Pressure Sensing Lines Fire Pump | NFPA 20 | in Urdu/Hindi

Поделиться
HTML-код
  • Опубликовано: 9 фев 2025
  • This is a fire fighting tutorial video about "Pressure Sensing Lines Fire Pump for NFPA 20 Fire Pumps" in Urdu/Hindi language. These pressure sensing lines are used with a jockey pump, electric fire pump, and diesel fire pump. It is basic learning detailed information about Pressure Actuated Controller Pressure Sensing Lines as per NFPA 20 standard requirements. It is also important for Firefighting/MEP technical staff. Here sharing my experience and knowledge that will be helpful to learn & grow for Engineers & Technical staff. If you found anything which is inappropriate then convey it in the comments for my information and rectification in the future.
    Tanweer Ahmed's Fire fighting videos for your watching and growing:
    1. NFPA-14 Pipe Schedule Method for Standpipe
    Video's link: • NFPA 14 Pipe Schedule ...
    2. NFPA-14 Flow Rate Requirements for Standpipe & Hose System
    Video's link: • NFPA 14 Flow Rate Requ...
    3. NFPA-14 Pressure Design Requirements of Standpipe & Hose System
    Video's link: • NFPA-14 Pressure Desig...
    4. NFPA-14 Classes of Standpipe Systems
    Video's link: • NFPA-14 Classes of Sta...
    5. NFPA-13 Pipe Schedule Method Designing
    Video's link: • NFPA 13 Pipe Schedule ...
    6. NFPA-13 Sprinkler Heads Distribution
    Video's link: • NFPA-13 Sprinkler Head...
    7. NFPA-13 Density & Area of Sprinkler Operation
    Video's link: • NFPA 13 Density & Area...
    8. NFPA-13 Sprinklers Discharge Characteristics
    Video's link: • NFPA-13 Sprinklers Dis...
    9. Wet Riser Landing Valve System
    Video's link: • Wet Riser Landing Valv...
    10. Testing of Wet Riser Landing Valve System
    Video's link: • Testing of Wet Riser L...
    11. Fire Hose Reel System
    Video's link: • Fire Hose Reel System ...
    12. Testing of Fire Hose Reel System
    Video's link: • Testing of Fire Hose R...
    13. Converting Pump Head to Pressure or Vise Versa
    Video's link: • Converting Pump Head t...
    14. Difference Between Pressure Reducing & Pressure Restricting Valve
    Video's link: • Difference Between Pre...
    15. Difference Between Pressure Relief & Pressure Safety Valve
    Video's link: • Difference Between Pre...
    16. Combined Firefighting System Water Demand
    Video's link: • Combination Standpipe ...
    17. Types of fire sprinkler system of fire suppression systems
    Video's link: • Types of fire sprinkle...
    18. Dry Pipe Fire Sprinkler System
    Video's link: • Dry Pipe Fire Sprinkle...
    19. Preaction Sprinkler System NFPA13
    Video's link: • Preaction Sprinkler Sy...
    20. Single Interlock Preaction Sprinkler System
    Video's link: • Single Interlock Preac...
    21. Double Interlock Preaction Sprinkler System
    Video's link: • Double Interlock Preac...
    22. Main Components of Fire Fighting Pump Room Part-1
    Link: • Main Components of Fir...
    23. Main Components of Fire Fighting Pump Room Part-2
    Link: • Main Components of Fir...
    24. Main Components of Fire Sprinkler System Part-1[Except Pump Room]
    Link: • Main Components of Fir...
    25. Main Components of Fire Sprinkler System Part-2 [Except Pump Room]
    Link: • Main Components of Fir...
    26. Testing of Fire Sprinkler System & operation of ZCV assembly
    Link: • Testing of Fire Sprink...
    27. Zone Control Valve | ZCV | Wiring Connection | Fire Alarm Panel
    Link: • Zone Control Valve ZCV...
    28. Fire Hydrants Locations and Distribution as per NFPA-1
    Link: • Fire Hydrants Location...
    29. Fire Hydrant Classification and Marking as per NFPA 1 and NFPA 291
    Link: • Fire Hydrant Classific...
    30. Fire Hydrants | Maximum Fire Flow Capacity | NFPA 291
    Link: • Fire Hydrants | Maximu...
    31. NFPA 1 Fire Code | Fire Flow Requirements of Buildings | Single-family dwellings | Part-1
    Link: • NFPA 1 Fire Code | Fir...
    32. NFPA 1 Fire Code | Fire Flow Requirements of Buildings | Single-family dwellings | Part-2
    Link: • NFPA 1 Fire Code | Fir...
    33. Automatic Circulation Relief Valve for Fire Pump NFPA 20
    Link: • Automatic Circulation ...
    #TanweerAhmed #nfpa20 #firefighting #firepump #pressure #sensing #line #mep #nfpa #pump #pressureline #sensingline
    = YOU CAN FOLLOW ME ON SOCIAL MEDIA =
    WEBSITE: engineertanwee...
    FACEBOOK: web.facebook.c...
    INSTAGRAM: / tanweersethar
    LINKEDIN: / tanweer-ahmed-00142631
    RUclips: / tanweerahmed
    TIKTOK: vm.tiktok.com/...
    TELEGRAM GROUP: t.me/hvacmepenggg

