How to Charge Refrigerant (Gas) in an AC unit?

Поделиться
HTML-код
  • Опубликовано: 28 авг 2023
  • Charging refrigerant in an AC unit involves adding the right amount of refrigerant gas to ensure the system operates effectively. Here's a simple explanation of the process:
    Safety First: Make sure the AC unit is turned off and unplugged. Safety goggles and gloves are recommended.
    Locate Service Valves: Find the service valves on the AC unit. There are typically two valves - a larger one called the low-pressure or suction valve and a smaller one called the high-pressure or discharge valve.
    Attach Gauges: Connect refrigerant gauges to the service valves. The blue gauge connects to the low-pressure valve, and the red gauge connects to the high-pressure valve.
    Connect Refrigerant Cylinder: Attach a refrigerant cylinder to the yellow hose on the gauges. Make sure the cylinder is in an upright position.
    Start the AC: Turn on the AC unit and set it to its maximum cooling mode. The compressor should start running.
    Add Refrigerant: Slowly open the valve on the refrigerant canister. This allows refrigerant to flow into the AC system. Watch the pressure gauges as you do this. The pressure readings should rise as the refrigerant enters the system.
    Monitor and Adjust: Continuously monitor the pressure readings on the gauges as you add refrigerant. Stop adding refrigerant when the pressures approach the recommended levels for your AC unit.
    Close Cylinder Valve: Close the valve on the refrigerant cylinder once the desired pressures are reached.
    Disconnect Gauges: Safely disconnect the gauges from the service valves. Be careful as there might be a small release of refrigerant when disconnecting.
    Test AC: Let the AC run for a while to ensure that it's cooling effectively. Check the temperature of the air coming out of the vents.
    Check for Leaks: If you needed to add a significant amount of refrigerant, it's a good idea to check for any leaks in the system. Leaks should be repaired before adding more refrigerant.
    Remember, handling refrigerant requires proper training and knowledge to ensure safety and proper functioning of the AC unit. If you're not comfortable with these steps, it's best to consult a professional HVAC technician to charge the refrigerant for you.

Комментарии • 66

  • @zameenwala754
    @zameenwala754 4 месяца назад +6

    You tell everything about gas charging step by step . Now No question is remain .
    Full guide 👍💡

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  4 месяца назад +2

      I am glad. But there are many things about refrigerant charging. I will explain everything in a video.

    • @zameenwala754
      @zameenwala754 4 месяца назад +2

      @@zebralearningsenglish-pn6fl oka sir I will be wait 😊

    • @jollyscaria1922
      @jollyscaria1922 3 месяца назад

      Suchionline contened dis ..chergd lind contactinv yelow chwfgjnv cylinder valvropon cylindef R420 cylimdef up fosn anc cherhrinv ues fighte allthsnkyou gues wdlcome purgdaftef yes testing fixing checkinv znd oneby meghec ok

  • @Balticblue93
    @Balticblue93 9 месяцев назад +21

    410A needs to have the bottle inverted upside down to charge properly as a liquid. If you charge it upright, it will fractionate the near-azeotropic mixture. R22 is a single component and can be charged as a gas.

    • @gabrielphilips6980
      @gabrielphilips6980 8 месяцев назад +1

      What is 410a? What is r22?

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  7 месяцев назад +2

      It's depends on the cylinder. Before charging the refrigerant we should check the instruction on the cylinder how to charge.

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  7 месяцев назад +5

      R410A and R22 is two different types of refrigerant (Gas).
      R22 is older type refrigerant and R410A is modern refrigerant.
      R410A is more environmental friendly than the R22 refrigerant.
      Because R22 has chlorine atoms which dangerous to ozone layer but R410A doesn't have any chlorine atoms.
      The modern AC systems are replacing the R22 refrigerant with R410A refrigerant.
      R22 Refrigerant will not be available in the future due to environmental concerns.

    • @DaveMavrik-ki7xb
      @DaveMavrik-ki7xb 3 месяца назад +1

      Does r22 and r32 also need to turn the cylinder upside down too?

    • @Balticblue93
      @Balticblue93 3 месяца назад +1

      @@DaveMavrik-ki7xb R22 and R32 are single refrigerant and their composition does not change. Thus both liquid charging and gas charging is possible. Liquid charging of R32 all at once from the low - pressure side may cause the compressor to malfunction.
      Working pressures for R32 are very similar to R410A and when charging, R32 is easier to handle as it can be charged in both a gas and a liquid state. This why R32 is classified as A2L “mildly flammable” while safety data sheets say it is extremely flammable but it really is very low flammability.

  • @elnursafaraliyev6618
    @elnursafaraliyev6618 8 дней назад +1

    Hi. Why need to connect high pressure line if we are not use that during charge refrigerant?

  • @anookgujjala4132
    @anookgujjala4132 3 месяца назад +3

    Nice explanation sir 👍thank you

  • @otrovx
    @otrovx Месяц назад +1

    Hi, thanks for the video. Is it necessary to attach the red hose to the air conditioner in order to fill it? I have simpler manifold gauge, with only blue and yellow hose (without red hose, and without red gauge).

