Watch a Pro Wire a 20A GFCI and 20A Receptacle, Any Code Violations?

Поделиться
HTML-код
  • Опубликовано: 4 фев 2022
  • Amazon Prime Free for 6 months for students. Then, enjoy Prime at half the price, just $7.49/month: amzn.to/3NsFy7Q
    Audible Plus Free for 1 month + 2 free books: amzn.to/3Do6Qrr
    To compete to enter the IDEAL National Championship next year: www.idealind.com
    Legrand radiant 15 Amp Decorator Receptacle Tamper Resistant Outlet, Weather Resistant, White, 885TRWRWCC8: Amazon: amzn.to/3Lc5zHv
    Leviton G5362-WTW 20A-125V Extra-Heavy Duty Industrial Grade Weather/Tamper-Resistant Duplex Self-Test GFCI Receptacle, White, 20-Amp: Amazon: amzn.to/3HL3e4l
    Orbit 2DB100-7X Electric Box, 2 5/8" Deep 7 Outlets w/1" Hole Size X-Configuration Weatherproof - 2-Gang - Gray: Amazon: amzn.to/3HuZyTT
    Ideal Industries 47-110J Insulating Wrap Silicone Blue Tape ArmourBand: Amazon: amzn.to/3AYI5Rk
    TayMac MM420C 1-Gang Nonmetallic Extra Duty Weatherproof In-Use Horizontal/Vertical 16-in-1 Standard Cover, 2.75 in, Clear: Amazon: amzn.to/3B1MaEp
    NFPA 70, National Electrical Code (NEC) Handbook Hardcover, 2020 Edition 1st Edition: Amazon: amzn.to/33EqhOK
    National Electrical Code 2020 1st Edition: Amazon: amzn.to/3IdF7el
    National Electrical Code 2020, Spiral Bound Version (National Fire Protection Associations National Electrical Code) 1st Edition: Amazon: amzn.to/3A10iNC
    NFPA 70 NATIONAL ELECTRICAL CODE 2020 NEC Paperback: Amazon: amzn.to/34VQucs
    Journeyman Electrician Practice Exam, 2020 NEC Paperback - January 1, 2020 by Mike Holt: Amazon: amzn.to/3FrvI0Z
    by Mike Holt
    Ugly’s Electrical References, 2020 Edition: Amazon: amzn.to/3lFqWD3
    Ugly’s Residential Wiring, 2020 Edition: Amazon: amzn.to/3lJXQTe
    Ugly’s Conduit Bending, 2020 Edition: 2020 Edition 3rd Edition: Amazon: amzn.to/3qnW2CF
    Ugly's Electric Motors and Controls, 2020 Edition Spiral-bound - July 10, 2020: Amazon: amzn.to/39SbyRB
    Ugly's Electrical Safety and NFPA 70E, 2018 Edition 4th Edition: Amazon: amzn.to/3oxE3Ik
    As an Amazon Associate I earn from qualifying purchases.
    Shipping, Entertainment, etc. Discounts:
    Discounts/free trials on shipping, entertainment, etc:
    Amazon Prime Student 6-month Free Trial: amzn.to/3kFkEVm
    Amazon Audible Plus 30 days free! Listen to thousands of Audible Originals, audiobooks, and podcasts. amzn.to/3gF9jDC
    Prime is just $5.99/month for qualifying government assistance recipients: amzn.to/3BojoNq
    Kindle Unlimited 30 day free trial for both reading and listening: amzn.to/3DrVHFC
    Amazon Prime 30-Day Free Trial: amzn.to/3BojS6c
    Give Amazon Prime as a gift: amzn.to/3DDKX7k
    Create an Amazon Wedding Registry: amzn.to/3mJMfaE
    Audible Gift Memberships: amzn.to/3BmTiKr
    Audible Premium Plus 30 day free trial and Get Up to Two Free Audiobooks, listen to professionally-narrated audiobooks: amzn.to/2Wt4fvt
    Amazon Prime Music: Get unlimited access to 75 million songs: amzn.to/2WE7rEg
    Create an Amazon Baby Registry: amzn.to/3kLKFT7
    Amazon Prime Wardrobe: Choose up to 8 items, keep only what you want, free and easy returns.: amzn.to/3jnRn2b
    Amazon personal shopper, just $4.99 per styling: amzn.to/2UXVOaG
    Amazon Business Account: Create a free account for your business with benefits.: amzn.to/3sUWzO9

Комментарии • 734

  • @constantinejosephides3312
    @constantinejosephides3312 2 года назад +31

    Great I'm apprenticeship ING with habitat for humanity wiring home's and I was contemplating putting an extra receptacle in my bathroom , thank you for the demonstration it will help me!