Комментарии • 53

  • @MMAli-nj8xl
    @MMAli-nj8xl 10 месяцев назад +1

    how much distance should be maintained between check valve and 90 deg. elbow in sensing line? is there any requirement for this

    • @TanweerAhmed
      @TanweerAhmed  10 месяцев назад

      Minimum distance should not less than 5 feet from check valve to check valve of sensing line is given in NFPA 20 but maximum limit is not provided therefore follow maximum distance as per site conditions.

  • @MirBaqirAliSethar
    @MirBaqirAliSethar 3 года назад +1

    Very good and informative

  • @jagsingh8324
    @jagsingh8324 Год назад +1

    Tanweer, always like your video. Please make videos on NFPA 25.

  • @sunilbhatt4490
    @sunilbhatt4490 3 года назад +1

    Bhut achi class sir🇮🇳🇮🇳

  • @abdulmajeeth3135
    @abdulmajeeth3135 3 года назад +2

    Thanks for sharing and can you explain how to testing for fm200 and testing for fire pump?

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      InshaAllah I will

    • @chetanmhatre8780
      @chetanmhatre8780 3 года назад +1

      Hi sir,
      How to zone high rise building to use multi stage pump?

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      Floor zones and height zones are different

  • @abbassetharofficial9169
    @abbassetharofficial9169 2 года назад +1

    Informative 👍👍

  • @aliraza-to5pf
    @aliraza-to5pf 3 года назад +1

    Both NRVs should be in direction from panel to pump discharge line or only one near to panel?

  • @thefirefighter8417
    @thefirefighter8417 Год назад +1

    Hi.. i have doubt..
    Why there is two check valves in sensing line .. for dampening purpose one check valve is enough , right?

  • @vasimwadkar7834
    @vasimwadkar7834 Год назад +1

    Bhai mujhe booster pump ka suction header aur discharge header change karna hai.. to mujhe pressure vessel ka line kholne se pehle kya procedure follow karna chahiye

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      Follow equipment manufacturer guidlines

  • @riannjamesvisto9471
    @riannjamesvisto9471 Год назад +1

    Hi. Is this applicable if the system has an Alarm Check Valve?

  • @atif-aftab1atif330
    @atif-aftab1atif330 2 года назад

    Sir deisel pump start to automatically hota hai... Sir isko off manually kiya jata hh ya off bhi automatic hota hai please answer ...

  • @sunilraju7710
    @sunilraju7710 2 года назад +1

    Engr Tanver Pl explain valves with zoomed schematic drg

  • @aliraza-to5pf
    @aliraza-to5pf 3 года назад +1

    Can we use brass pipe for sensing line?

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      As per NFPA requirement is copper tubes and stainless steel tubes. You are following standard requirements or not, now it's up to you.

