Hi, after replacement main PCB in indoor unit model FXSQ125 an error C6-01 appeared .It's correct because the Capacity Plug Adaptor for the new Main PCB is 160 instead 140. But 140 CPA is available in stock now. Can I do something in such situation to help the client?
The out door unit model is RXYQ20T The connection between main PCB and fan PCB is OK. The new main PCB is same like replaced PCB only the capacity plug adaptor is not macth. 160 instead of 140.
Where is PCB ? Indoor or outdoor ?
and we must replace the PCB with a new one?
What if it's still blinking green and comes one temporarily?
hi can you tall a fafx80suv modle CE 01 erro cord
Master ...🙏
Thanks
Thanks for sharing mate.
Thanks bro
Hi, after replacement main PCB in indoor unit model FXSQ125 an error C6-01 appeared .It's correct because the Capacity Plug Adaptor for the new Main PCB is 160 instead 140. But 140 CPA is available in stock now. Can I do something in such situation to help the client?
Check main pcb and fan pcb connections.
And model not macth.
What is outdoor unit model
The out door unit model is RXYQ20T
The connection between main PCB and fan PCB is OK. The new main PCB is same like replaced PCB only the capacity plug adaptor is not macth. 160 instead of 140.
@@vladimirmakhney5407 you try setting to 140
Good and professional jobs
Thanks bro
Informative video thanku sir Love for india
Thanks bro 🙏🙏🙏
Hi uncle, I've got a question, what is the difference between VRV3 and VRF and VRV4, please and thank you
Normally Daikin call VRV(variable refrigerant volume),Mitsubishi call VRF(variable refrigerant flow)
VRV3 =inverter compressor and standard compressor.
VRV 4 = only inverter compressor
@@BonMj , appreciate for your perfect definition, when you're saying standard comprassor what that means, thanks again
@@بنامایران-ي2ر standard compressor is not inveter,direct 3phase current to the compressor.
@@BonMj understood, tq
@@BonMj I just found out that there is onather system called VRV4 , what that means?
Can someone tell me the value of R1T, R2T, R3T Thermistor Sensor value at 25dig. Centigrade Daikin vrv
I think it is 15k, but you can double check the service manual
👍
Thanks
Nice job bro
Thanks bro
Hi bro
Hi
CE-01
Check thermistor
@@BonMj what thermistors