The point of the acknowledge button is if you have a two stage system, you have to press that within about 5 minutes or else the panel will think that there’s nobody investing the alarm and evacuate the building.
Use the dipswitches under the bell cct LEDs to bypass the bells. But always call the monitoring company first that monitors the panel to put the system on test with the fire dept
@@CJ9899 yea we self monitor and I called them myself so that parts fine but I would just turn off all dip switches in the first bank with the plastic cover ?
The point of the acknowledge button is if you have a two stage system, you have to press that within about 5 minutes or else the panel will think that there’s nobody investing the alarm and evacuate the building.
Yes, I realized that after I made the video
thanks man . Could you do a Verification on this panel and system ?
Nice 😀👍👍
Shy is walk-test not allowed in canada?
I saw a Mircom Series 1000 at a hotel a few days ago! (Is the one in the video A Series 1000? (Im from canada, it was in BC)
Ah, yes. The Kanata Inn in Invermere. And yes, the Series 1000 is identical.
@@Twentythree33 ty
Wait, who are you? I've never met you before.
@@Twentythree33 uh lmao im max xd
Hi , (Auxiliary disconnect ) is the only button I need To push for by-passing the system if I am working on the sprinkler system?!
No, you need to use the dip switches or pop out the terminal blocks. Auxiliary bypass will only bypass the relays
@@CJ9899 alright thanks man!!! Cool channel
what is the difference between buzzer silence and signal silence?
hossein bakhshi buzzer silence silences the panels piezo. Signal silence silences the NAs
Hey what if a panel is stuck in Test/Confi mode without dipswitch being touched? How do i reset without a hard reset?
Hey, you work for Oakridge. What’s up Darshan
Darshan
how do i put the system in test mode so it doesnt go off during renovations
Use the dipswitches under the bell cct LEDs to bypass the bells. But always call the monitoring company first that monitors the panel to put the system on test with the fire dept
@@CJ9899 yea we self monitor and I called them myself so that parts fine but I would just turn off all dip switches in the first bank with the plastic cover ?
@@iiiuuj the 4 dipswitches under the bell cct LEDs will bypass your bells.