HVAC Service: Replacing A Zone Damper Motor

Поделиться
HTML-код
  • Опубликовано: 28 авг 2024

Комментарии • 92

  • @markh7229
    @markh7229 Год назад +3

    Great video, only rule of thumb is to always wire and test first before sealing up. Just in case there Is a faulty replacement part. It happens

    • @jimtalor7971
      @jimtalor7971 Год назад

      Just curious why did he change the whole assembly? Aren't those motors replaceable?

  • @kraghhertel8202
    @kraghhertel8202 2 года назад

    I appreciate the tip on testing while at the damper by swapping the open/close wires. That is handy if (when) you're working alone. I think it's also very useful for test/debug when you're approaching a zone problem and don't have it narrowed down yet.

  • @davidvo30
    @davidvo30 2 месяца назад

    This is great how to video and much appreciated for taking the time to post this. How do i know which size of the damper from the ac? Thanks again.

  • @Channel-cm7yc
    @Channel-cm7yc 9 лет назад

    Hey Stephen I learned something new about zoned system equipment.
    I don't think I'd like that up north in my house with a heat pump, keeping auxiliary heat use to a minimum is tuff up here with defrost cycles and building load nose diving beyond way beyond the BTU output the of the heat pump HSPE's are way better nowadays but still not enough contrary to what most people think lol lol... We ran our heat pump system up north as stable as possible till the heat pump would lock itself out completely and backup was electric for the duration of extreme cold man that's a meter spinner up Whoo hoo... Man you guys in the south are lucky!

  • @jhhvacplumbing1944
    @jhhvacplumbing1944 9 лет назад

    Great job Stephen and explaining.

    • @StephenRardon
      @StephenRardon  9 лет назад

      justin henning Thanks Justin, Congrats on winning that tool from T&N Services LLC.

    • @jhhvacplumbing1944
      @jhhvacplumbing1944 9 лет назад

      Stephen Rardon thank u man

  • @joeschneider67
    @joeschneider67 8 месяцев назад +1

    So that zone board it's a constant power open or close? If so, then the actuator once is open or close it internally disconnect it's own power ? But the green or red light stays on to let you know the status ?

  • @jrm523
    @jrm523 6 лет назад

    Fantastic video! Thank you for taking the time to do it and also thank you for adding the extra bit of info. You should see if Comfort Solutions can set you up with a small kickback for referrals to help cover the cost of making videos. :)

    • @StephenRardon
      @StephenRardon  6 лет назад

      +Janson McCreery that would be nice! They wouldn’t come off a advertisement budget

  • @GaryVerderamo
    @GaryVerderamo 3 месяца назад

    So, there is no calibrations required?
    What about matching parts? Do certain dampers only work with certain systems or will any damper work as long as the size matches?

  • @codymon100
    @codymon100 9 лет назад

    Cool damper good job Stephen.

    • @StephenRardon
      @StephenRardon  9 лет назад

      codymon100 thanks for watching Cody, i really like that zoning equipment.

  • @BillyKnoth
    @BillyKnoth 9 лет назад +1

    See I like tour videos... You explain things so I can understand... I can't do that... I feel like I'm babbling... Nice one man!!! I like that damper setup.

    • @StephenRardon
      @StephenRardon  9 лет назад

      Billy Knoth TOUR videos?! wtf are you talking about? I guess you could say that this was a tour of the job....LOL i don't know why but i'm enjoying being a spelling nazi recently.

    • @BillyKnoth
      @BillyKnoth 9 лет назад

      I ment your.....not tour...

    • @StephenRardon
      @StephenRardon  9 лет назад

      See how easy it was, to push the correct letters when spelling properly? Lmao 😂😂

  • @RobHVAC
    @RobHVAC 9 лет назад +1

    Nice Job Stephen Rardon

  • @saintpete3573
    @saintpete3573 Год назад

    Great video! I think my first floor zone1 damper motor is dead (stuck opened). Can I confirm by swamping the Red and Black on the damper? I guess if it doesn’t close it would mean my damper is bad?
    Thanks for the video. Oh one more thing, why do you have to connect the white common wire to the new damper? Can connect the white common wire to zone2 damper?

  • @Nuro1992
    @Nuro1992 9 лет назад

    im still trying to get the hang of wiring. The other day I was staring at an old RTU, I forget what make it was but it had some where around eight contactors that controlled the different components in the unit.
    The wiring was a freaking mess.

  • @TandNServices
    @TandNServices 9 лет назад +1

    You were lucky on that one. Most of the damper change outs I get the installer most have thought there was a massive air leak at the damper and slapped a shit ton of mastic on the joint. Makes an easy change out a nightmare.

