Here is the troubleshooting I did in our provision refrigeration system #ETO #marineelectrician #leckyjake #refrigeration #evaporator #seaman #seafarer
Your videos are the most simplified and well explained. Keep posting such. It has been a great practical knowledge booster for many of the youngsters like us😊👍🏻
As always excellent and informative video keep them coming. This is a common problem I’ve encountered this many times but the Chief just had me use hot water to break up the ice 🧊
Kindly it would be nice to elaborate on superheat thing. First of all if the system was running fine before this problem happened and there was no work done on the TXV of veg room . So why to solve the problem we have to open the TXV more . As we know it has been set by factory before it was fitted as per requirement of the system. That clearly says that TXV should automatically open more as per the operational requirement. That means opening pressure due to the bulb sensing is not sufficient to maintain the superheat. Though the action solved the problem but I feel if TXV is malfunctioning then it needs to be changed so that it maintains the temperature in the previous setting of the TXV.
Risk to open too much is flooding back and damaging the compressor. However, at sea those TXV are subject to a lot more mechanical disturbance than on land.
its up to you to research,. they teach you what you need to know the rest is up to you. your going to have to learn how to learn. you will have to start thinking for your self now, no one can teach you everything, no one!
Thankyou sir very informative .. seaferer din ako passenger vessel mag isa lang din po ako na reefer dito ... upload ka din sir sa trouble ng chiller compressor
Good job sir jake kaya pala nag ice build up yung evaporator ng chiller dahil d wastong pagset yung TXV..lage po ako nanonood sa vlog nyu sir.sana palarin gaya nyu po.
thank you for making very informative video -as you mentioned at the end waiting video regarding other problems facing on refrigeration ,keep doing very good work lecky
Hi,, thanks for the vedio which is very usefull.. Lecky,, I have a same trouble which is Ice deposit on expansion valve. I have cleaned inside filter and run the system. But trouble is remaining still. Unfortunately , I dont have a spare one onboard ...😒
Hi Elect, thank you for the video, just curious if the vegetable room have evaporator pressure regulator since the piping is interconnected with meat and fish freezer? Means both suction pressure are the same. Provision compressors on this video is Bitzer / Sabroe open type.
Dear Jake, Icing on evaporator ,so you reduced the super heat by turning it into counter clock wise. Actually here, superheat was "increased". I believe it's done after turning the adjustment screw to "clock wise ."
Our Blaster Freezer room (-40C) frequently have icing on the floor (we have proper door with gasket and curtain strips but hot air from outside or products when we push the hot product into the room to freeze them). Our floor has changed to use PU to reduce icing and anti-slip yet still have this issue... do you have any suggestions?
I liked the video.,yes there is a great responsibility to keep the system going,out at sea.Water is the superheat U maintain on this cooler? In future show us the superheat setting
Hi! Lecky Jake good day to you. Elect I have a question maybe you can help me. My question is, what is the common caused or the problem of the Cylinder head and the line in Marine Refrigeration Icing?
How we know we increased or decreased superheat by turning the screw.is there any marking for clock wise and anticlock wise for increased or decreased the superheat
Gmg sir saw ur vidio on no spare of txv.how to make. And troubleshooting for icing on evaporator.thanx Best regards Imran kazi 2nd engineer Teekay tanker ship mgmt.
Hello leckay goo day! may tanong lang po ako sa reefer provision namin ang MEAT ROOM hindi mag auto start...pero mag auto stop naman? Pls. share your a good idea..
Good day sir lecky may tanung po ako tungkol sa MGPS nmin dito, kasi may voltahi nman papuntang cells nya ang problima walang current reading sa or no current indicaes at ammeter. Thank you sir lecky isa narin po akng electrician sa barko dito sa cebu interisland lang muna sir.
Okay I love you videos but you do know you should mention to people if you take off a solenoid coil when it's energized that you going to end up burning up the coil
Thank you for this video. I still have a question, how do you know the level of the refrigerent is okay? And how do you assess the evaporators on your meat and fish room are still good?
