Sounds like a relay sticking with the addition of a glitch in the programming of the board, for it to throw off binary something glitches bad , great video I love your stuff, you and Chris from HVACR videos make some really good content
Haha , I was going to ask how many Manitowoks were 410A and as I was writing it you said"Lets put this on the right refrigerant..." haha , love your videos !
Has it happened again? I have a machine with a new board (less than 1 year) that does the same thing. It says it's freezing but the compressor is off and the water system is on. It makes good ice until it randomly glitches.
If it's a new machine it should be under warranty? I would have a service guy check it out. Sounds like a water level sensor may not be making good contact.
Kinda packed? Holy crap that was packed. Dirty condenser. That board had issues. I wonder if the that condenser fan motor Isnt working as well from the dirty condenser coil.
I had one acting up about a year ago after a different company changed the board. When I checked to see what software it was running, all I got was gibberish. So I shut the power off and restarted the unit, and I still had gibberish for software. I also found no model or serial numbers on the board. I had to manually enter the M&S#s and update the software and then had no more problems. Makes you yearn for the old B series😉
On a CME250AE-1A what would cause the water valve not to get power to it.I measured the resistance across the terminals and got .612 kohm is this normal? after I removed it from the ice maker
612 ohms sounds possibly normal? I don't have their charts in front of me. It could be as low as 30ohms?. I would put it in test mode and verify you've got the rated voltage going to the solenoid.
Hi, my compressor is running fine ?? Because the water is running but it’s not making ice. It is cooling inside the bin. Any troubleshooting tips? My tech guy came by and measure the pressure and recommended replacing compressor ? We can’t afford that right now. Last time I did cleaning and reset then it worked. Summer time maybe ? I will be grateful. Thank you 😊🥳😘😁🍉🍉
Most problems are water-related, make sure your water filter is clean and got at least 20 to 30 lb of pressure and make sure your coils are clean and that you ran cleaner through the machine the way it's describes. After that it's hard to say without seeing it.
What is all these fancy electronics in a simple ice-maker, I remember working on Monitowoc ice makers in a Hotel, things were simple, limit switches and one small harvest board. matter of fact that ice maker probably still works.
I don't remember, I run 4-6 calls a day so that's several jobs ago since I recorded this. We charge time and material for most jobs unless it's quoted.
Those board always give problem had a problem like that in Barnes and noble band new board install 2 days later recall had to reorder board manufacturer defect
Good evening! Sir please help me I repair ice machine.. in the monitor display ice machine said Sittings low what is the problem in this ice machine ? Please help me thank you..
I know you walked into this after the fact, so not trying to knock you down, just my first impression seeing this vid for the first time and being a bit distracted at that.
Have learned a lot from you and Chris S...as well as Manitowoc annual training which I missed this year's Zoom version, but since I don't have that much time at my facility to dive into the ones we have was just dropping in to try and pick up a tidbit.
@@HVACRSurvival I just don't understand why if the keypad worked yesterday but not today. But so far that's what I've been told it probably is. Thank you
So the other tech installed the board on a Friday......and didn't check anything else....ask him for a copy of his work order with all the pressures and times for 3 cycles....
In a perfect world lol. I did call him and he said everything worked fine at that time. What's interesting is we had to go back several times later for other things which were very suspicious. The water sensor kept falling down three times in a row every week to week and a half. Very weird . I would not put it past the employees to sabotage the machine.
I had a machine doing something like this once. It turned out it was voltage drops at the outlet where it was plugged in. Their POS machine would flicker as well..
Honestly they're pretty reliable normally. that's why I had a hard time accepting a brand new board taking a dump right after another board was replaced for whatever reason.? I'm not the one that replaced the other board.
Try going back Turn off condenser soo it will go off on high pressure If board does not read the error again U know what's up Ever heard of ghost codes They are real
I found a few things wrong later, one of the issues was someone else replace the board and diagnosed it. I came in second and can't fully explain without creating drama.
Sounds like your at a Wendys. and yea, ive got a local wendys here thats constantly "out of ice". things that make you go hmmm especially after you mentioned they dont want to do anything to it, or proper maintenance.
@@HVACRSurvival Ahh ok. Kinda sounded like a Wendys. Personally, I like Culvers or a place like that. But they arnt close to me where I ended up moving to.
@@HVACRSurvival deep mountains in north carolina. Closest one is in the city of Ashville which is about an hour and 30 mins out. Closest HVAC youtuber to me would be Ted I believe. :-)
1 ad for every two minutes of content. I barely got the gist of your video, I am getting carried away into your ads. Sorry man I wanted to support your channel, but thats just way too many ads. Yea its your channel and I dont have to watch. I know.
Looks like that reference book has a lot of good info! Wish I had an opportunity to work on more ice machines! Good stuff Rick!