    • @StephenRardon
      @StephenRardon  9 лет назад

      I was a little
      Worried about what I would uncover. Turned out nice though.

  • @AmanacerTropical
    @AmanacerTropical 5 лет назад +1

    Excellent instructions. Thank you!

  • @daveolliemetalhead
    @daveolliemetalhead 3 года назад

    Thank you for sharing

  • @EminHVAC
    @EminHVAC 9 лет назад

    well done buddy. I liked how you explained everything. Also I am very Happy you were not working in the crawl space lol

    • @StephenRardon
      @StephenRardon  9 лет назад

      Emin HVAC i had fun making that one, did you notice the different camera views? that took a little bit of editing to make the views work.

    • @EminHVAC
      @EminHVAC 9 лет назад

      Actually I did. You're definitely a lot better with the camera then most people are.

  • @ramc1918
    @ramc1918 6 лет назад

    Thank you. Excellent video and instruction.

  • @harrydickson4575
    @harrydickson4575 9 лет назад +1

    great video Stephen

    • @StephenRardon
      @StephenRardon  9 лет назад

      Harry Dickson Thanks checking it out Harry

  • @reesef6030
    @reesef6030 Год назад

    After replacement of a loan dampener should you calibrate or adjust?

  • @wudaddy
    @wudaddy 9 лет назад

    Great vid. I'm about to try this myself. Thanks!

  • @luisdepaz6438
    @luisdepaz6438 5 лет назад +1

    great video

  • @NETWizzJbirk
    @NETWizzJbirk 3 года назад

    I would have just replaced that thermostat wire with a new wire. Possibly even used ethernet cable.

  • @SoaringRedEagle
    @SoaringRedEagle 4 года назад

    THANKS!!!!!

  • @MyPinkPanthers
    @MyPinkPanthers 8 лет назад +3

    incredible detail. Thank you for sharing. You just saved me thousands of $$,

    • @StephenRardon
      @StephenRardon  8 лет назад

      +David C hope it all works out for you

    • @NETWizzJbirk
      @NETWizzJbirk 8 лет назад +4

      It is not thousands to replace a damper. It is thousands to install a new zone control system.

    • @wanelly
      @wanelly 3 года назад

      @@NETWizzJbirk money weight is relatively personal. A$100 may feel like $1000 depending on where and how you make yours.

  • @zachburgess8518
    @zachburgess8518 5 лет назад

    Thanks mann

  • @fencerider1492
    @fencerider1492 5 лет назад +1

    I think my honeywell M847d1004 automatic damper is bad i noticed today upstairs was not cooling right. I checked the dampers and one was stuck closed. I moved it open and closed and it seems to be working a bit. But I noticed that it wont close fully now when the other dampers are open and that one should be closed. I hope that made sense. Then it clicked for a little bit but stopped. Anyways, can I just replace the motor/actuator instead of the whole assembly like you did?

    • @StephenRardon
      @StephenRardon  5 лет назад +1

      Yes! You ought to be able to replace the actuator. Guessing you probably could find a new actuator online by searching for the number and Damper Actuator

    • @StephenRardon
      @StephenRardon  5 лет назад

      In fact the actuator only is much easier to deal with!

    • @fencerider1492
      @fencerider1492 5 лет назад

      @@StephenRardon Sweet, thx for the reply and help. Gonna look for the part tomorrow. And will be subbing ya 😉

  • @mattrobinson8059
    @mattrobinson8059 5 лет назад

    Can a faulty damper prevent the blower in the furnace from turning on with the AC?

    • @StephenRardon
      @StephenRardon  5 лет назад

      I can’t think of a situation where the damper might determine whether the blower would run or not. That’s an odd one. If you’d like you could send me an email with pictures of the situation and I may be able to help StephenRardon@RardonHomePerformance.com

  • @nicholasceea4109
    @nicholasceea4109 9 лет назад

    Nice job....

  • @jeffreycarrigan5440
    @jeffreycarrigan5440 4 года назад

    I have a damper that doesnt have the red light on it lighted up. I traced that wire back to the board to zone two. The red power light on zone 2 isnt on. Would that be tue board or the damper at fault?

    • @StephenRardon
      @StephenRardon  4 года назад

      Hard to say for sure, they don’t all have lights. Sorry I can’t be of more help

  • @CaptainBret
    @CaptainBret 8 лет назад

    Great video

  • @garyoconnordbaairrepair7775
    @garyoconnordbaairrepair7775 5 лет назад

    I guess rules about insulation is different in other states from here in CA.

    • @StephenRardon
      @StephenRardon  5 лет назад

      Yeah, I assume your talking about wrapping the collar and damper with fiberglass?
      With the humidity here that would never do any good, need vapor/moisture barrier.