For the level, check your pressures, and on the sight glass you will see the level. For the evap of meat room and fish room, no ice to thaw on the grill and the temperature is in range.
So is the same compressor running all 3 rooms? I was curious on refrigerant level as well but did not see any gauge readings. Nice video. I would like to see a little more testing before your determination. Thank you. Im about to get certified but lack experience because of covid schooling turned to online.
@@SCAMATICS777 Its the same as a multi split system AC. no difference, dont confuse yourself with labels, look at what they are, just a pump cycle with switches and relays, oh and mini switches and relays (PCB's). easy as pie, a trained money could do this work. im living proof.
You can see the refrigerant level on the sightglass paced on the condenser unit wich should be at middle the liquid level. Furthermore the temperature from fish and meat room are both in range -18 °C, also you can see the refrigerante gauge from low pressure the indication should be about 1 bar or higher with one of the chamber are working, i hope this make sense and can help you.
Napaka systematic mo talaga sir pag apporach sa problem. Thumbs up!
Thank you and sana meron ka din sayo na yung convinient ka sa ginagawa mo. Safe sailing
Informative and on point- thanks for putting this together!
Thanks leaky Jake hope can hear more knowledge from you
Thanks for sharing this refrigeration information, along with your electrical information as well! 🙂
Very Nicely explained. I am excited to see your next video on Provision refrigeration troubles. Thanks
Your videos are the most simplified and well explained. Keep posting such. It has been a great practical knowledge booster for many of the youngsters like us😊👍🏻
Thank you very much. Next video is the modification of wiring diagram
very informative Elec. thank you
Thanks a lot for sharing your thoughts
Thank you Jake... expecting more videos related to refrigeration and air condition....Thank you...😊
Very good video and explained. I am excited to see your next video on Provision refrigeration troubles. Thanks
As always excellent and informative video keep them coming. This is a common problem I’ve encountered this many times but the Chief just had me use hot water to break up the ice 🧊
Godbless po!,please keep posting such knowledge and ideas👍👍👍
Sir salamat Po sa mga idea ng mga troubleshooting..
❤️Keep safe all
Thanks for your video sir. It's very helpfull 🙏.
Very informative sir thank you for sharing your expertise ingat lagi SA paglalayag God bless
Excellent,,
Kindly it would be nice to elaborate on superheat thing. First of all if the system was running fine before this problem happened and there was no work done on the TXV of veg room . So why to solve the problem we have to open the TXV more . As we know it has been set by factory before it was fitted as per requirement of the system. That clearly says that TXV should automatically open more as per the operational requirement. That means opening pressure due to the bulb sensing is not sufficient to maintain the superheat. Though the action solved the problem but I feel if TXV is malfunctioning then it needs to be changed so that it maintains the temperature in the previous setting of the TXV.
😊
Risk to open too much is flooding back and damaging the compressor. However, at sea those TXV are subject to a lot more mechanical disturbance than on land.
Nice very informative video. Just piece of advice much better and safer to use water in defrosting expansion valve.
Good share from kabayan base on his experience faced on board ship recently as it also can advance to someone else knowledge about fridge system...😊
Thank you for the knowledge. Keep it up!
Thank you for your support
Your video cover much more than what institutes teach us. Awesome video 👌🏻
its up to you to research,. they teach you what you need to know the rest is up to you. your going to have to learn how to learn. you will have to start thinking for your self now, no one can teach you everything, no one!
Excellent!
Great job✅
Very Nice . Thank you.
Nice bro, thank u for the knowledge
Thank you sir lecky for another knowledgeable ideas.
Thank you for your good comments
Thankyou sir very informative .. seaferer din ako passenger vessel mag isa lang din po ako na reefer dito ... upload ka din sir sa trouble ng chiller compressor
thank to your sharing kabayan God keep
bless you
Nice video sir thanks
Good job sir jake kaya pala nag ice build up yung evaporator ng chiller dahil d wastong pagset yung TXV..lage po ako nanonood sa vlog nyu sir.sana palarin gaya nyu po.
