Finding Low Voltage Shorts Fast! HVAC Troubleshooting!

Поделиться
HTML-код
  • Опубликовано: 4 дек 2020
  • In this HVAC Training Video, I show How to Quickly Find Low Voltage Shorts with a Multimeter! Once you know where to look and how to divide the wiring, troubleshooting the problem can be done fast! Supervision is needed by a licensed HVACR Tech while performing tasks as Experience and Apprenticeship garners Wisdom and Safety.
    Tools Used In The Video
    Alligator Jumpers- amzn.to/2PxqJXn
    UEI DL479 Multimeter With Temp Sensor amzn.to/2jtsUbJ
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our Related Videos
    • HVAC Electrical Troubl...
    • How to Test a Thermost...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Educational Books, E-Books, Workbooks, Cards, Posters, and PowerPoints:
    All Our Educational Products on Our Site: www.acservicetech.com/store
    All Our Educational Products on Amazon: amzn.to/48pDd82
    Mini Split Book and E-Book on Our Site- www.acservicetech.com/mini-sp...
    Mini Split Paperback on Amazon- amzn.to/3ytHJSs
    Mini Split Paperback on TruTech Tools- www.trutechtools.com/BooksGui...
    Refrigerant Charging Book and E-Book: www.acservicetech.com/ac-book
    Refrigerant Charging Paperback on Amazon: amzn.to/46xTeHf
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Online Resources!
    Our HVAC Calculators: www.acservicetech.com/hvac-ca...
    Our Newest Articles: www.acservicetech.com/articles
    Try our HVAC/R Quizzes! www.acservicetech.com/quizzes
    Our Other Resources: www.acservicetech.com/resources
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Tools Used in Our Videos!
    Tool Links on Our Site: www.acservicetech.com/tools
    Our Tool List on Amazon: www.amazon.com/shop/acservice...
    Support the Channel by purchasing tools through TruTech Tools!
    Use this link www.trutechtools.com/?aff=8
    Save 8% at checkout using code "acservicetech"
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Follow Us On Our Social Media & Podcasting Channels!
    Patreon: / acservicetech
    Facebook: / acservicetech
    Instagram: / acservicetech
    X: / acservicetech
    LinkedIn: / ac-service-tech-llc
    Tiktok: / acservicetech
    Spotify: open.spotify.com/show/74KXLz5...
    Apple Podcasts: podcasts.apple.com/us/podcast...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    ⚠️ Disclaimer:
    Information in this video is intended for educational purposes only. Any work related to the topics in this video should be performed by licensed technicians or by apprentices under the supervision of licensed technicians. AC Service Tech LLC is not responsible for any possible damages or injuries caused by the use or misuse of any information provided. ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    #hvacr #hvacr #hvactrainingvideos #hvactraining #hvactraining101 #acservice #acservicetech #lowvoltage #short #electrical #voltage #volt #V #multimeter #circuitboard #acunit
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal.

Комментарии • 242

  • @acservicetechchannel
    @acservicetechchannel  3 года назад +6

    -Our Website has FREE Videos, Calculators, Podcasts, Articles, Tips, Quizzes, Q/A: www.acservicetech.com
    -Facebook Tips: facebook.com/acservicetech
    -Tools we use, Our Book, Workbook, and Quick Cards: www.amazon.com/shop/acservicetech
    -Our E-book, Paperback, Workbook, Quick Cards, Powerpoint, www.acservicetech.com/ac-book
    -Our E-book: play.google.com/store and search "ac service tech"
    -Spanish Book & E-book: www.acservicetech.com/store
    -Join our updates list for an email strictly from us for new videos, articles, products and website features! www.acservicetech.com

  • @jericosha2842
    @jericosha2842 3 года назад +41

    Dude I know you made this due to feedback. You're awesome!