    • @SparkyChannel
      @SparkyChannel  2 года назад +2

      My pleasure!

    • @madabz81
      @madabz81 2 года назад +1

      Weird I’m working with habitat wiring multi dwelling units as well lol

    • @MariWannaSnipe
      @MariWannaSnipe 2 года назад

      @@madabz81 do you get paid or is it all charity work?

    • @constantinejosephides3312
      @constantinejosephides3312 2 года назад

      @@MariWannaSnipe volunteer

    • @tricklicker69
      @tricklicker69 2 года назад

      It's very sad that most large contracting company is on housing developments do the code minimum of one receptacle per 12 ft wall in a bedroom when you had that one receptacle behind the bed board it's very hard to get the electric blanket and alarm clocks and night lights all hooked up to both sides of the bed for His & Hers the actual cost to put it in an extra extra receptacle is probably less than $10 time and material I have always been one to over Supply the owner of the home in an extra Outlet or two it doesn't cost that much more and it makes people's lives much easier down the road

  • @avengence
    @avengence 2 года назад +79

    I thought Scotty Kilmer did car videos

    • @SparkyChannel
      @SparkyChannel  2 года назад +7

      LOL!

    • @kllgrogto5838
      @kllgrogto5838 2 года назад +2

      😂😂😁

    • @shirkophobe
      @shirkophobe 2 года назад +7

      Maybe he’s Scotty’s calmer electrician brother. 😏

    • @SparkyChannel
      @SparkyChannel  2 года назад +9

      @@shirkophobe LOL, that's funny! When I was in Nashville for the Ideal Championships I invited Scotty to the finals. He said he couldn't make it because it was close to Christmas. It would have been cool if he could have made it. I would have done a video with him!

    • @JohnSmith-lw2bm
      @JohnSmith-lw2bm 2 года назад +2

      I know he sounds just like him, right? Same tone, cadence, inflection, etc.

  • @5_fun_facts123
    @5_fun_facts123 2 года назад +12

    Its so refreshing to hear "bonding" over "grounding" in your videos.

  • @gregr1672
    @gregr1672 2 года назад +1

    Wow! Thank you for the quality of your videos & your explanations ! Top notch ! I love seeing tradesman that know their stuff & do clean work . I am older guy who worked doing electrical work under supervision of heavy industrial electricians who had good old school fundamental trainng. The one guy learned in vo tech & then in Air Force , went into industrial work later in life . He really taught me the importance of trouble shooting & not overlooking the simplest things first ! I learned to ask someone when I ran into something I wasn't totally familiar with . I see the electrician in the video used blue non conductive bands around the terminals .I like those . I usually wrap electrical tape around to protect in a similar fashion . I ve been told ,its a waste of time! I like it as an added layer of protection !

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      Hi Greg! I agree with everything you said. The basics are really important!

  • @luckyhiker3434
    @luckyhiker3434 2 года назад +1

    Wow! You really put a good instructional video together and your narration was just suited perfectly.

  • @timdyer7692
    @timdyer7692 2 года назад +1

    Thanks, Bill! Another very good an informative video. I appreciate your analysis and references to the code.

  • @texastitan6567
    @texastitan6567 2 года назад

    So refreshing to see people passionate in their trade always trying to learn more and be better.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Absolutely! It was so great to be at the championships with all those great electricians!

  • @GAMarine137
    @GAMarine137 Год назад +5

    Never thought I would watch a play by play of receptacle wiring 🤣

  • @TimboStang71
    @TimboStang71 2 года назад +2

    Yahhh I got the violations right. Mainly cause I got hit with these few years ago lol. Was installing a underground 200 foot pipe run and exterior outlets for a home depot tool rental, got inspected and didn't pass cause the outlets weren't weather resistant. Fixed and was "saul good man" love your channel and knowledge sparky you da man !!!!

  • @mikell3087
    @mikell3087 2 года назад +8

    406.4 is specifically for replacing non grounding type recepticals where an equipment grounding conductor does not exist. Since there is a grounding conductor that code wouldnt apply

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      Thanks!

