I have a notifier 640 , after an annual inspection , we had 2 annunciators (acm-24at) and the udact go "inv reply" , a little trouble shooting i was able to get the udact to come back online by disconnecting the 2 annunciators from the system but when the annunciators are powered back up they take down the udact, any idea what i might have going on here?
@@AlarmSystemTech I do agree its easier seeing it in a video rather than in text sometimes. But! I just programmed the sync and works like a charm. But overall these are great panels, although I do have another question.. is its possible to expand off the 320, and make it a two or three bay panel with an AMG-1 attached kinda like your 640?
Hello, very helpful video. I’m trying to silence my horns but still keep strobes flashing. When I hit silence system everything including strobes turn off. Would you know what I need to do to get that function going ?
NFPA no longer allows audible silence. I’m guessing your AHJ wanted this. You have to go into point programming and select & for the strobe output. You’ll then see *FW change that to **W.
@@AlarmSystemTech programming is out of my scope, there is 3rd party to come and solve such issues. Is there any other way to solve that kind of issues?
I have a notifier 640 , after an annual inspection , we had 2 annunciators (acm-24at) and the udact go "inv reply" , a little trouble shooting i was able to get the udact to come back online by disconnecting the 2 annunciators from the system but when the annunciators are powered back up they take down the udact, any idea what i might have going on here?
Thank you! This was very helpful, don't know why I couldn't figure this out.. even when I'm reading through the manual haha
Glad I could help. It's much easier explaining it in a short video than typing it all out lol.
@@AlarmSystemTech I do agree its easier seeing it in a video rather than in text sometimes. But! I just programmed the sync and works like a charm.
But overall these are great panels, although I do have another question.. is its possible to expand off the 320, and make it a two or three bay panel with an AMG-1 attached kinda like your 640?
VAFireTech122 The 320 and AMG are not compatible. NCAlarms has confirmed this.
dear sir. thanks for supporting this was vary helpful. i really appreciate if can help me. how can add smoke detect that was deleted from system
How to install printer?
Can each NAC do a different coding/sync option or no?
If yes, how?
No
@@AlarmSystemTech Oh alright
Thanks for the quick reply!
Hello, very helpful video. I’m trying to silence my horns but still keep strobes flashing. When I hit silence system everything including strobes turn off. Would you know what I need to do to get that function going ?
NFPA no longer allows audible silence. I’m guessing your AHJ wanted this. You have to go into point programming and select & for the strobe output. You’ll then see *FW change that to **W.
Hi, can u tell how to rectify "corrupt program" trouble?
Muhammad Jawad Haider You’ll need to upload and download the database with VeriFire Tools.
@@AlarmSystemTech programming is out of my scope, there is 3rd party to come and solve such issues. Is there any other way to solve that kind of issues?
@@muhammadjawadhaider2152 I'm afraid not.
Can we get device maintenance list from notifier system, like we can see in est3 systems?
I really wish Notifier would let us refer to the NFS-640 and 320’s NAC circuits in logic equations.