  • @cutabove9046
    @cutabove9046 3 года назад +104

    Let me suggest a method for finding low voltage shorts without removing all those wires. First I'll be obvious, the reason the fuse is blowing is because something is shorted and therefore has very low resistance or zero resistance drawing lots of current and causing the fuse to blow. The temporary solution is to add series resistance (inline with the fuse or replacing it) to the circuit with a known level of resistance drawing less current than the rated fuse. The simple answer is to insert a 24 volt bulb in a socket with two wires or a commercial short finder (all these things are is a 24 volt bulb packaged nicely with wires). The current draw will be 2.5/3.0 amps which isn't enough to blow the fuse. The bulb will light because you have 24 volts on one side and the short giving you a ground on the other side. Grab your multimeter and wrap the current jaws around each low voltage wire on the control board until you find the wire/circuit drawing 2.5/3.0. That is the wire/circuit where your short is. Now track that wire to its termination point which could be a component. Disconnect the component and if the light goes out you found your shorted device. If it doesn't track that wire along its length to find where the wire is touching another wire or the frame of the furnace. In any case you cut your troubleshooting of the short down to five or ten minutes. You can use the same procedure on a cars, but use a 12 volt bulb. I've used this process for years to track down short on cars, furnaces and even circuit boards. I've found the current jaws on a multimeter the most underutilized item in a tool bag. Hope you find this useful.

    • @dennisnoone7427
      @dennisnoone7427 3 года назад +3

      Yes clamp meter is a great tool, makes those parasite draw much easier to find, great tip!

    • @youngjedi5599
      @youngjedi5599 3 года назад

      What would my amps be of the other low voltage wires? It never dawned on me to use my claw to read low wiring amperage?

    • @youngjedi5599
      @youngjedi5599 3 года назад

      I didn’t think a multi meter could pick up amps that low such as 2-3amps

    • @Savage-lx5yj
      @Savage-lx5yj 3 года назад +1

      Great point! Resistance testing often produces flawed results for a host of reasons.

    • @dandearman2871
      @dandearman2871 3 года назад +10

      You can use your clamp meter to measure very small AC currents. For example. If you clamp your meter on a single conductor carrying 1 amp, your meter will of course read 1 amp but if the same conductor passes through the jaws twice, now you will read 2 amps and 10 times, your 1 amp will now read 10 amps on the meter. It's not very handy to wrap a wire around the jaws 10 times and then insert that in series in the circuit you want to measure but it works. And a tip on finding a short circuit. You don't want to go crashing in on a short because in the process you may clear it and then it won't be there anymore to track down, then in a couple of weeks have the short return and the fuse blow again. I think a person is fortunate to have a dead short rather than one that is intermittent. Sometimes I also use the light in series with the load to track down shorts. I bought your refrigeration book last year and it really helped me understand the subcool and superheat I've heard about and didn't understand. It's always nice to learn something new.

  • @moeselec
    @moeselec 3 года назад +17

    Low voltage Shorts are time consuming and can get frustrating . Your "process of elimination" is well explained . I find this video very helpful to deal with this issue. Thank you very much for sharing this video.👍😊

    • @Review-This
      @Review-This 2 года назад

      I always use continuity to find low-voltage shorts.. Please explain why ohms is better then using continuity on a short to ground or common?

  • @grecomsiri1532
    @grecomsiri1532 3 года назад +10

    Beautiful, this trade is becoming more easier watching you sir. Thank you!

  • @iateyourmic
    @iateyourmic 9 месяцев назад +4

    This video helped me diagnose a short to ground from our humidifier, which was causing our ecobee to only call for heat for less than a second, and the 3 amp fuse on the furnace board to blow when contacting Rc and W1. Turns out one of the wires poking through a sharp hole in the cold air return got nicked, who knew?!
    Thank you so much, you've saved me a bunch of trouble and money.

  • @sgalford
    @sgalford 4 месяца назад +1

    Wanted to give a big thanks. Had the dreaded 3amp fuse issue on a 4yr old carrier split system. Out of all the videos I watched yours by far was the easiest to follow and quickest to resolution. Thanks for sharing your knowledge.