Thanks for the video!!!
thank you for making very informative video -as you mentioned at the end waiting video regarding other problems facing on refrigeration ,keep doing very good work lecky
Thank you for the support
Hi,, thanks for the vedio which is very usefull.. Lecky,, I have a same trouble which is Ice deposit on expansion valve. I have cleaned inside filter and run the system. But trouble is remaining still. Unfortunately , I dont have a spare one onboard ...😒
Thank you so much sir, stay safe always!!!!
Thank you
What a cool job! Sailing the beautiful seas and keeping the vessel's systems in ship-shape!
Only a guy that has never worked on sea can say that (marine engineer with 14 years expirience)
@@pjero2005 Maybe true, but I still think Lecky Jake has an enviable job!
Thank you so much for your information
Thanks very much.
This is the best Refrigeration field for a job. Excellent trouble shooting. 9/30/2022yr
Sir please keep on update more knowledge eto videos
Thank you for the support
I'll love to be side by side with you while you do the troubleshooting,,, I'll be asking 2 million questions 😂😂
nice one Lecky Jake
Thank you for watching
Sir good job Sana mag labas ka din ng video kung paano ang adjustment ng txv sa ice machine tnx sir
Nice videos, which ships are you sailing on ?
A Lot of tHanks for the vídeo
Thanks for this video sir more power to you,anyway sir where you can bought your tool permanent magnet it is so nice?
Thank you.
What will be the problem if i get ice only on expansion valve but not on Evaporator.
Hi thx u for the content , I got confused when u lower the super heat the ice will be melted? Isn't increasing the heat will melt the ice
I am studying for eto now... Urs video r very useful to me.. Thank u
Thank you for watching
Excellent Trouble shooting a superheat adjust ment needed. 10/30 2021
Super thank you sir
Slmat sir lecky jake
Good one sir. Sir how did u adjusting the manual txv value did there is any specific adjustment value is there ah sir
Keep posting sir tnx
Hi Elect, thank you for the video, just curious if the vegetable room have evaporator pressure regulator since the piping is interconnected with meat and fish freezer? Means both suction pressure are the same. Provision compressors on this video is Bitzer / Sabroe open type.
Nice video lecky 👍🏻
Thank you for the support
Thankyou sir...very helpful ❤️
Thanks for the support
Thank You po Sir Leckyjake👍🙏☺️
👍👍👍
Sir sana next video Po charging of refrigerant..at ano procedure safety ways
how about back pressure control valve on the evaporator out let? does it function correctly? need adjustment. i guess.
Thank you sir
Dear Jake, Icing on evaporator ,so you reduced the super heat by turning it into counter clock wise. Actually here, superheat was "increased". I believe it's done after turning the adjustment screw to "clock wise ."
Are u eto
Superheat is reduced by turning anticlockwise.
Tnx for sharing,,,,
Thanks for watching
Very good vedio ..after watching yr vedio thing came in my mind Is let me first subscribe then go for next😂
Our Blaster Freezer room (-40C) frequently have icing on the floor (we have proper door with gasket and curtain strips but hot air from outside or products when we push the hot product into the room to freeze them). Our floor has changed to use PU to reduce icing and anti-slip yet still have this issue... do you have any suggestions?
I liked the video.,yes there is a great responsibility to keep the system going,out at sea.Water is the superheat U maintain on this cooler? In future show us the superheat setting
trial and error
Okay
Salamat lecky
Salamat sa idea master
Sir you are my favorite one ❤️
Lots of love 💕
Keep making knowledgeable videos and share your experience 🙏🏻
Thank you for your wonderful comment. This is what I need to keep me going
Happy to see your reply i will always support you ❤️
@@leckyjake plz give ur mail address
Hi! Lecky Jake good day to you. Elect I have a question maybe you can help me. My question is, what is the common caused or the problem of the Cylinder head and the line in Marine Refrigeration Icing?
