Should always do a 10 min (Hold) 300lb#Nitrogen Pressure Test before Pulling your Vacuum on the Line-set and indoor coil . Nice Video good luck in future Videos !
Confirmation Message from Senville:: The vacuuming process on this unit must be done as a whole, this unit has a shared manifold, you will need to open up every valve using a Hex Key / Allen Key on all the active ports (the ports that are being used, for example if you are installing 3 indoor units, there will be 3 active ports and 6 valves that must be opened). Connect your equipment to any active low side service valve and pull a vacuum, if you are considering a pressure test please do so before pulling a vacuum. Once you are confident that the vacuum is holding and no leaks are evident, only then you should go ahead and open up both master valves with a Hex Key / Allen Key to release the refrigerant. Installation Guideline For SENA/36HF/MOZ
At your place I would also have used “Nylog” and your vacuum was not done adequately, you only vacuumed your blue line since you opened the valve after the vacuum. You should have opened the 4 bottom valves before vacuuming and on one LP only, wait 30 minutes to detect leaks then when everything is perfect open the 2 “master” at the top slowly.
You did a great movie, ❤ change your BACHO tools to something neather and precice and follow some advice from your viewers ❤❤❤ too, we might be hard on you, but we love you ❤❤
@@craftsmantv7205 i am just a consumer ( i live in sweden) and just had a panasonic system installed by a tech firm, now i plan to set up a new system myself, i checking tools, how best practise is used, safety etc etc and learn before i start my project ❤️❤️❤️❤️
I always remove that corrogated hose and install a clear plastic one the grooves on the hose eventually will create mold because grooves don't allow smooth water flow
Pioneer customer service is terrible, only got back to me once out of several emails, unit build was very cheap, I eventually ordered an 18000 from Della and it was built like a tank, 22 seer with WiFi which the Pioneer didn't have and was only 18 seer, Della 18000 was the size of an 24000 due to better efficiency and price was basically the same but with a lot more features.
I believe oxygen free dry nitrogen OFDN shall use for leakage Testing and at 1.5times of working pressure in lines. The vaccum shall stand for atleast 15minutes @100micron. 16:48
My iManifold gauge would like to say otherwise on the vacume through the manifold. It’s called maintaining your gauge, change the Teflon seals, it’s a thing you should’ve learned while learning to use your equipment.
@@josezuniga4968 its called micro gauge on the liquid side ,3/4 true blue on suction ,to a 12 cfm pump with cores removed . under 100 in 5 -10 min .u dont vacume thu a manifold. as far as learning ,i have 37 years in hvac ,doubt u have more ex
When the valve is opened, the pressure is inside the pipe and indoor unit is already in there. So I tested with soap. When the unit is on during the test, the pressure in the big pipe drop so I don't turn it on the unit.
It needs a lot of tools and more people and you guys a always make it look like it’s not difficult, BUT nothing like the video, because I know, I do this for living, they never show everything, so if you doing it yourself, be ready, lol. Surprise
I want to s Ask if outdoor have one compressor but mult in door unit so how does the out door be stoped by one in door unit while the next one is running? Whe you recomend different room temperature?
மிகச்சிறந்த வேலை தோழியருக்கு வாழ்த்துக்கள்...
I love your work. I am also a Ac technician from Nigeria
You just earned a subscriber! Good job and first time I'm coming across this type of AC
Should always do a 10 min (Hold) 300lb#Nitrogen Pressure Test before Pulling your Vacuum on the Line-set and indoor coil . Nice Video good luck in future Videos !
Beautiful job. . You should hide that outlet. And put it inside that wall. Will make it nicer .