  • @Zeekay80970
    @Zeekay80970 2 года назад

    Aoa,
    Hope you are doing well and fine.
    Sir plz confirm that Pressure sensing line can be connected with horizontal split case pumps only as it comes with seperate control panels like for jockey we have separate control panel for electrical pump we have separate control panel like wise for standby pump.
    What about end suction pumps on which single control panel provided with pump set EDJ. ?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад +1

      Kindly watch video, all detail is explained. Sensing line provide separate for each pump

    • @Zeekay80970
      @Zeekay80970 2 года назад

      Ok sir thanks

  • @TheMentorFESH
    @TheMentorFESH 2 года назад

    On an external Fire Hydrant line, is there any minimum requirement to put pressure gauges? Like any specific distance, or on each fire hydrnt?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад +1

      Pressure gauges shall be installed only in fire pump room. During testing of fire hydrants, pressure gauge arrangements will be arranged.

  • @sunilraju7710
    @sunilraju7710 2 года назад +1

    Engr Tanver Pl show drg in the full screen

  • @satishindia5357
    @satishindia5357 6 месяцев назад

    In what case pressure sensing line is not required?

    • @TanweerAhmed
      @TanweerAhmed  6 месяцев назад +1

      When fire fighting system is not installed 😄

  • @atif-aftab1atif330
    @atif-aftab1atif330 2 года назад

    Electric pump diesel pump both I'm talking.. band kaise hota hai automatic ya manually bnd krna parta hai.

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      Electric fire pump on & off automatically. Diesel fire pump on auto and off manually

  • @dilshadkhan8990
    @dilshadkhan8990 3 года назад +1

    I have 1000gpm electrical and Diesel pump but running time 400gpm getting not going above

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      How did you know that flow is 400gpm and not flowing more?

    • @dilshadkhan8990
      @dilshadkhan8990 3 года назад +1

      @@TanweerAhmed showing the gpm meter

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      It will be physically checked either problem in pump, flow meter, installed pipes or somewhere else

  • @pinoyrakista
    @pinoyrakista Год назад +1

    Pls provide English subtitles 😊

  • @niazafridi3651
    @niazafridi3651 5 месяцев назад +1

    تنویر صاحب اسلام علیکم
    عرض یہ ہے کہ آپ نے یہ بتایا کہ دو چک والو لگانے ہیں جن کے درمیان پانچ فٹ کا فیصلہ ھو اور ایک میں حول بتایا جو کہ ڈھائ ملی ھوگا اور دوسرا چک والو بھی لگا نا ہیں جو پمپ کی طرف ھوگا آ یا اس کو بھی الٹا لگانا ہیں یا سیدھا اگر سیدھا لگانا ہیں تو پھر تو اس میں حال کرنے کی ضرورت نہیں۔ اور اگر اس کو بھی الٹا لگانا ہیں تو پھر اس میں بھی حول کرنا پڑیگا۔ آپ اس کی وضاحت فرمائیں پلیز۔ اور دوسری بات۔ جو چک والو ہیں اسکا جو ڈسک ھوتا ہیں ٹھیک اس کے درمیان میں سونگ کا نٹ لگا ھو تا ہیں۔ تو پھر حول کیسے کیا جائے۔ میں آپکا سبسکرائبر ھو انتظار کروں گا شکریہ

    • @TanweerAhmed
      @TanweerAhmed  5 месяцев назад +1

      وعلیکم سلام، آپ کو ڈرائنگ کو دیکھیں جو این ایف پی اے 13 میں دی گئی ہے، فر آپ کے بہت سے سوالوں کے جواب مل جائیں گے۔ اور ڈسک میں سوراخ کرنا ہوتا ہے جو چیک وال میں لگی ہوتی ہے۔ مزید اور ویڈیوز اور ڈرائنگ کو اسٹڈی کریں جیسے آپ کے سمجھنے میں آسانی ہو ۔

  • @TheMentorFESH
    @TheMentorFESH 2 года назад

    Are you CFPS ?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад +1

      No

    • @TheMentorFESH
      @TheMentorFESH 2 года назад +1

      @@TanweerAhmed You must try it. You have a very good knowledge.

    • @TanweerAhmed
      @TanweerAhmed  2 года назад +1

      What is the requirement?

    • @TheMentorFESH
      @TheMentorFESH 2 года назад +1

      @@TanweerAhmed Ye bhi sahi he. Good, if we have some certificates as a Consultant

    • @TanweerAhmed
      @TanweerAhmed  2 года назад +1

      👍