yes, from Sindh, Pakistan
High rise building me water pressure top par kitna hoga and overhead tank aur booster pump ke case me pressure distribution kaise kaam karte he please explain.
Kindly watch my firefighting videos and check in my playlist. I hope you will understand
Good
Thanks dear
Hi sir, Can you please do a video on Vertical turbine fire pump?
Ok noted and thanks
ممتاز
?
@@TanweerAhmed great
Vaiya please Help me. NFPA As a rule how to calculated fire centrifugal pump water pressure bar and bar to galleon to pound. How to calculation. Please Help me vaiya.
Watch my video i.e. " NFPA-14 Pressure Requirements" which to be helpful for you
Thank you vaiya
From where we take connection for outer fire hydrant in combined sprinkler and fire hydrant system
From discharge header of fire pumps
@@TanweerAhmed thanks to reply
Please confirm me from header or from riser
secondly what will be dia of 4 or 6 inch if our header is 4 inch
Riser means standpipe: this pipe is installed vertically for water flow upward to building, while hydrant are installed outside of building at ground floor (Note: no hydrants are installed inside of building, these are called landing valve or standpipe hose connection with or without cabinet and hose reel)
If header is 4" means your system is not combine system. In hydrant system, minimum main pipe should be 6" diameter as per standard requirements.
@@TanweerAhmed thanks to reply our header is 6 inch and hydrant are out side building
My question is that we will take two connection from header one for riser and one for out side hydrant or only one connection for riser and than from riser we will take a connection for hydrants.
Thanks for your valuable input
Boss Zone Control valve say flow switch ka distance kitna hona chiyay?
2D
السلام علیکم
Dear Sir,
Kindly make a video for supervisory switch and fire alarm.
Thanks
Ok noted 😊
❤
Thanks
Tanweer Bhai agar kaam shikhna hoto kya Karin
Kaam sikhnay k leay kaam Karna paray ga. Start practical work like job
Whater curon nozal agar chalu ho jay to floor suich signal dega ae hame pata nahi janna hai
Yes, it will provide signal at fire alarm panel and you have reach at the zone where is happened
Assalamualaikum
Sir Aap Ka Company Ka hai
W.Salam,
Karachi, Sindh, Pakistan
thanks for videos sir but i need documentation english because my langue arabic english please
I will try subtitles
@@TanweerAhmed thanks sir
It's a Pressure reducing valve. It is required to maintain pressure not more than 175 psi.
Ok
It's a function of prv rather than pdv
Sir 1 ICV m kitne sprinkler install Kiya ja sakta h
What is ICV?
@@TanweerAhmed installation control valve
As per NFPA 13:2019, 4.5.1 The maximum floor area on any one floor to be protected by sprinklers supplied by anyone sprinkler system riser or
combined system riser shall be as follows:
(1) Light hazard - 52,000 ft2 (4830 m2)
(2) Ordinary hazard - 52,000 ft2 (4830 m2). Therefore on any one floor, you can install one Zone Control Valve Assembly and sprinklers quantity to be calculated according to hazard recommended area.
Sir fire fighting system installation drawing Ka upor video Di ja
There is available video in my playlist of firefighting. If you have any questions then you can ask
Kamal ka describe kya
Thanks
Bhai ZCV ka zikar hi nhi hai kahi 🙄
These all things are part of Zone Control Valve Assembly
Assalamu alaikkum
Sir aappka wattsapp nambar thega
Already shared
Please add English suptitle brother
Ok noted
No English
I will make subtitles but it take time
@@TanweerAhmed thank you 😊
Good
Thanks