Confirmation Message from Senville::
The vacuuming process on this unit must be done as a whole, this unit has a shared manifold, you will need to open up every valve using a Hex Key / Allen Key on all the active ports (the ports that are being used, for example if you are installing 3 indoor units, there will be 3 active ports and 6 valves that must be opened). Connect your equipment to any active low side service valve and pull a vacuum, if you are considering a pressure test please do so before pulling a vacuum. Once you are confident that the vacuum is holding and no leaks are evident, only then you should go ahead and open up both master valves with a Hex Key / Allen Key to release the refrigerant. Installation Guideline For SENA/36HF/MOZ
Good & hard work my dear sister Great
Nice sharing dear your ne friend from India 🤝
Sister you did great work , very well sealed pipe, big thumbs up 👍
Tines que liberar el refrigerante antes de quitar el adaptador, si quitas primero el adaptador en precion negativa succiona un poco de aire al sistema
Mashallah nice work sister 👍
At your place I would also have used “Nylog” and your vacuum was not done adequately, you only vacuumed your blue line since you opened the valve after the vacuum. You should have opened the 4 bottom valves before vacuuming and on one LP only, wait 30 minutes to detect leaks then when everything is perfect open the 2 “master” at the top slowly.
Beau travail est merci pour le partage c'est vraiment très intéressant ❤ merci encore une fois
Nice and clean install! Where are you from?
You did a great movie, ❤ change your BACHO tools to something neather and precice and follow some advice from your viewers ❤❤❤ too, we might be hard on you, but we love you ❤❤
Thank you, I will❤️❤️❤️
@@craftsmantv7205 i am just a consumer ( i live in sweden) and just had a panasonic system installed by a tech firm, now i plan to set up a new system myself, i checking tools, how best practise is used, safety etc etc and learn before i start my project ❤️❤️❤️❤️
Замуровать гайки в стене , это гениально))
Гайки не в стене, а с обратной стороны стены на улице, это было показано и хорошо видно. В случае чего, они легко в доступе.
Nice work and good job
Nice work khalid de Maroc Casablanca
Hello sir I am new technician from Pakistan i am watching your video and like your video can you guide me in ac work please please
This unit is made by Carrier-Midea like Mr Cool units. Here in Spain we have the same one by another brand
Bon travail mérites un salut
I always remove that corrogated hose and install a clear plastic one the grooves on the hose eventually will create mold because grooves don't allow smooth water flow
Pioneer customer service is terrible, only got back to me once out of several emails, unit build was very cheap, I eventually ordered an 18000 from Della and it was built like a tank, 22 seer with WiFi which the Pioneer didn't have and was only 18 seer, Della 18000 was the size of an 24000 due to better efficiency and price was basically the same but with a lot more features.
Good essay but you should tike care of water leakage level also you should to make a oil trap !!! Anyway your installation essay it's clean
Excellent work for you and honest women god bless you 🙏
Great sharing, thanks
It's Amazing ❤❤❤ Good work 👍
I believe oxygen free dry nitrogen OFDN shall use for leakage Testing and at 1.5times of working pressure in lines.
The vaccum shall stand for atleast 15minutes @100micron.
16:48
Nice job 👍
Very well done! God bless you 😘
Good job dear
why 2 ac ? for small place ? maybe an office or something ?
Conference room.
why do you need 2 indoor units? is it so that the cold is spread across the room?
I Liked It...Your Done Perfect Instalation With Vacuum. Keepit Up Sister😍🙏
Good job
But is it only 1 compressor that is inside the outdoor unit
Yes only one compressor.
در صورت رسیدن به دمای مطلوب اگر ترموستات فرمان off بدهد چه میشود؟ @@craftsmantv7205
Super ..i am big fan
In India we don't have that 2 multi indoor AC units
Indian m nahi hai ya
Hai bhai isko multi split bolte hqi pr ye commercially use hota hai ghr me single split hota hai
So what
30 years back, it was available in India. Carrier, Voltas, Blue Star - all had it. Even LG had the Multi Split ODU with double fan.
Bhai freematch k naam se voltas india me available hai
nice videos from pakistan tecnicain
Labo fair athy v ahyo jya ac
@@sheikhshahzad6431 Yeah she is really great
Great work ! Iam from Pakistan
Nice work Bravo Bravo ❤
Good work... keep it up.
What if we purged the line instead of vacuuming?
Nice job lady air tech
Clean job
No pressure test , no micron gauge , no torque wrench 🔧, never pull a vacume thru a manifold , how not to install a mini .