  • @justinwallace390
    @justinwallace390 Год назад +18

    This is a great explanation for the process of elimination. I would also recommend to especially younger technicians to get a Lil Popper fuse reset tool or something similar. They come in 3 amp and 5 amp sizes. They are helpful during the troubleshooting process so that you aren’t just burning through fuses.

    • @anthonys6187
      @anthonys6187 2 месяца назад

      I was using one the other day on a twinned system and it kept blowing the fuse on the second air handler and not my popper… I was so confused

    • @justinwallace390
      @justinwallace390 2 месяца назад

      @@anthonys6187 I have seen that happen before too. Now that everyone is switching over to cool mode, make sure the contactor is not shorted. If they are in cooling mode and you are blowing through fuses and transformers, that is likely your problem with these seasonal changes.
      Other things
      Did you try and isolate the 2nd twin from the mother system to see if it was the one popping the fuse? I naturally want to look at the outside thermostat wire to see if an animal has been chewing on it or a melted wire on the outside condenser. Sometimes the low or high pressure wires touch the hot copper line.

  • @paulklingele
    @paulklingele 9 месяцев назад

    Fantastic explanation! This helped me isolate my yellow wire which was shorting -- it was wrapped over the edge of a housing where the access door would rub on it every time the door was opened, slowly fraying the wire until it finally made contact with the housing creating a short.

  • @kitchenratt
    @kitchenratt 3 года назад +2

    I’ve done refrigeration for 30 years, I don’t get much practice on home units. Very informative! Thanks for sharing!!

  • @Phemsdasla
    @Phemsdasla 2 года назад +3

    it is the best channel for HAVC systems ... welldone man

  • @CaptainBobSVChimera
    @CaptainBobSVChimera Год назад +3

    Not sure how old this video is but it was tremendously helpful to let me today. While my problem turned out to be something unique (an unused wire from the contractor coil outside had lost the electrical tape that was shielding it and it was arcing on the cabinet) . using your guide, I was able to determine everything it was not which eventually led me outside to look at the contractor coil. Thank you!!!!

  • @MrDmadness
    @MrDmadness 3 года назад +5

    For boards I often find thermal imaging shows the blown component ( seek thermal pro for smartphone ) you can also usually spot the hot flash of the groundcshort asthe fuse trips... excellent video as always

  • @eevalobo
    @eevalobo 2 года назад +14

    To keep from making one million trips wire a T-stat to carry w/ you for the amount of wiring you need. You can use 2H/1C T-Stats for furnaces if you wire the W to your Emergency Heat in your diagnoses T-Stat. If it’s a Heat Pump set then just continue as the wiring should be applied. Attic trips are a killer, don’t forget your fuse pop switch so you don’t burn through fuses.

    • @EdenFL97
      @EdenFL97 Год назад +1

      Explain in more detail please!

  • @dillonchalk438
    @dillonchalk438 2 года назад +3

    Your vids are top notch and have helped me become a better tech for my customers and business partners! Thanks a million sir.

  • @romarro4616
    @romarro4616 3 года назад +6

    As always thank you for sharing your thoughts and knowledge

  • @Karnol428
    @Karnol428 2 года назад

    Thank you so much testing with resistance is something I was struggling with seeing in perspective like this is an eye opener

  • @Falcon-eh8tq
    @Falcon-eh8tq 2 года назад +2

    This is great, helps narrow down the search to 1 run. Thank you.

  • @TheKabeman
    @TheKabeman Год назад

    Very good tutorial on troubleshooting the low voltage side of the furnace. Thank you !

  • @freecheese4143
    @freecheese4143 2 года назад

    The explanation is very thorough.

  • @manikandandhanapal7679
    @manikandandhanapal7679 Год назад

    Fantastic explanation on every part of the hvac house. Thanks

  • @JoseTorres-ou6ue
    @JoseTorres-ou6ue 11 месяцев назад +1

    Very knowledgeable and straightforward thank you.