    • @brettsalling
      @brettsalling 2 года назад

      Absolutely. Came here to comment the same thing

    • @hangngoaigiare
      @hangngoaigiare 2 года назад

      @@SparkyChannel no idea why he apply the middle of the code but not the whole thing.

  • @matsfreedom
    @matsfreedom 2 года назад +6

    I've never met an electrician who couldn't nitpick the other guys work, nor an inspector who couldn't fail a perfectly good job.

    • @kevinmach730
      @kevinmach730 2 года назад

      Yep. Same thing in the IT field. I appreciate true experience and knowledge in any fiield, but the bottom line is nothing this guy did put the busines owner or contractor at substanial risk, physically or financially. But some people like to geek out on the code, so there it is...

    • @SparkyChannel
      @SparkyChannel  2 года назад

      True!

    • @kevinmach730
      @kevinmach730 2 года назад

      @@SparkyChannel No disrepsect intend, by the way, I appreciate what you're doing and as a person who does some of their own electrical work, I have learned a lot from your channel and grateful for the education.

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      @@kevinmach730 That's cool, we all need to help each other. Things work better that way.

  • @danieltimmons9928
    @danieltimmons9928 2 года назад +1

    Mr. Sparky I always enjoy your videos sir !

  • @michaell4527
    @michaell4527 2 года назад

    Hey sparky this helps, as an apprentice who forgot a few things from school. Wanted to say thanks.

  • @willschultz5452
    @willschultz5452 2 года назад +1

    Good points you brought up here Bill. I noticed he used a regular screwdriver to install the receptacle to the box. I use one of those hand held electric screwdrivers, especially when installing a whole slew of receptacles. Saves on the old wrist 😂

    • @RB-xv4si
      @RB-xv4si 2 года назад

      Most guys would just use their drill if they didn’t want to bother with a standard screwdriver.

  • @Landesign58
    @Landesign58 2 года назад +1

    Bill, thanks for showing your audience the use of the silicone bands- they are fantastic!

    • @ethelryan257
      @ethelryan257 2 года назад +1

      Pricey, but nice. Now, we get to hear from the 'but they cause heat' crowd. And the 'only wirenuts are any good' crowd.

    • @SparkyChannel
      @SparkyChannel  2 года назад +2

      No problem, thanks!

  • @JP-pf1nj
    @JP-pf1nj 2 года назад

    Great videos. I would you wire a light switch to turn off the non GFCI outlet?

  • @garydudgeon
    @garydudgeon 2 года назад +1

    Good video Sparky. He is methodocal and efficient.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Yes, good observation. Good work pace.

  • @apagan65
    @apagan65 2 года назад

    Hey, I actually got that one right!😊 Thanks Sparky!

  • @LocalElectricianPH
    @LocalElectricianPH 2 года назад

    So sparky..thank you Sir

  • @chilIychilI
    @chilIychilI 2 года назад +1

    I waited to see a spring load type wire tuck into the box. I Always feel like I could do that more efficiently and you have to start that plan immediately. But a shove & hold seemed effective enough for the ideal pro 🤣 I know this is not a demonstration for cosmetic perfection but every once in a blue moon, I'll pop a receptacle open and be pleasantly surprised by the professionalism in the wire tuck. Not very often but it does happen.
    Seeing something straped to the box with 1 and a ½ inches of wire being left is much more common here in philly. Especially if the home owner claims some "crazy unique issue" 🙄 that couldn't possibly be from the install.

  • @Jeff-Lawrence
    @Jeff-Lawrence 2 года назад +1

    HI bill from Sparky Channel
    LOVE IT
    I didn’t realize GFCI receptacles had a weather resistant option.
    Thanks for the lesson and all your effort
    You’re a great commentator as well.
    Perhaps you should have been a sports announcer 🏎
    👍👍👍

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      Oh yes, they've been around for a while now. I told them at the IDEAL championship that if anything happened to their announcer I could fill in. LOL! Thanks Jeff!