  • @martinwoods1921
    @martinwoods1921 6 лет назад

    What brand of zoning system do you prefer, install, change existing equipment with...?

    • @StephenRardon
      @StephenRardon  6 лет назад

      I prefer the Ecojay zoning in general. I am considering the Jackson Systems zoning as an option though.

  • @brennanac1
    @brennanac1 9 лет назад

    great video! thank you!

    • @StephenRardon
      @StephenRardon  9 лет назад

      brennanac1 thanks for watching, i had fun working on that one.

  • @lastboomer6164
    @lastboomer6164 4 года назад

    how much does a job like this cost, parts + labor?

  • @66lwmorgan
    @66lwmorgan 6 лет назад

    Is it possible to over ride this piece and open the damper as a temporary fix till I can get a tech out here?

    • @StephenRardon
      @StephenRardon  6 лет назад

      very possibly, send me an email stephenrardon@gmail.com

    • @66lwmorgan
      @66lwmorgan 6 лет назад

      It keeps saying the email is invalid and won't let me send

    • @StephenRardon
      @StephenRardon  6 лет назад

      Stephenrardon@gmail.com
      Check spelling carefully

    • @StephenRardon
      @StephenRardon  6 лет назад

      Or shoot me a text 919-346-3532

    • @66lwmorgan
      @66lwmorgan 6 лет назад

      I copied and pasted but it still didn't work. The damper did however start working again, I moved the arm behind the actuator up and it came back down so I assumed the spring wasn't broke and then it started working. That leads me to believe there could possibly be a stripped gear and it caught just enough to start working again. Does this sound like it could be a possibility, Thank you again for replying.

  • @daveolliemetalhead
    @daveolliemetalhead 3 года назад

    What is the Difference between ARD AND A ZD HONEYWELL SYSTEM.
    I have to replace a damper the Motor

    • @StephenRardon
      @StephenRardon  3 года назад +1

      That’s a good question, I know ARD standard for automatic round damper but I’m not sure on ZD

    • @daveolliemetalhead
      @daveolliemetalhead 3 года назад

      Thank you for your response

    • @StephenRardon
      @StephenRardon  3 года назад +1

      Looks like the ZD is their square damper
      forwardthinking.resideo.com/products/zoning/detail/zd_damper.html
      www.google.com/aclk?sa=L&ai=DChcSEwitiIPvstLuAhVxCn0KHbnrAuwYABAGGgJwdg&ae=2&sig=AOD64_1nwUhy37MC_qx18z6TkEbwkOVjEg&ctype=5&q=&ved=2ahUKEwjp4PvustLuAhWPQc0KHR_FDz0Qwg96BAgCEBU&dct=1&adurl= this could be what you need to replace only the motor

    • @daveolliemetalhead
      @daveolliemetalhead 3 года назад

      Thank you for your kindness and information have a great day and be safe.👍

  • @AndreMercado
    @AndreMercado 9 лет назад

    what manufacturer builds the power open/close damper you used?

    • @StephenRardon
      @StephenRardon  9 лет назад +1

      Formerly known as XCi they are called EcoJay now. www.comfortsolutionsinc.com

  • @michaelmattson3515
    @michaelmattson3515 3 года назад

    Huh, cool.

  • @chrisnashley01
    @chrisnashley01 8 лет назад

    how do i know which damper motor will work with what i have now?

    • @StephenRardon
      @StephenRardon  8 лет назад

      +Ashley Hook depends, the zone board usually matches the brand of damper

    • @chrisnashley01
      @chrisnashley01 8 лет назад

      Ok thanks will look a board

  • @petesingh292
    @petesingh292 4 года назад

    Hi Stephen , I got a damper motor that keeps buzzing when power is disconnected , it has 3 wires and I know the motor is no good the damper stays closed

    • @ronthatus
      @ronthatus 4 года назад

      I have one that’s doing the exact same thing

  • @dannyp3652
    @dannyp3652 4 года назад +3

    its easier amd faster just to remplace the motor , takes 2 minuts

  • @ZCV7853
    @ZCV7853 6 лет назад

    +1 Thumbs up from me m8! Thx a lot!!!!

  • @sergiobullitt4509
    @sergiobullitt4509 8 лет назад +1

    no mask bro u breathed. all tha insulation man

    • @StephenRardon
      @StephenRardon  8 лет назад

      I'll die from something else that worse, can't stand a mask.

  • @richardcampbell226
    @richardcampbell226 7 лет назад

    Instead of all the trouble of removing the entire damper, how about a damper manufacture you just replace the board and motor?

    • @StephenRardon
      @StephenRardon  7 лет назад

      Depends on the situation mostly, we've don't just that several times when we can get the motor easily or quickly