  • @fernandofrancisco3106
    @fernandofrancisco3106 3 года назад

    Like how you show exactly step by step on finding a low voltage short circuit. This issue is always on my job I’m the ac tech on my job we have heat pump. The units are over 10 years old and the wiring in the condensing unit is exposed to heat and cold weather mostly I find shorts on line from evaporator to condenser. Also through all the years of being used 24/7 the thermostat do fail most of the time.

  • @johnviastikopoulos9729
    @johnviastikopoulos9729 2 года назад

    Thank You !
    Extremely Informative and much appreciated. Keep up the amazing work.

  • @gillcorona9615
    @gillcorona9615 3 года назад +2

    You are a Great! teacher for that reason i purchased your books.

  • @logancook4790
    @logancook4790 3 года назад +1

    I love your videos you guys really do stuff the right way and you've helped me learn a lot

  • @brianmcdermott1718
    @brianmcdermott1718 3 года назад +1

    Great troubleshooting tips Craig. Thank you.

  • @MaMa-qh4dy
    @MaMa-qh4dy 3 года назад +2

    Easy to follow detective work!

  • @jimmysegovia2688
    @jimmysegovia2688 3 года назад +1

    awesome craig! thank you so much for sharing! alway's lovin your video's!.

  • @thetheDMT
    @thetheDMT Год назад

    excellent troubleshoot, you are a pro, much appreciated ✌️

  • @downformineyoutubelist
    @downformineyoutubelist 2 года назад

    Nice ! Keep up the positive outpouring

  • @Gabe0220
    @Gabe0220 3 года назад +2

    Thank you for sharing your knowledge 👍

  • @tptm100
    @tptm100 Год назад

    Excellent Video, very good visual and explanation.

  • @bill944
    @bill944 3 года назад +3

    Once again, great video and explanation.

  • @TaddyDigest
    @TaddyDigest 3 года назад +1

    Great video I love the set up the app it's a great learning

  • @KwabenaKirikou
    @KwabenaKirikou 3 года назад +1

    Thanks. Very simple.

  • @hvacguy542
    @hvacguy542 2 года назад

    Love your content. I work industrial HVAC for a plant 8,000 tons of cooling and forget the residential stuff sometimes. Helps with side work lol.

    • @Turtle-sz7sk
      @Turtle-sz7sk Год назад

      What type of plant needs that much cooling? That’s mental

    • @hvacguy542
      @hvacguy542 Год назад

      @@Turtle-sz7sk I work at a very big airport it is mental lol

    • @Turtle-sz7sk
      @Turtle-sz7sk Год назад

      @@hvacguy542 wow wouldnt want that elect bill lol

  • @raybunting7398
    @raybunting7398 2 года назад +1

    I love and watch a video just about everyday..

  • @joseenciso5925
    @joseenciso5925 3 года назад +13

    Craig i appreciate all your time and effort u put into your videos thanks for helping all of us that are starting out u have teached me alot and thanks to u i have hope to one day have my own company ur very inspiring to all of us i want to let u know that god bless your family always thanks for helping us all out man your an awesome human i admire u

    • @anthonynguyen8031
      @anthonynguyen8031 11 месяцев назад

      he's been a great help for us guys starting out for sure!

  • @Ted_E_Bear
    @Ted_E_Bear 3 года назад

    Good to know !

  • @goldhammer561
    @goldhammer561 3 года назад +2

    Great video thanks for sharing

  • @jadklafjkejalka
    @jadklafjkejalka 7 месяцев назад

    Thank you for posting this!

  • @tntheatingandairllc
    @tntheatingandairllc 3 года назад +1

    Great video buddy very helpful 👍👍

  • @brianb5779
    @brianb5779 3 года назад

    Awsome info, thank you for sharing.

  • @stanleykania7184
    @stanleykania7184 Год назад +1

    Watching this again

  • @freecheese4143
    @freecheese4143 2 года назад

    Its like the basics explained in a simple way.

