Daikin | How to solve error code U3 after replacing new main pcb |VRVA

Поделиться
HTML-код
  • Опубликовано: 26 авг 2024
  • Brand : Daikin
    model : RXQ16AYM
    Replace new main PCB.
    Important, for Daikin VRV-A ,after replacing new PCB, must conduct Auto Charge before
    test run.
    #daikin #bonmj #vrv4

Комментарии • 152

  • @paulbrown1079
    @paulbrown1079 2 года назад +4

    Wouldn't mind shadowing you for a few weeks with fault finding on different systems 👍👍

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @hossainurrahman6700
    @hossainurrahman6700 2 года назад +2

    great teacher nobody like him for me
    thanks

    • @BonMj
      @BonMj  2 года назад

      Welcome

  • @vladimirmakhney5407
    @vladimirmakhney5407 2 года назад +1

    Hi ,this video is just in time, I will have to change the main board to Daikin. Thanks

    • @BonMj
      @BonMj  2 года назад +1

      This is vrv4- A , auto charge system.

  • @bago-uw2cw
    @bago-uw2cw 6 месяцев назад +1

    -I'm Myanmar Citizen.
    -I want to work and learn from you.
    -I'm in Singapore now!

  • @rogelebro3456
    @rogelebro3456 2 года назад +1

    It is a very nice tutorial, Sir Bon...I've learned another trouble and how to rectify it..thanks..

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @user-pb1dz6bd4s
    @user-pb1dz6bd4s 5 месяцев назад +1

    mr bon juat wanna ask when i want to do auto charge should i open valve to release gas from compressor first or dont open the valve and auto charge it and then release the gas from compressor ?

  • @narayanaya5519
    @narayanaya5519 Год назад +2

    Could you please let me know the details about that copper line connected to pcb

  • @deshanabeysekara5124
    @deshanabeysekara5124 Год назад +1

    your videos big help for us.Thank you sir...

  • @CHOPPA78
    @CHOPPA78 Год назад +1

    Hi Mr Bon, i love watching your instructional videos i just wondered how would you charge the extra refrigerant, if you could not determine the pipe length, does the auto charge procedure automatically detect the correct refrigerant charge ?

  • @sweetswocas7646
    @sweetswocas7646 3 месяца назад +1

    Thank You

    • @BonMj
      @BonMj  2 месяца назад

      You're welcome

  • @ismaielchaudhary
    @ismaielchaudhary 9 месяцев назад +1

    Sir what would be reason Daikin VRV liquid line is freezing, I check solenoid and sensors and ohms reading look acceptable.

  • @taqmeemalam8852
    @taqmeemalam8852 2 года назад +1

    ❤️❤️

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @juliocesarherrerasierra3074
    @juliocesarherrerasierra3074 Год назад +1

    exelente pagina muchas gracias

  • @suhanurrahman9822
    @suhanurrahman9822 10 месяцев назад +1

    • @BonMj
      @BonMj  10 месяцев назад

      Thanks

  • @dicksonfu8604
    @dicksonfu8604 Год назад +1

    Why need to do freon charging when replacing the PCB?

  • @sarfarajshaikh4582
    @sarfarajshaikh4582 2 года назад +1

    As always
    Great jo brother 👍

    • @BonMj
      @BonMj  2 года назад

      Thanks bro

  • @jiezhang730
    @jiezhang730 Год назад +1

    Hi, May I ask for Daikin R407c, ds2 and ds3 which button should be on?

  • @BonMj
    @BonMj  2 года назад

    Correction.
    The model is RXQ16AYM.
    Thanks

  • @sonukurmi305
    @sonukurmi305 Год назад +1

    Hi sir please tell me 99 settings video

  • @Marcelo.M.Quaiotti.01
    @Marcelo.M.Quaiotti.01 Год назад +1

    Hi. Do you have U3-10 in the manual?

  • @Actechwala
    @Actechwala 2 года назад +1

    Superb sir.

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @Ramprasad-fo5ui
    @Ramprasad-fo5ui 2 года назад +1

    So great video

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @electrolatif
    @electrolatif Год назад +1

    Thank you Mr Bon to share you knowledge

  • @VinodKumar-ix7rt
    @VinodKumar-ix7rt Год назад +1

    Thank you sir❤❤

    • @BonMj
      @BonMj  Год назад +1

      Welcome

  • @voonkengchong5465
    @voonkengchong5465 2 года назад +1

    Do u conduct any course for water cooled package / air cooled package unit?

  • @JayaKumar-sj3oo
    @JayaKumar-sj3oo 2 года назад +1

    Thank you sir

    • @BonMj
      @BonMj  2 года назад

      Welcome

  • @NaimKhan-tv4rz
    @NaimKhan-tv4rz Год назад +1

    Great 👍sir

  • @alanwang2900
    @alanwang2900 2 года назад +2

    Great video, by the way, when auto charge active, is this gonna cause the system over charged?