  • @7starernhernh580
    @7starernhernh580 11 дней назад

    Very good sir ji....exvelenttt

  • @4cchansemicircle944
    @4cchansemicircle944 4 месяца назад +2

    ​​This is a very good video. Please my question is I added refrigerant to my 1hp Samsung spit AC when the power was turned off and I waited 10 hours to put the power on. Is it okay?

  • @babaolowo35
    @babaolowo35 9 месяцев назад +2

    THANK you

  • @phyowin5288
    @phyowin5288 Месяц назад +1

    very clear video🎉🎉

  • @7starernhernh580
    @7starernhernh580 11 дней назад

    I m instrctor r/ac..but your mathed very Excelent.......

  • @HarunTechnology
    @HarunTechnology 2 месяца назад +1

    Nice video

  • @jacobprem26
    @jacobprem26 29 дней назад

    How much time will it take to transfer gas from cylinder to ac outdoor unit

  • @QuangLe-eg5si
    @QuangLe-eg5si 3 месяца назад +1

    Could you explain to me what happens if we open high-pressure on-off valve when we charge refrigerant ( GAS ) in an AC UNIT ?

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  3 месяца назад

      If we open the High Pressure On/Off Valve, Refrigerant will start going from AC Unit to Refrigerant Cylinder. Because the pressure in the High Pressure Side of the AC Unit is more than the pressure in the Refrigerant Cylinder.

  • @densista1160
    @densista1160 3 месяца назад +1

    can you fill using the red hose to the low pressure side?

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  3 месяца назад

      No you can't fill through the red hose. Because the red hose in connected the high pressure side. If you try to charge through the red hose. Instead of the refrigerant going into the unit, the refrigerant will return to cylinder from the unit because of the pressure difference.

  • @HunterRavin
    @HunterRavin 6 месяцев назад +1

    How to know when its time to close the blue vlv after letting air out

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  6 месяцев назад +1

      Nice question. You can see that easily when the refrigerant comes out. It will come out like spraying water.

  • @naeemtahir3406
    @naeemtahir3406 22 дня назад

    I was charging 410a while charging compressor and fan shut down itself, I checked breaker and thermostat both were on , what could have gone wrong

  • @patakotisrinivas1918
    @patakotisrinivas1918 4 месяца назад +1

    Nice

  • @densista1160
    @densista1160 3 месяца назад +1

    one question, is the red hose to high pressure line, complete shut off all the process?

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  3 месяца назад

      Yes, it will be completely shutoff through out the process.

    • @densista1160
      @densista1160 2 месяца назад

      why have it connected then? can't you just have the blue hose connected to fill ?@@zebralearningsenglish-pn6fl

  • @samisiddique5000
    @samisiddique5000 10 дней назад

    please tell us before charging gas required vacuum full machine required time and -psi value

  • @ganeshgarai416
    @ganeshgarai416 5 дней назад

    What is the need of connect high pressure guage????

  • @TheGines1979
    @TheGines1979 2 месяца назад +1

    Can you show other techniques? Please

  • @tilvalhalla9343
    @tilvalhalla9343 5 дней назад

    Why does nobody ever show you what you do if you have a recovery cylinder I don’t know whether to hook it through the red or the blue

  • @mohammedegyptian2527
    @mohammedegyptian2527 Месяц назад +1

    bravo

  • @abgzulkifli
    @abgzulkifli 16 дней назад +1

    How do we know how much gas need to be refill

  • @daffodilsinspire4908
    @daffodilsinspire4908 9 месяцев назад +1

    👍👍👍

  • @tbone6354
    @tbone6354 3 месяца назад +1

    A very helpful tip is to add 50ml of purified water to the compressor before regassing. This reduces corrosion and no need to vacuum

  • @user-wt2ys9hc9p
    @user-wt2ys9hc9p 7 месяцев назад

    Brother it's totally half knowledge about gas charging it's not the way we have to first leakage check and fill leakage than vaccum after all process gas charging 😊😊

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  7 месяцев назад +1

      It's just a basic concept of gas charging method. I'll make a detailed process of gas charging video and will upload it.

  • @pradeepkumar-bd1wc
    @pradeepkumar-bd1wc 5 месяцев назад +1

    Gas charging ka Hindi me animation

  • @mohammedmuneer2390
    @mohammedmuneer2390 2 месяца назад +1

    In hindi translation plz

  • @davewindt1506
    @davewindt1506 3 месяца назад

    Should shut down the unit en perform a vacuum test 24 hours prior charging the system to be sure the system is leak free and all the air is out.

  • @muhammadalifblogs
    @muhammadalifblogs 2 месяца назад +1

    রিদয় নাড়া দেওয়ার মতো একটি নাটক।

  • @abdullahzafar8779
    @abdullahzafar8779 9 месяцев назад +1

    Hindi video

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  9 месяцев назад +1

      main hindi video bana raha hoon aur jald hee upload karoonga.

    • @ujjawalkamboj2965
      @ujjawalkamboj2965 9 месяцев назад +1

      Please continue in english

    • @zebralearningsenglish-pn6fl
      @zebralearningsenglish-pn6fl  9 месяцев назад

      @@ujjawalkamboj2965 Yeah sure, in this channel I will upload only English video. I have opened a separate channel for Hindi. In that channel I will start to upload videos in Hindi.