  • @gotchaplumber
    @gotchaplumber 2 месяца назад

    Great low voltage short video!

  • @TeslaBoy123
    @TeslaBoy123 2 года назад

    Thank you sir 👍👍

  • @tedfurth1569
    @tedfurth1569 9 месяцев назад

    Great video. Saved me a bunch of cash. Thank you!!!

  • @toolemanful
    @toolemanful 3 года назад +1

    Greatest video so helpful

  • @cani6767
    @cani6767 3 года назад +1

    Thank you so much for the easy to understand troubleshooting for the new techs. I will have to watch it a few times to let it sink in.

  • @kennethdandurand3472
    @kennethdandurand3472 3 года назад

    Aww, and I thought you were gonna tell us what the magnet was for. Oh, well, loved the isolation procedures! Thanks.

    • @michaelguido7505
      @michaelguido7505 3 года назад

      It’s to close the door switch so power can run with blower door off

    • @joehead1294
      @joehead1294 3 года назад

      Probably to hold the door safety switch closed.

  • @LesAkl
    @LesAkl 2 года назад

    Great video

  • @fabiandelarosa6987
    @fabiandelarosa6987 3 года назад +1

    Great job!!!!

  • @OthmanAlikhan
    @OthmanAlikhan 2 года назад

    Thanks for the video =)

  • @rocker8692
    @rocker8692 Год назад

    21.1 jigawatts, Great Scott

  • @Googlename699
    @Googlename699 5 месяцев назад

    Thank you

  • @marcusdarnell3348
    @marcusdarnell3348 3 года назад +1

    Thanks

  • @cutabove9046
    @cutabove9046 3 года назад +2

    Want to find a short even faster than my suggested method using current jaws? First, use the technique explained in my previous post by adding serial resistance with a 24 volt bulb in place of the fuse or in series with it. This will prevent the circuit from blowing the fuse while allowing it to remain active drawing somewhere around 2.5 amps. Next drag out a Thermal Imaging Camera and look over the wires and control board (remember all wires whether from the thermostat or outside units terminate at the control board). The shorted circuit will be obvious. Thermal imaging cameras can be had pretty cheap these days and worth adding to your tool kit. Hope this suggestion helps in your troubleshooting.

    • @armandorodriguez6447
      @armandorodriguez6447 2 года назад +1

      Wowe I’ve got the tools in my van. I’m purposely going to cause a short and test it. Good advice

    • @Curious0189
      @Curious0189 2 года назад +2

      Film a RUclips video showing us in field footage.

  • @brent562
    @brent562 3 месяца назад

    Thank you. This video taught me something today. Where can I send you a check 😅😂. The hats seem nice I’ll take better look when I get home great job explaining

  • @harkamagar201
    @harkamagar201 6 месяцев назад +1

    good morning Craig! all of your hvac articles, videos and books are very clear and well explained. I got your mini split hvac books from Amazon and I am still learning it so far very helpful. so. common and ground are same because they are touching each other. when hot wire touched to the ground it will just blow the fuse but if hot wire touch the common directly than it will blow the transformer with fuse. but common and ground are same on the other hand. why short with common directly will kill transformer not just the blow the fuse?

    • @acservicetechchannel
      @acservicetechchannel  6 месяцев назад +2

      It will still blow the fuse but may also blow the transformer because both hot and common are connected to the transformer. Hot to ground will still blow the fuse but is less likely to blow the transformer unless the path of least resistance is back to the common on the transformer. regardless, we do our troubleshooting with blowing fuses or breakers and by using electrical resistance measurements, thanks!

  • @matthewforestieri6895
    @matthewforestieri6895 3 года назад

    thank you

  • @cecilyt006
    @cecilyt006 2 года назад

    BOSS LEVEL!