No you don't, I thought that also until I got stuck doing one after another. 😏
Wish I could get a book like that one ! Could you tell me where to find etc.?
Sign up for Manitowoc training.
Sounds like a relay sticking with the addition of a glitch in the programming of the board, for it to throw off binary something glitches bad , great video I love your stuff, you and Chris from HVACR videos make some really good content
Thanks man 👍👍I really appreciate your compliment 🤜🤛
Good Video ! Maybe Board is not Grounded or Dirty Ground. Loose wire where wires enter machine. loose wire nut.
Haha , I was going to ask how many Manitowoks were 410A and as I was writing it you said"Lets put this on the right refrigerant..." haha , love your videos !
Yep, I'm definitely not flawless🤫
@@HVACRSurvival but I like your style my friend!
Well thank you, I appreciate your kind words and for viewing my videos.
Some newer ones are 410
board busterz repairs the manitowoc control boards. Takes us 1 day and it's a much cheaper option. Keep us in mind!
Great Job. I charge like that sometimes, too. When I want in running at 100%, I pull the charge and recharge it. You got to do what you got to do.
Thanks Abel👍👍
Impressive little vid Slick Rick ... Hey to Slick Chick ... Lol ... You both are awesome ...
Thanks Eddy 🤜🤛👍👍
Has it happened again? I have a machine with a new board (less than 1 year) that does the same thing. It says it's freezing but the compressor is off and the water system is on. It makes good ice until it randomly glitches.
I've got a brand new manitowoc ice machine and the pan over flows with water sometimes. Its level what else do I need to check
If it's a new machine it should be under warranty? I would have a service guy check it out. Sounds like a water level sensor may not be making good contact.
Kinda packed? Holy crap that was packed. Dirty condenser. That board had issues. I wonder if the that condenser fan motor Isnt working as well from the dirty condenser coil.
I had one acting up about a year ago after a different company changed the board. When I checked to see what software it was running, all I got was gibberish. So I shut the power off and restarted the unit, and I still had gibberish for software. I also found no model or serial numbers on the board.
I had to manually enter the M&S#s and update the software and then had no more problems. Makes you yearn for the old B series😉
I like to check programming anytime I get weird problems.
How do you update the software on the control board?
Usb stick and down load from the factory site
@@HVACRSurvival Thanks! found great info on the factory website
On a CME250AE-1A what would cause the water valve not to get power to it.I measured the resistance across the terminals and got .612 kohm is this normal? after I removed it from the ice maker
612 ohms sounds possibly normal? I don't have their charts in front of me. It could be as low as 30ohms?. I would put it in test mode and verify you've got the rated voltage going to the solenoid.
Where do you get those books?
From the Manitowoc school. They have them at different supply houses go online and look and see where one is near you.
The relays the boards go wacky all the time. Especially on self contained
relays, made of the finest ROHS and new prone to fail contact materials! ( chinesium)
What is the reason blue LCD screen of Manitowoc Indigo series ice machine ?
I don't understand? Blue background makes it is easy to read?
Hi, my compressor is running fine ?? Because the water is running but it’s not making ice. It is cooling inside the bin. Any troubleshooting tips? My tech guy came by and measure the pressure and recommended replacing compressor ? We can’t afford that right now. Last time I did cleaning and reset then it worked. Summer time maybe ? I will be grateful. Thank you 😊🥳😘😁🍉🍉
Most problems are water-related, make sure your water filter is clean and got at least 20 to 30 lb of pressure and make sure your coils are clean and that you ran cleaner through the machine the way it's describes. After that it's hard to say without seeing it.
@@HVACRSurvival Thank you so much! After cleaning. I can make a video and send to you? 😃 Can hot weather made it this way?
@@JM168M If the system has issues like dirty condenser coils, low on refrigerant etc the hot weather can make it worse.
Where did you get that book?
From the manufacturer
Good one Rick 👍
Anything 4 you Greg 😁👍👍. Thanks 4 checking it out!
Them manitowocs can drive you crazy 😜 sometimes
Wow! So many problems!
What is all these fancy electronics in a simple ice-maker, I remember working on Monitowoc ice makers in a Hotel, things were simple, limit switches and one small harvest board. matter of
fact that ice maker probably still works.
Yep 😏👍👍
How much did you charge for this call? How long did it take?
I don't remember, I run 4-6 calls a day so that's several jobs ago since I recorded this. We charge time and material for most jobs unless it's quoted.
Those board always give problem had a problem like that in Barnes and noble band new board install 2 days later recall had to reorder board manufacturer defect
Sounds great ☹️👎👎. Thanks 4 watching!
Good evening! Sir please help me I repair ice machine.. in the monitor display ice machine said Sittings low what is the problem in this ice machine ? Please help me thank you..