    • @BonMj
      @BonMj  2 года назад +1

      When new air con is done,u can gauge the amount of refrigerant needed to be charged by measuring the pipe lenght and pipe size.
      Auto charge can only charge 4kg of refrigerant.

    • @BonMj
      @BonMj  2 года назад +1

      For this case the the auto charge just run for awile and stop.just a bit charge in only

    • @CHOPPA78
      @CHOPPA78 Год назад

      Hi Mr Bon, i love watching your instructional videos i just wondered how would you charge the extra refrigerant, if you could not determine the pipe length, does the auto charge procedure automatically detect the correct refrigerant charge ?

  • @patrociolacic6088
    @patrociolacic6088 Год назад +1

    MERCI GREAT JOB

  • @CircinusMusic
    @CircinusMusic 2 года назад +1

    Sir if panel fault no need gas recharge? Just to observe the to1 to po9 only?

    • @BonMj
      @BonMj  2 года назад +1

      After reset if U3 , u need to do .

  • @engineeringpteltdshengheng833
    @engineeringpteltdshengheng833 2 года назад +1

    Thanks a lot

    • @BonMj
      @BonMj  2 года назад

      Welcome.

  • @Lee-mu2jc
    @Lee-mu2jc 2 года назад +1

    老板谢谢你每次用心讲解
    如果是换其他电板也是一样要这样做吗
    也是vrv4 还是只是换你这样的电板才需要这样做 谢谢

    • @BonMj
      @BonMj  2 года назад +1

      VRV4 有两个款
      1)有Auto charge
      2)没有Auto charge
      这个video 是 vrv4 有auto charge,所以要这样做。
      如果没有auto charge, 只需要test run 就好。

    • @Lee-mu2jc
      @Lee-mu2jc 2 года назад +1

      @@BonMj 老板要怎样分辨哪一个款式是有没有auto charge谢谢

    • @BonMj
      @BonMj  2 года назад +1

      @@Lee-mu2jc你注意看service valve那边(check gas 的地方右手边),有个进gas 的service port.
      你注意看我video,蓝色pipe就绑在那个service port.

  • @pappykwabee5296
    @pappykwabee5296 2 года назад +1

    I have worked on the vrv 2 and 3 a lot but I have not worked on vrv 4 yet.Please why do you have to do all these settings(auto charge and test run) after you have replaced the main Pcb.On vrv 2 and 3
    Is straight forward you don't need to do anything.
    What is auto-charge by the way?Is it something to do with the refrigerant being recharged into the system?
    PLEASE advise.thank you

    • @BonMj
      @BonMj  2 года назад

      VRV 4 auto charge system, when you replace the main pcb, this procedure is compoundsery. by manufacturer.

  • @doninovithendrianto1269
    @doninovithendrianto1269 2 года назад +1

    Halo Mr.bon,untukVRV A apabila ada additional indoor perlu melakukan prosedur Auto charge juga ?

    • @BonMj
      @BonMj  2 года назад

      Ya...

  • @karaors8970
    @karaors8970 2 года назад +1

    Hello nice Job bro 🇹🇷👍🛠️

    • @BonMj
      @BonMj  2 года назад

      Thanks bro

  • @joycetan4180
    @joycetan4180 2 года назад +1

    Hi I got the same model and it show f6 error on the peu controller. Can advise please? Thanks I advance

    • @BonMj
      @BonMj  2 года назад

      May system overcharge
      Or check liquid pipe thermistor

  • @selvarasumanikandan7646
    @selvarasumanikandan7646 2 месяца назад +1

    how to do troubleshoot daikin vrv 3 cu side ice

  • @ersham13
    @ersham13 2 года назад +1

    What was the error meaning and wht did we get the error
    Just reset it and pretend nothing is wrong?

    • @BonMj
      @BonMj  2 года назад

      U3-Test run execution failure.
      This error appear when we do the test run after replace new pcb.
      Try it twice is same error U3.
      Use the new installation method, Auto charge and after that test run.
      The unit but to normal.

  • @laxmanbhaloriya729
    @laxmanbhaloriya729 Год назад +1

    Explain sir Aircon bypass settings

  • @cutacatas9207
    @cutacatas9207 2 года назад +1

    Bagus ah you...

    • @BonMj
      @BonMj  2 года назад

      Terima kasih master

  • @syaha-dw9pj
    @syaha-dw9pj Год назад +1

    Hi Mr Bon, if a model RXQ14TY1 VRV4 after replace the main pcb are we can test run without auto charge first?

