Notifier NFS2 640 Programming Guide

Поделиться
HTML-код
  • Опубликовано: 21 авг 2024

Комментарии • 58

  • @Roxxofoxxo
    @Roxxofoxxo  2 года назад +2

    0:00 - Intro
    1:32 - How to go into programming mode
    3:17 - How to program/add points in the SLC
    7:02 - Point programming
    12:10 - Notifier special function programming
    13:27 - How to program NAC sync/coding options
    17:14 - Setting up an agent release NAC
    19:21 - How to change notifier LED polling speed
    21:12 - How to change the system normal message
    22:38 - How to turn off trouble reminder
    23:30 - How to change addressable protocols
    24:04 - Testing the panel and alarms

    • @dc5rick
      @dc5rick 8 дней назад

      @Roxxofoxxo Hey I have this same system but I’m having an issue when my main sprinkler valve is closed I get a trouble but when the valve is close the supervisory light should turn on but it’s not any input would be appreciated thank you.

    • @Roxxofoxxo
      @Roxxofoxxo  8 дней назад

      I'm assuming you know the monitor module address that is connected to the tamper value. You're using the wrong point type for that device, go into programming mode and change the point type from a trouble to a tamper point type

    • @dc5rick
      @dc5rick 8 дней назад +1

      @@Roxxofoxxo I do have the address I will look at it tomorrow thank you again.

  • @jorgemm1914
    @jorgemm1914 Год назад +3

    Excelente demostración. Felicidades!

  • @thailander5572
    @thailander5572 Месяц назад

    there is some reason we need to shutdown this control box. how do we do it? and how to turn it on again when we want to use it ?

  • @arturoibarra6944
    @arturoibarra6944 Год назад +2

    But, what if i don't have the password

  • @timothyfranche2513
    @timothyfranche2513 2 месяца назад

    I cant seems to get to the " change program " menu, even im using the correct password. It just gets back to the home screen. Sometimes it works but most of the time not. 1:32 .
    I know that its not a wrong password since it doesnt shows error it just simply puts me back to home screen.

  • @Omegamoney32
    @Omegamoney32 3 месяца назад

    theres Security LED and try connect home security with panel

  • @arturoibarra6944
    @arturoibarra6944 5 месяцев назад

    I have a remote annunciator, and i do not know how to program it, could you help me with that

  • @marxbautista9323
    @marxbautista9323 6 месяцев назад

    Is there a default passwork to access Basic Programming?

  • @mvsmahesh669
    @mvsmahesh669 8 месяцев назад

    How to Change Date and Time

  • @MrFido9209
    @MrFido9209 8 месяцев назад

    We replaced an existing FSP-851 with the newer FSP-951 detector and base. But the panel showed trouble TEST F. What could be the problem...?

    • @EZBANK4L_
      @EZBANK4L_ 6 месяцев назад +1

      You have to use the FSP-951IV if not the it won’t accept the new device. New FSP-951 are flash scan protocol the since you were working on an older system which is set up for clip mode protocol, you would have to use a FSP-951IV which is set for both Flash Scan & Clip Mode Protocol.

    • @MrFido9209
      @MrFido9209 6 месяцев назад

      @@EZBANK4L_ Thanks. That's exactly what we had to do to resolve this issue...

  • @SergioLopez-sl6zc
    @SergioLopez-sl6zc Год назад

    I have a smoke detector that failed to recall the elevator. So the recall relay isn’t assigned with the smoke. Is it possible to change that through the panel ?

    • @N9ne20
      @N9ne20 Год назад

      Yes, you’ll need the master password. Go into programming and edit the device, you’ll need to add the zone for recall to that detector.

  • @sebastiaopereiradacruzjuni5545
    @sebastiaopereiradacruzjuni5545 2 года назад +1

    is there any way to remove this beep from the fault ?