  • @lpsrt
    @lpsrt Месяц назад

    Sweet video ! I just ran into this issue. When I turn my thermostat to either AC or the heat pump, it blows the 5amp fuse on the board inside the furnace unit. If I use just electric heat, then no issues.
    I isolated the short to the yellow wire by unhooking it from the AC unit outside. I turned my thermostat back to cool and the fan on the furnace came on with no issues and the fuse didn’t blow again. I decided to use the spare wire from the outside unit and used the black/white wire. Once that was hooked up again, the fuse blew as soon as I requested cool. What I also noticed on the board where the wires hook up, is that I have 2 wires on the same connection. (Yellow and white, but now black/white and white). It’s an older unit so I don’t have wires at my thermostat to test. I did trace the thermostat wires from the furnace unit and put together the new black/white wire with the white wire. Now the fuse no longer blows when I switch it to cool, but now my outside unit is not switching on. Any ideas ? 🥲

  • @practicemakesbetter7132
    @practicemakesbetter7132 3 года назад +3

    Great video, I found a rare problem when troubleshooting a circuit board fuse problem. The contactor coil in an outdoor unit was the culprit, I measured the resistance of the coil and to ground both readings were normal. When 24 volts was applied the fuse blew instantly, the only symptom I found after removing the contactor was that the contactor had a burnt insulation smell. Normally when a contactors coil is energized with 24 VAC a magnetic field is produced opposing electrical current, because the coil insulation was damaged several turns of wire in the contactor shorted together. As a result the coil did not produce a magnetic field allowing excessive current to flow through the coil destroying a 3 AMP fuse.

    • @Swoliosis1
      @Swoliosis1 Год назад

      Was that the permanent fix?

    • @practicemakesbetter7132
      @practicemakesbetter7132 Год назад

      @@Swoliosis1 That was the permanent fix, the original AC contactor was damaged due to faulty wiring when the owner changed his furnace circuit board. After properly installing a new circuit board and replacing the AC contactor the problem was solved.

    • @Swoliosis1
      @Swoliosis1 Год назад +1

      @@practicemakesbetter7132 We recently had some very bad storms in my area... a day later, my system blew the 3 amp. Replaced it, blew again instantly as soon as the contactor energized.
      Checked all over for shorts... replaced fuse, disconnected contactor... fuse did not blow at FAN ON or COOL ON. Replaced contactor, system now works. Contactor tested at ~16 ohm.. not shorted to ground. Don't know?

    • @practicemakesbetter7132
      @practicemakesbetter7132 Год назад +1

      @@Swoliosis1 Good job finding the bad contactor fault! Normally when 24 volts AC is applied to the coil of a contactor, the coil produces a magnetic field that impedes the flow of Alternating Current thru its coil. Because the coil windings were damaged, there was no magnetic field created and there was very little impedance to the flow of current thru the coil; that is why the 3 Amp fuse blew when 24 volts was applied to the coil.

    • @Swoliosis1
      @Swoliosis1 Год назад +1

      @@practicemakesbetter7132 About 72 hours out and we're still running...
      The DIY videos, web sites, etc... don't really talk about parts still being bad, even though they measure well (by typical methods). Maybe at the moment the contactor engages and/or under load it exhibits the symptoms and only then. If so, may need a lab setup to prove it... either way, old contactor in the trash.. ordered a new one for $10...

  • @shawnrender6935
    @shawnrender6935 3 года назад

    Awesome

  • @1calledChuckles
    @1calledChuckles Год назад

    Thank you for the help you've given me so far. I determined that I have a low voltage short coming from my AC compressor (read 0.5 ohms instead of 15-20 ohms). Do you have a video for troubleshooting at the compressor that I can watch?
    Thanks.

  • @acrepairnearme
    @acrepairnearme 3 года назад +1

    Great tips!))))))

  • @aliso-pv7ll
    @aliso-pv7ll 3 года назад

    On the 3A fuse protection for the transformer, which is best, fuse on the primary or secondary? Thanks for your fine videos.

  • @zesty2023
    @zesty2023 3 года назад

    *sees title* well that could be useful yes!