    • @BonMj
      @BonMj  Год назад

      Depend by error, if no error no need

  • @geralddiaz5491
    @geralddiaz5491 7 месяцев назад +1

    Hi mr.bon please help we was replacing the main pcb.after that ua is appear please help.what the next step

    • @BonMj
      @BonMj  7 месяцев назад

      PCB setting correct?

    • @geralddiaz5491
      @geralddiaz5491 7 месяцев назад

      Yes mr. Bon with thanks

  • @faresimrod3483
    @faresimrod3483 Год назад +1

    Thank you very much sir, What about error code LC - 14 . AND F6 -02

    • @BonMj
      @BonMj  Год назад +1

      LC-14 transmission error master cu inverter pcb

    • @faresimrod3483
      @faresimrod3483 Год назад +1

      @@BonMj thank you very much.

    • @faresimrod3483
      @faresimrod3483 Год назад

      Hi mr bon, i have to change both the INV1 pcb and the CU pcb but the problem Still exist, do you have an idea plz

  • @traduccion1024
    @traduccion1024 2 года назад +1

    What happens when the three displays are fixed but do not turn off?

    • @BonMj
      @BonMj  2 года назад

      Comunication problem

  • @choonhaukwa1878
    @choonhaukwa1878 2 года назад +1

    请问Auto charge 出现 P9 过后,是不是就说明gas已经足够,不用再进了?

    • @BonMj
      @BonMj  2 года назад +1

      其实auto charge 最多可以进4kg.
      如果新装的VRV要先算pipe的长度,在auto charge之前要先进gas,然后再auto charge.
      如果像这个video,只是换电板,程序上一定要做auto charge,但是过程是很快的,应为gas是足够的。
      对,P9是完成了auto charge.

  • @SasiKumar-gj3jg
    @SasiKumar-gj3jg 2 года назад +1

    What is the reason for E2 error in Daikin vrv4 outdoor unit and how to rectify?and also three times second inverter compressor changed but again second inverter compressor grounded

    • @BonMj
      @BonMj  2 года назад

      E2 you need to check the high pressure switch and high pressure sensor reading.
      Compressor replace 3 times!suggest you release all the gas,make the pipe calculation ,and recharge gas with correct quantity.

    • @CHOPPA78
      @CHOPPA78 Год назад

      Release means reclaim in to a reclaim cylinder , don't want to release" could be misunderstood !

  • @aircondbala
    @aircondbala 2 года назад +1

    super nice 👌👌👌

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @narayanaya5519
    @narayanaya5519 Год назад +1

    What is the voltage between f1f2

  • @Omprakash-cg8zo
    @Omprakash-cg8zo 2 года назад +1

    Hello brother
    We are getting UF 01 error code during test run mode
    My mchine is new vrv x
    Can it be problem if we do not provide earthing

    • @BonMj
      @BonMj  2 года назад

      Check all the valve make sure is open.
      Restart your test run

  • @kcomfortsystemshvac7060
    @kcomfortsystemshvac7060 2 года назад +1

    Bon,,,, very 👍 job,,, mate,,,,, I have question. Those DS1 and DS2 setting what there for ? Can you help me that please

    • @BonMj
      @BonMj  2 года назад

      Thanks.
      This pcb for all model.
      DS1 and DS2 is model setting

    • @kcomfortsystemshvac7060
      @kcomfortsystemshvac7060 2 года назад +1

      @@BonMj thanks Bon…. I really appreciate!!!👍

    • @BonMj
      @BonMj  2 года назад

      @@kcomfortsystemshvac7060 welcome

  • @suryavns7338
    @suryavns7338 2 года назад

    Very nice video sir,u2 error code in what is problem,thank you sir

    • @BonMj
      @BonMj  2 года назад

      Check inverter pcb voltage

  • @salimagwan9672
    @salimagwan9672 2 года назад +1

    RXYMQ8ARY16
    Will auto gas charging be done in this model sir

    • @BonMj
      @BonMj  2 года назад

      Sorry.this model i not sue,but in the cu should have the auto charge instruction if this is auto charge system

  • @hvacandvrvspecialvedoindus7891
    @hvacandvrvspecialvedoindus7891 2 года назад +1

    🙏🙏🙏

  • @hvacandvrvspecialvedoindus7891
    @hvacandvrvspecialvedoindus7891 Год назад +1

    Only mastar dip swich setting

  • @hvacandvrvspecialvedoindus7891
    @hvacandvrvspecialvedoindus7891 2 года назад +1

