How To Enable Strobe Synchronization - Notifier NFS-320 & NFS2-640

Поделиться
HTML-код
  • Опубликовано: 22 янв 2025
  • НаукаНаука

Комментарии • 18

  • @YZFR16666
    @YZFR16666 3 года назад

    I have a notifier 640 , after an annual inspection , we had 2 annunciators (acm-24at) and the udact go "inv reply" , a little trouble shooting i was able to get the udact to come back online by disconnecting the 2 annunciators from the system but when the annunciators are powered back up they take down the udact, any idea what i might have going on here?

  • @vafirecollector9547
    @vafirecollector9547 4 года назад

    Thank you! This was very helpful, don't know why I couldn't figure this out.. even when I'm reading through the manual haha

    • @AlarmSystemTech
      @AlarmSystemTech  4 года назад +2

      Glad I could help. It's much easier explaining it in a short video than typing it all out lol.

    • @vafirecollector9547
      @vafirecollector9547 4 года назад

      @@AlarmSystemTech I do agree its easier seeing it in a video rather than in text sometimes. But! I just programmed the sync and works like a charm.
      But overall these are great panels, although I do have another question.. is its possible to expand off the 320, and make it a two or three bay panel with an AMG-1 attached kinda like your 640?

    • @AlarmSystemTech
      @AlarmSystemTech  4 года назад +1

      VAFireTech122 The 320 and AMG are not compatible. NCAlarms has confirmed this.

    • @eng-anwerkadhim5335
      @eng-anwerkadhim5335 3 года назад

      dear sir. thanks for supporting this was vary helpful. i really appreciate if can help me. how can add smoke detect that was deleted from system

  • @JREQ-tv1wm
    @JREQ-tv1wm 8 месяцев назад

    How to install printer?

  • @Roxxofoxxo
    @Roxxofoxxo 3 года назад

    Can each NAC do a different coding/sync option or no?
    If yes, how?

  • @JOSE20805
    @JOSE20805 3 года назад

    Hello, very helpful video. I’m trying to silence my horns but still keep strobes flashing. When I hit silence system everything including strobes turn off. Would you know what I need to do to get that function going ?

    • @AlarmSystemTech
      @AlarmSystemTech  3 года назад +1

      NFPA no longer allows audible silence. I’m guessing your AHJ wanted this. You have to go into point programming and select & for the strobe output. You’ll then see *FW change that to **W.

  • @muhammadjawadhaider2152
    @muhammadjawadhaider2152 4 года назад

    Hi, can u tell how to rectify "corrupt program" trouble?

    • @AlarmSystemTech
      @AlarmSystemTech  4 года назад +2

      Muhammad Jawad Haider You’ll need to upload and download the database with VeriFire Tools.

    • @muhammadjawadhaider2152
      @muhammadjawadhaider2152 4 года назад

      @@AlarmSystemTech programming is out of my scope, there is 3rd party to come and solve such issues. Is there any other way to solve that kind of issues?

    • @AlarmSystemTech
      @AlarmSystemTech  4 года назад +1

      @@muhammadjawadhaider2152 I'm afraid not.

    • @muhammadjawadhaider2152
      @muhammadjawadhaider2152 4 года назад

      Can we get device maintenance list from notifier system, like we can see in est3 systems?

  • @bob5074
    @bob5074 4 года назад

    I really wish Notifier would let us refer to the NFS-640 and 320’s NAC circuits in logic equations.