She's lucky that the valves didn't break when she tightened the nuts. You're supposed to hold them with a wrench.
True @@MrJameslar
My iManifold gauge would like to say otherwise on the vacume through the manifold. It’s called maintaining your gauge, change the Teflon seals, it’s a thing you should’ve learned while learning to use your equipment.
@@josezuniga4968 its called micro gauge on the liquid side ,3/4 true blue on suction ,to a 12 cfm pump with cores removed . under 100 in 5 -10 min .u dont vacume thu a manifold. as far as learning ,i have 37 years in hvac ,doubt u have more ex
I always do that the same way she is doing
6:42 That looks like it didn't seat well. I think it will leak in future
Good job mam
Old school well done 👏
Looks like the freon was prefilled on this unit. She just purged the system and opened the valves.
Yes ..you are right.
太棒了,是个好老师
That’s insane ! 😮
Very nice job.
solid electric wire ! instead of standard wire ?
Great job.
Nice videos
Kalo di indonesia Ada Daikin Multi S Dan Gree Combo, salam dingin Dari Teknisi Indonesia
And what about the pressure test ???
The same vacuum pump does the pressure test, you just gotta leave it on the unit after vacuuming…
No
When the valve is opened, the pressure is inside the pipe and indoor unit is already in there. So I tested with soap.
When the unit is on during the test, the pressure in the big pipe drop so I don't turn it on the unit.
Will this wire be able to take such a high ampere load?
of course as long as the ampere of the wires is higher than the unit
@@craftsmantv7205 you got a subscriber multi talented girl
I agree that cable is seriously under sized to power a condenser of that size and also 2 inside units
It needs a lot of tools and more people and you guys a always make it look like it’s not difficult, BUT nothing like the video, because I know, I do this for living, they never show everything, so if you doing it yourself, be ready, lol. Surprise
Good 👍 job
Good 👍 Thank you verry verry much, its verry verry good 👍🙏 bravo 💪🙏🎩😊
Should live line two power to outdoor unit be taped black to indicate power?
Nice fetting miss❤😊
Don't you think should have more room between the wall and the condenser?
As long as it has a distance of at least 6 inches or more.
เก่งคับ สวยงาม
I want to s
Ask if outdoor have one compressor but mult in door unit so how does the out door be stoped by one in door unit while the next one is running? Whe you recomend different room temperature?
The flange service was not so good.There was double layer on the pipe.The pipe was not countersunk.
Do you love your job
Amazing girl!
Good work
Good Job
I Am Work on Repairing
How much price for this work? 🤔
Great content thx
Really informated video
Why you not try the safety shoes
I m ac technician from Pakistan 15 year experience
Why do you test for leaks in the system while it is charged with the refrigerant?
Why no need to purging after vacuum mam?
Good job
Can u just open the valves without pressure check
Do you need to put freon in these pipes?
Thread tape needed when connecting pipes to outside unit?
there is no need to use tape because the female thread will push the copper pipe flare firmly at the end of the male thread
Thanks teacher
Thank you madam❤
Which country's AC are they?
We don’t have that multi indoor unit in Nigeria. How can e get it here there are high demand here for it
Nice a vedio
Seems like the piping not been flare well
Beautiful installation
😊 nice 👍👍
Is it possible to wire these with a traditional thermostat like Google Nest, or are they already smart capable with an app?
Yes..it has a port to connect a wifi usb hub then download the apps for smartphones.
only centralized air conditioner needs an thermostat
❤❤❤Good
Do you mean 4 indoor units connected to 1outdoor unit?
1.5 tr 3 nos indoors, multy zone outdoor need
I'm AC technician from Pakistan experience 6 years ago for job
Amppaers?
Amazing
daikimeu ar condicionado quando funciona depois de um tenpo area disjuntor
Good video thanks Good 👍
The copper pipe doesn't should be cut and the vacuum isn't for time
Nice ❤❤❤
How may compressor in the outdoor unit
Just one compressor.
@@craftsmantv7205
How to wiring
Can u make one videos for wiring indoor to outdoor