    Help sar

  • @vipinkumar5098
    @vipinkumar5098 2 года назад +1

    Please tell me
    E3 daikin vrv 3

    • @BonMj
      @BonMj  2 года назад

      Check high pressure switch

  • @chongyawteng8297
    @chongyawteng8297 2 года назад +1

    老师请问RSQ14TAYM,出U4. 3fcu,第一台没 连接后两台会走,第一台给他一对一会走,三台连接等一台出U4,CU,PCB可以reset故障吗?我有打电话去间,他们说reset电 就ok了,电我关了两天喽!都不可以😂😂😂

    • @BonMj
      @BonMj  2 года назад

      是关CU的电对吧!
      开回,按reset button 超过5秒

    • @BonMj
      @BonMj  2 года назад

      我比较担心是comunication wire 没有接对

    • @BonMj
      @BonMj  2 года назад

      1对1=可以
      1对2=可以
      3台接一起不可以。
      你花点时间check 3台fcu comunication wire 有接对吗

    • @chongyawteng8297
      @chongyawteng8297 2 года назад

      @@BonMj cu/fcu都关2天

    • @chongyawteng8297
      @chongyawteng8297 2 года назад

      @@BonMj 都连接对。

  • @Sundar_ramanujam_
    @Sundar_ramanujam_ 11 месяцев назад +1

    How could you ensure pcb board faulty? Can you elaborate more?

  • @rogelebro3456
    @rogelebro3456 2 года назад +1

    Good Day Sir Bon...How can you rectify the Error Code U9 on Daikin VRV 4 unit? ..If you have a video for this error, its better....Thanks

    • @BonMj
      @BonMj  2 года назад +1

      U9 mean other fcu got problems

    • @rogelebro3456
      @rogelebro3456 2 года назад +1

      @@BonMj Yes Sir...some of the units had a problem

  • @Ramprasad-fo5ui
    @Ramprasad-fo5ui 2 года назад +1

    And English after use hind best long before

  • @alanwong2761
    @alanwong2761 2 года назад

    Mr Bon isn't need to auto charging first before test run for all VRV 4 models?

    • @BonMj
      @BonMj  2 года назад +1

      No, for Auto Charge system only, depend by model

    • @alanwong2761
      @alanwong2761 2 года назад +1

      Thanks your reply Mr Bon

  • @hvacandvrvspecialvedoindus7891
    @hvacandvrvspecialvedoindus7891 2 года назад +1

    Bon sar pleas help me u1-16

  • @MYDUBAI78628
    @MYDUBAI78628 2 года назад +1

    Is machine run automatically after test run ??

    • @BonMj
      @BonMj  2 года назад

      After test run aircon stop running.
      You need to on indoor .

    • @MYDUBAI78628
      @MYDUBAI78628 2 года назад +1

      @@BonMj understood

    • @MYDUBAI78628
      @MYDUBAI78628 2 года назад +1

      @@BonMj Bon I am h fresher with 1 year experience can i get job in Singapore as Aircon technician from abroad

    • @BonMj
      @BonMj  2 года назад

      @@MYDUBAI78628 👍

    • @MYDUBAI78628
      @MYDUBAI78628 2 года назад +1

      @@BonMj guide m sir how to i apply from abroad

  • @hvacandvrvspecialvedoindus7891
    @hvacandvrvspecialvedoindus7891 2 года назад +1

    Please sar 🙏😊

  • @bulbmandai2024
    @bulbmandai2024 2 года назад +1

    Sir how to fix daikin vrv 3 ac AH error code

    • @BonMj
      @BonMj  2 года назад +1

      This hot water system?

    • @bulbmandai2024
      @bulbmandai2024 2 года назад +1

      Not hot water system.

    • @BonMj
      @BonMj  2 года назад +1

      @@bulbmandai2024please check indoor pcb

    • @bulbmandai2024
      @bulbmandai2024 2 года назад +1

      Ok sir is this complint about indoor section?

    • @BonMj
      @BonMj  2 года назад +1

      @@bulbmandai2024 ya.may be

  • @hvacandvrvspecialvedoindus7891
    @hvacandvrvspecialvedoindus7891 2 года назад +1

    Bon sar vrvx u7 11

    • @BonMj
      @BonMj  2 года назад

      Check outdoor to outdoor unit connections

  • @nirajgalthariya
    @nirajgalthariya 2 года назад +1

    Hello
    Why am I in your country I can get a job

  • @mohamedelsadk7362
    @mohamedelsadk7362 2 года назад

    My name is Mohamed Al-Sadiq Mohamed, VRV refrigeration and air conditioning technician. I am from Egypt. I want to travel to work and work hard. I need help

  • @janshaw5472
    @janshaw5472 2 года назад +1

    VRV 感觉好难(⊙o⊙)for me

    • @BonMj
      @BonMj  2 года назад

      不会难,换了pcb要auto charge然后再test run