  • @renatotuestavilca
    @renatotuestavilca Год назад +1

    Thank you, very helpful

  • @BigmoRivera
    @BigmoRivera 2 года назад

    Thank You 😉👍🏽⚡️My First Time Sein A Brass Fiting

  • @kimberlyrodriguez5794
    @kimberlyrodriguez5794 2 года назад

    Hey, I’m Kimberly Rodriguez a senior at Bronx Design And Construction Academy and currently in the electrical major, my instructor recommends a lot of your videos they have helped me understand NEC requirements and violations that can be easily made, I have learned a lot from them thanks a lot, really appreciated it.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Hi Kimberly. Write me at wpm44@yahoo.com if you would like some Sparky Channel stickers. They are the perfect size for hard hats. Also, I can send some for fellow students if you like as well.

    • @FernandoRodriguez-ur8wc
      @FernandoRodriguez-ur8wc 2 года назад

      @@SparkyChannel Your videos has been helpful throughout our senior year in high school. We’ve applied code regulations when doing our jobs or lessons our instructor gives us. We’ve learned so much by watching your videos, we appreciate you!!

    • @tdnrhbm9144
      @tdnrhbm9144 2 года назад

      @@SparkyChannel Hey sparky, your videos have been very helpful to me and my senior peers in BXDCA, also your conduits bending videos have been a blessing, made conduit bending a little bit more easier, especially the 3 points and 4 points saddle bends.

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      @@tdnrhbm9144 Excellent, great to hear!

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      @@FernandoRodriguez-ur8wc Fantastic!

  • @daveholte7658
    @daveholte7658 Год назад

    Interesting. I just got done wiring this up in my Tuff Shed. Armour band? Hmm did not see that included in box. I used a plastic gang box Cant do the Green Ground configuration to that right? Great video

  • @squarebody8454
    @squarebody8454 4 месяца назад +1

    In washington state the violation would be not wearing your license visibly. Here you have to actively wear your license at all times while doing electrical work.

  • @netpasyanetpasya6381
    @netpasyanetpasya6381 Год назад +5

    1. Greg didn't caulk around the box.
    2. Greg did not use a level to make sure the receptacles are perfectly straight up and down.
    3. Greg did not use a Platinum-Titanium coated screwdriver to prevent scratching the screws.

  • @LarryOohLaLa
    @LarryOohLaLa 2 года назад +1

    Great job brother

  • @micheljauvin3536
    @micheljauvin3536 2 года назад

    very good lesson

  • @ricardobocus6304
    @ricardobocus6304 2 года назад +4

    Me "Judge, I cant do this job you gave me the wrong outlets"
    Judge "Correct, Pass!"

    • @SparkyChannel
      @SparkyChannel  2 года назад +2

      LOL! What else could the judge say?

  • @djjammindave
    @djjammindave Год назад +1

    HELPFUL, LIKE ALWAYS....

  • @BelleRiverHeating
    @BelleRiverHeating 2 года назад

    Can you please do a video on a set of three way two pole switches tide to a fan /light combo. so as to operate the fan and/or light from two different locations?

  • @Eddy63
    @Eddy63 2 года назад +1

    Good and informative vid ... Thx ...

  • @RB-xv4si
    @RB-xv4si 2 года назад +2

    A fourth violation is of 110.3(B). The outdoor device box with 1/2” hubs is only listed for use with threaded conduit (I.e. rigid conduit or IMC). EMT fittings aren’t technically allowed to be used with these boxes. Again, not the fault of this electrician. He used what they gave him to use.

  • @Maatson_
    @Maatson_ 2 года назад +2

    I picked up right away he was not using weather resistant receptacles. Receptacles with the green dot are usually 20amp hospital grade receptacles and they are not listed for outside.

  • @jeremynelson8496
    @jeremynelson8496 2 года назад +2

    That was some fancy Ideal electrical tape.

    • @SparkyChannel
      @SparkyChannel  2 года назад +2

      They are: Ideal Industries 47-110J Insulating Wrap Silicone Blue Tape ArmourBand: Amazon: amzn.to/3AYI5Rk

  • @not_jose904
    @not_jose904 Год назад +1

    Hospital grade gfci is added and standard commercial grade outlet is added

  • @adisharr
    @adisharr 2 года назад +1

    I've never seen a wrap like that, pretty neat!. How long are they supposed to last?

    • @SparkyChannel
      @SparkyChannel  2 года назад

      I don't know. they are quite thick so they should last a long time.

  • @DESPYS1LOSTCITY
    @DESPYS1LOSTCITY 2 года назад +1

    My opinion I would screw down the grounding entering the water proof box from the emt then run it to the wago/wire nuts last gfci and outlet 💡

  • @lancerudy6584
    @lancerudy6584 2 года назад

    Very mice video. THANKS

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Thank you very much! Have a great day!