Normaly expantion valve how many turn Jack , ❤❤❤
Very good job 👍
Sir where can you buy that magnetic solinoid tester?
Sir good day , what pressure of refregirant for low and high pressure can you say that your refrigerant is enough ??thankyou
by freezing, possibility, thermostat, coolant, or some leak in ducts etc.
How we know we increased or decreased superheat by turning the screw.is there any marking for clock wise and anticlock wise for increased or decreased the superheat
Is there any filter near the exp valve
Gmg sir saw ur vidio on no spare of txv.how to make.
And troubleshooting for icing on evaporator.thanx
Best regards
Imran kazi 2nd engineer
Teekay tanker ship mgmt.
After wait is end 🥰🥰🥰
Thank you for your support
nice galing
Sir what is hardest part of being a seafarer?
Sir please make one Vidio about how to test generator alarm for the serveay require
Hello leckay goo day! may tanong lang po ako sa reefer provision namin ang MEAT ROOM hindi mag auto start...pero mag auto stop naman? Pls. share your a good idea..
what is cause of the freezing expansion valve?
wher
which turn direction in that case sir...the ice build up problem,,,1 full turn left or right?
Sir what's the use of heat exchanger?
I talk about you new generation eto officers to watch your videos :)
Thank you very much for your wonderful comment. Very much appreciated
Defrosting procedure using water is not an excellent way of doing it. This is the old way done by old marine engineer but you have done a good job.
After long time sir
Just arrived in the port today
If thermoking sb210 does can I do same thing and it my help
Can we clean evaporator with hot gun?
Good day sir lecky may tanung po ako tungkol sa MGPS nmin dito, kasi may voltahi nman papuntang cells nya ang problima walang current reading sa or no current indicaes at ammeter. Thank you sir lecky
isa narin po akng electrician sa barko dito sa cebu interisland lang muna sir.
Check condition of anode/cathode
Okay I love you videos but you do know you should mention to people if you take off a solenoid coil when it's energized that you going to end up burning up the coil
You still sailing? did you get your refeer endorsement?
Air ano kaya problem ng meat room
May icing na rin & -3 na lng ang temp
I can see there is always lot of ice formation on the door sometime it is very impossible to open what could be the reason pls reply
Thank you for this video. I still have a question, how do you know the level of the refrigerent is okay? And how do you assess the evaporators on your meat and fish room are still good?
For the level, check your pressures, and on the sight glass you will see the level.
For the evap of meat room and fish room, no ice to thaw on the grill and the temperature is in range.
So is the same compressor running all 3 rooms? I was curious on refrigerant level as well but did not see any gauge readings. Nice video. I would like to see a little more testing before your determination. Thank you. Im about to get certified but lack experience because of covid schooling turned to online.
@@SCAMATICS777 Its the same as a multi split system AC. no difference, dont confuse yourself with labels, look at what they are, just a pump cycle with switches and relays, oh and mini switches and relays (PCB's). easy as pie, a trained money could do this work. im living proof.
Super heat and subcooling is hoew to tune a system, go look it up. you will need to know what they mean if your going for a jab,... i mean job.
You can see the refrigerant level on the sightglass paced on the condenser unit wich should be at middle the liquid level. Furthermore the temperature from fish and meat room are both in range -18 °C, also you can see the refrigerante gauge from low pressure the indication should be about 1 bar or higher with one of the chamber are working, i hope this make sense and can help you.
Sir tanong ko lang po Kung.. ano pag kakaiba ng oil separator, accumulator, liquid reciever,
Sir tanong lang po pag nag yeyelo ba ang adjust ba natin ay counter clockwise o clockwise thanks po
It simply needed an off cycle defrost timer installed or replaced. Or may have been trying to run it too cold. I doubt the txv needed adjusting.
It is actually a vegetable room so no defrost for the system
@@leckyjake How do you keep 4C in there without defrost ? In a humid enviroment in a kitchen and especially on a ship at sea.
Could you please explain the fish room tem. Not coming more then -15 dig set tem. Is -18 dig. Meat room mainten 18dig.