  • @yaseenhashim8538
    @yaseenhashim8538 2 года назад

    awesome

  • @douglieberman6406
    @douglieberman6406 Год назад

    I have seen in another application of the secondary of the transformer that the common wire connected to ground would have to have a diode from anode to cathode and cathode connected to ground that way the back current cannot go back because the diodes reverse bios will stop any back current flow!

  • @artolivares3506
    @artolivares3506 3 года назад +1

    Great video. How do you fix an issue where the problem Is not a direct short where the fuse doesn’t blow right away.
    I

  • @viper22304
    @viper22304 Год назад

    thanks for sharing. Questions: does anyone know what it means if you do get a resistance reading, for example: common to green, instead of OL?

  • @joemcorbett
    @joemcorbett 3 года назад

    Another quick way to find it is to unhook the tstat and cu wires. If fuse blows problem is inside furnace. Hook them back up one at a time with the call on that's blowing fuse. When the fuse blows you've found the bad wire. Most times it's outside in the weather.

  • @josephl728
    @josephl728 3 года назад

    very common too...dog bite on the control wire into condenser (to contactor coil) causes a short.

  • @kevinvega1572
    @kevinvega1572 6 месяцев назад

    I have a question on the harness which was the first wire you stuck your lead too ???

  • @markharris9647
    @markharris9647 Год назад

    When you pull the fuse out and test red and common do you take the other wires off or you leave them connected

  • @ThelifeExperiment
    @ThelifeExperiment 3 года назад

    If you have a resettable 3 amp breaker is it possible to insert that into the fuse spacing and use it to diag the system? Just to prevent burning multiple fuses?

  • @acrepairnearme
    @acrepairnearme 3 года назад

    Once I saw how the metal tape insulation was touched inside part of the high temp limit switch. The problem was appearing sometimes. And that playing price of metal tape was a conductor for the shortage. And it blew up the fuse sometimes.

    • @kennybaker16
      @kennybaker16 Год назад

      This right here is an underrated comment. Ive had it happen 2 times and let me tell you it needs to be addressed because shit gets real when its 130 in the attic looking for these lol

  • @youngjedi5599
    @youngjedi5599 3 года назад

    Testing the resistance of the board last are you still looking for a low value resistance of .5?

  • @jjjames5089
    @jjjames5089 3 года назад

    Great stuff! However, I'm confused how a low voltage wire from a transformer which is not grounded could possibly give any worthy reading, if the hot or common wire accidentally touched the frame anywhere.

  • @paulstandaert5709
    @paulstandaert5709 Год назад

    I recently dealt with an HVAC company who someone else called to fix something. He blew up THREE transformers before he told me that there was a dead short in the thermostat wires.... Which I already knew and already told him.
    Why didn't I just do it myself? I was working there temporarily and i didnt make the call and i was too busy to deal with it. Ultimately, I used an unused wire to the stat as a substitute.

  • @kengxiong7007
    @kengxiong7007 Год назад

    This video is very helpful but I am still having issues. I have a split system, AC and heat. I tested the system similar to what you did. I have two sets of thermostat wires going into my FAU. The ones from the Thermostat does not trip my fuse. When I plug in the thermostat wires from the AC unit outside It trips the fuse. I even tried switching the wires and still trips so its not a break in the line or grounding issue. Any ideas on what it could be? I am replacing the AC capacitor as a last resort of something cheap before calling an HVAC.

  • @RobertoCarlos-re3uw
    @RobertoCarlos-re3uw Месяц назад

    I wish you put videos on vrf /vrv

  • @cullenrahman3561
    @cullenrahman3561 3 года назад

    I feel like the short pro tool is easier than this way but this is great info!

    • @cullenrahman3561
      @cullenrahman3561 3 года назад

      @Andy Peek watch some videos on it, it changed my life on how I diagnose shorts

  • @RayRay-nb7tn
    @RayRay-nb7tn Год назад +1

    Do you have a 24v trouble shooting card made up? Easy to keep the the truck.