    • @Roxxofoxxo
      @Roxxofoxxo  2 года назад

      Press the acknowledge button

  • @Experemented
    @Experemented 2 года назад

    yes I will totally need this for totally legit fire alarm stuff hmmm yes

  • @calebmorand4604
    @calebmorand4604 2 года назад +1

    If cross zones activate, will it cause a pre discharge countdown? Thanks!

  • @colsonjames-wx5hw
    @colsonjames-wx5hw 2 месяца назад

    nfs 320 next plz

  • @MantenimientoSalvavidas
    @MantenimientoSalvavidas 2 месяца назад

    I need you help..

  • @notifierfan6078
    @notifierfan6078 4 месяца назад

    does the 640 use both the 320 and 2-3030 cpu cause ive seen some with the 3030 cpu and the 320 cpu like this one

    • @Roxxofoxxo
      @Roxxofoxxo  4 месяца назад

      It used a cpu similar to the 320, that is basically identical besides some hardware and firmware differences

    • @notifierfan6078
      @notifierfan6078 4 месяца назад

      @@Roxxofoxxooh

  • @hsn000hsn2
    @hsn000hsn2 11 месяцев назад

    How to activate the smoke detector remotely, through the control panel ?

    • @arturoibarra6944
      @arturoibarra6944 5 месяцев назад +1

      no can do, but if you want to make the sirens to go, keep pushing drill botton for 2 seconds

  • @legrandscanlan6336
    @legrandscanlan6336 Год назад

    I try modifying a detector and it wouldn’t let me. For example I tried modifying a detector the address was 1D001 but instead it took me to the 2 detector which is 1D002 I tried, and tried changing ID001 but it just skips to 1D002. Do I have to run auto program again to modify this point????

    • @Roxxofoxxo
      @Roxxofoxxo  Год назад

      What are you trying to modify detector 1 as, or are you trying to add detector 1 to the panel?

    • @legrandscanlan6336
      @legrandscanlan6336 Год назад

      @@Roxxofoxxo I wanted to label it 1D001 - Admin Board room, and it’s zone but it just skips to 1D002 which I already labelled as Admin Sales

    • @arturoibarra6944
      @arturoibarra6944 5 месяцев назад

      to add a new device you need to autoprogram, to erase other you doit in modify point.@@legrandscanlan6336

  • @user-zu2uc1sv9i
    @user-zu2uc1sv9i Год назад

    ¿como habilitar software de una nfs2 640 bloqueada?

  • @m7md034
    @m7md034 Год назад

    When i press auto programming nothing is happening what to do?

    • @Roxxofoxxo
      @Roxxofoxxo  Год назад

      Do you have devices connected to your SLC?

  • @calebmorand4604
    @calebmorand4604 2 года назад

    Can you autoprogram a new device if you already have existing programmed detectors or modules on the slc?

    • @Roxxofoxxo
      @Roxxofoxxo  2 года назад

      Yes
      Just use autoprogram

    • @calebmorand4604
      @calebmorand4604 2 года назад

      @@Roxxofoxxo awesome! Thanks.

    • @Roxxofoxxo
      @Roxxofoxxo  2 года назад

      Np!

    • @Roxxofoxxo
      @Roxxofoxxo  2 года назад

      @@calebmorand4604 you plan on getting a Notifier onyx?

    • @calebmorand4604
      @calebmorand4604 2 года назад

      @@Roxxofoxxo yes I do. They seem very nice. Probably a 320 or 640. Do both program the same?

  • @kwanmo5077
    @kwanmo5077 Год назад

    Can you tell me,how to use CBE

    • @mimi2
      @mimi2 Год назад

      Set the module to the zone you wish to control
      Then a output module or a nac to said zone

  • @uniteddrones7626
    @uniteddrones7626 2 года назад

    Do you have a template of the word meanings like AHJ codes like that and what they are used for… and please don’t abuse ur panel at 14:48 I almost dropped my dinner 🤣🤣

  • @NoahDoane
    @NoahDoane 2 года назад

    Notifier simp 😤

  • @stzenterprises6155
    @stzenterprises6155 9 месяцев назад

    Tea you are terrible