Please email me if your a service technician in the refrigeration field. hvacrsurvival@gmail.com
Guess I would first question why a board was replaced before routine basic condenser and machine cleanings were done?
I know you walked into this after the fact, so not trying to knock you down, just my first impression seeing this vid for the first time and being a bit distracted at that.
@@davejohnsonnola2758 I can't go into all those details without creating drama... And that can cause problems
@@HVACRSurvival its all good,... rhetorical questions anyway so long after the fact. Thanks for sharing what you can and do.
Have learned a lot from you and Chris S...as well as Manitowoc annual training which I missed this year's Zoom version, but since I don't have that much time at my facility to dive into the ones we have was just dropping in to try and pick up a tidbit.
@@davejohnsonnola2758 That's awesome Dave, I really appreciate you mentioning that👍👍
Great job and video
Thanks Donnie 👍👍
Very informative video
Thank you👍👍
the roof cond. coil "kind of packed" more like fur rug(self made filter) lol
You're absolutely right, generally a coil that's been neglected will get so dirty that it really won't be internally embedded like you would think.
HELP Ice machine will clean but it won't go back to the regular menu. It only says
OFF
On/ Off Mode
What's wrong??
It worked yesterday
Probably a bad keypad.
@@HVACRSurvival I just don't understand why if the keypad worked yesterday but not today.
But so far that's what I've been told it probably is. Thank you
The test
Good
🤜🤛👍👍🙌
So the other tech installed the board on a Friday......and didn't check anything else....ask him for a copy of his work order with all the pressures and times for 3 cycles....
In a perfect world lol. I did call him and he said everything worked fine at that time. What's interesting is we had to go back several times later for other things which were very suspicious. The water sensor kept falling down three times in a row every week to week and a half. Very weird . I would not put it past the employees to sabotage the machine.
my machine at work doesn't make ice it's rare, it beeps we check everything and can't find the problem.
If it beeps it’s likely not a Manitowoc.
Hello
HPC dirty condenser was very bad.
I had a machine doing something like this once. It turned out it was voltage drops at the outlet where it was plugged in. Their POS machine would flicker as well..
Very unusual only thing i can think of was the relay may have been stook
The LED was not lite in the beginning of the video, that rules that out 🤷🏻♂️. Crazy, thanks 4 watching!
@@HVACRSurvival must have been a microcontroller glitch then and when you did the self relay test it fixed it
Maybe 🤷🏻♂️👍👍.
Could have been due to transient power glitch. Just enough to confuse the controller but not enough for the staff to notice.
True 👍👍
This noise and flash at 3:15 on the Board
I don't understand?
Nice +1 💯💯👍😷😷
Thank you for checking it out 👍👍🤜🤛
@@HVACRSurvival 👍
Those mani logicators seem to take "garbage in garbage out" to heart even though the inputs are not relevant to the process
Honestly they're pretty reliable normally. that's why I had a hard time accepting a brand new board taking a dump right after another board was replaced for whatever reason.? I'm not the one that replaced the other board.
Why don't my water pump, pump water in the first and second sequence
Is it getting power when it should?
Try going back
Turn off condenser soo it will go off on high pressure
If board does not read the error again
U know what's up
Ever heard of ghost codes
They are real
I found a few things wrong later, one of the issues was someone else replace the board and diagnosed it. I came in second and can't fully explain without creating drama.
👍
Thank you 👍👍
Sounds like your at a Wendys. and yea, ive got a local wendys here thats constantly "out of ice". things that make you go hmmm especially after you mentioned they dont want to do anything to it, or proper maintenance.
I've done work for Wendys before and I don't care to do it because it's a grease pit however that wasn't a Wendy's. That's a local fast food place.
@@HVACRSurvival Ahh ok. Kinda sounded like a Wendys. Personally, I like Culvers or a place like that. But they arnt close to me where I ended up moving to.
Yeah we don't have any Culver's near us either. What state are you in?
@@HVACRSurvival deep mountains in north carolina. Closest one is in the city of Ashville which is about an hour and 30 mins out. Closest HVAC youtuber to me would be Ted I believe. :-)
probably better off without ice anyway :))
👍👍👍
👍👍🤜🤛 Thanks Harry!
really seemed like a logic issue to me...
That's what I thought too, kinda weird it happens after the board is replaced.
1 ad for every two minutes of content. I barely got the gist of your video, I am getting carried away into your ads. Sorry man I wanted to support your channel, but thats just way too many ads. Yea its your channel and I dont have to watch. I know.
I can't tell whether they're putting overlays or if it's an actual ad I may have to go through and manually adjust that. Thanks for letting me know.
#18 thumbs uP
Thanks Steve 👍👍