  • @Duck1cVE
    @Duck1cVE 6 месяцев назад

    Do you have to disconnect the wires on the board in order to get proper ohm readings? I noticed it had a measureable resistance when it was connected to board and not OL even though nothing was calling and the power was off. Can you explain it? I'm just curious as to why it wouldn't read OL, i would assume the wires aren't touching on the board until a call is made

  • @JustPlumDucky
    @JustPlumDucky Год назад

    Where'd you get that magnet for the door switch? Approximate O.D. diameter please. Thx much!

  • @clambert2370
    @clambert2370 2 года назад

    I had a house on Friday where there with a 6 zone pneumatic zone control. After about 2 hrs of tracing a maze of wires, there were no marrettes on the humidifier, and they were touching the duct work. The ac low voltage wire was also bad inside a finished ceiling, and the R wire entering the zone control was broken and touching the case of the box. It was a mess.

  • @sterlingarcher46
    @sterlingarcher46 3 года назад

    Very good explanations mate 👍
    By the way , how do you like your UEI meter , I hear both sides , some say they're good some say they're not reliable or precise enough?
    Cheers mate 👍.

    • @jericosha2842
      @jericosha2842 3 года назад +1

      A UEI meter is good. They are a good price for their accuracy. The biggest difference you will notice between them and higher end Flukes is millivolt and small ohm resistance readings. Rarely do you need that much precision when diagnosing anything, especially residential. I bought a very expensive Fluke and while it's good and reads capacitance on capacitors MUCH faster than my lead techs UEI, it's not really worth the money/hype. Also I like that UEI meters have a magnet on the back making it easier. Only thing that I hear consistently is that Flukes tend to last really long.
      Just make sure you get one with "true RMS."

    • @sterlingarcher46
      @sterlingarcher46 3 года назад +1

      @@jericosha2842 Cheers mate

  • @0664arn
    @0664arn 3 года назад

    Awesome videos and I just placed an order for your book Refrigerant Charging and Service Procedures for Air Conditioning Spiral-bound - May 24, 2019
    by Craig Migliaccio (Author)from Amazon. thank you

  • @444teach
    @444teach Год назад

    Hello sir. Do you know what would cause the outside ac unit fuse to blow. I replaced the capacitor already. Thanks

  • @mikellandrum6673
    @mikellandrum6673 Год назад

    I dont have a control board. I have a blend air box. Would that affect how I test for this.

  • @aa-ron1596
    @aa-ron1596 2 года назад

    Hello, If a compressor was recently replaced in January and not cooling due to low freon, and constantly running and trying to cool the house but the temp keeps rising, could this constant load of the compressor trying to cool with low freon for hours cause a disconnect to short out?

  • @brianaustin8136
    @brianaustin8136 3 года назад

    So I have a honeywell smart wifi thermostat and a carrier gas furnace. Whenever I run the heat and the furnace does it's heat cycle, soon as it goes into 90 second cool down where the fan keeps goin but the furnace isnt calling for heat my thermostat cuts off and then restarts once it's done. Any thoughts?

  • @douglieberman6406
    @douglieberman6406 Год назад

    I have installed transformers and the metal frame of the transformer is connected to. Ground and as I understand the bare copper wire is connected to the ground frame terminal and back to the service disconnect ground terminal which then goes to the ground rod to earth ground.

  • @stevealoia
    @stevealoia 2 года назад

    I had one today. The led was in standby mode. As I was testing I crossed W with R
    Blow the fuse. But didn’t blow the fuse when
    The thermostat called for heat . The furnace didn’t come on . As I was going through the troubleshooting I found it . The high limit switch was shorted to the frame .

  • @huflungpu4456
    @huflungpu4456 2 года назад

    Do this exact thing with a basic gas garage heater. I unplugged everything from the board and it still blows the fuse. I ordered a new board after running out of options.

  • @chenchris7576
    @chenchris7576 Год назад

    How are you sir, i want ask you a question, can l replace resettable transformer to a normal transformer, instead burning the transformer l can just reset the switch??? Thank you