  • @HoosierRallyMaster
    @HoosierRallyMaster 2 года назад +4

    I'm going out on a limb here, but I think that that section of the NEC only applies when there is no EGC in the box. Since all the work shown has an EGC then you will have to look elsewhere for the labeling requirement.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Thanks!

    • @ethelryan257
      @ethelryan257 2 года назад

      Depends on the inspector, in my jurisdiction, they demand it. Inspectors fancy themselves demi-gods and arguing with them leads to unnecessary challenges.

  • @Drewby98
    @Drewby98 2 года назад

    Also not sure if he had a plastic bushing on the connector inside the panel. Could put it on later in the installation but looked like he was shaping the wires already.

  • @tedlahm5740
    @tedlahm5740 2 года назад +1

    Looking for the breaker end of the install. Thank you.

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      See: Pro Round 2 IDEAL National Championship from Nashville 2021 Troubleshooting and Panel Installation: ruclips.net/video/tKfE4mPtdkQ/видео.html

  • @tcarable
    @tcarable 2 года назад

    It's been awhile since I've done electrical work but the gfcis I know Levitin brand came with stickers and the sticker said ground-fault intercept protected and you would usually put them on the outlets that are away from the GFCI so that the person would know that that's ground-fault protected

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Yes, the stickers come in the GFCI box, good point.

  • @oliverwright8500
    @oliverwright8500 2 года назад +2

    406.4 (D) (2) (C) only applies to grounding type receptacles installed after a GFCI if there isn’t a ground. Specifically. So since the is an equipment ground in this circuit, that section doesn’t apply and no label is needed. If you read the section on on screen in the video it specifically says that. But they should have been weather resistant of course.

  • @VideoByPatrick
    @VideoByPatrick Год назад +3

    Does Lowes sell those Ideal contact rubber band guards ?

    • @djjammindave
      @djjammindave Год назад +1

      AMZAZON....10 BANDS FOR $9.99

    • @wingman2k
      @wingman2k Год назад

      @@djjammindave woof, I'll stick to super 33

  • @EvelynAndEleanor
    @EvelynAndEleanor Год назад

    When Outdoors, can you use the gray plastic conduit into a metal WR gang outlet? Still adding the grounding wire like he did to the box at @1:22

    • @foogod4237
      @foogod4237 Месяц назад

      Yes, as long as the metal box/etc are properly bonded to the ground wire (which is required anyway), and the right type of connectors are used to join the conduit to the box, there is nothing wrong with using plastic conduit with metal boxes (or vice-versa).

  • @VOLTRONDEFENDER4440
    @VOLTRONDEFENDER4440 10 месяцев назад +1

    The gfci is hospital grade? Red dot on receptical

  • @tedmcdonald3377
    @tedmcdonald3377 2 года назад +1

    Good morning Bill, have a great weekend 😎🛠️😎🛠️😎

  • @clydenakashima7393
    @clydenakashima7393 2 года назад

    Yes. and the scene at Hapuna on the Big Island.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      If I was there right now I'd be out snorkeling!

  • @RobertLeBlancPhoto
    @RobertLeBlancPhoto 2 года назад +1

    It's nice to see pros use the Ideal Push-In connectors. I love em, even though a lot of pros will only ever use wire nuts.

    • @ethelryan257
      @ethelryan257 2 года назад

      Tell me about it. There's no comparison when it comes to long-term reliability in residential work. Just be sure to go with WAGO and not the cheap knock-offs.

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      Thanks!

    • @RobertLeBlancPhoto
      @RobertLeBlancPhoto 2 года назад +1

      @@ethelryan257
      I like Wago for lever lock type connectors, and Ideal for the Push-In type. :)

    • @kevinjensen7752
      @kevinjensen7752 2 года назад

      37 years as the IBEW contractor and employee over 10 to 14 employees at a time I would never allow them to use Wago or ideal push in connectors as I would never allow them to use backstabbing into a receptacle your contact surface area of the wire is very minimal on each of these a good wire nut covers three quarters of an inch or 5/8 of an inch of solid copper that is Twisted together in a very secure manner thus giving you a much more surface area conductivity

  • @theoisaac9948
    @theoisaac9948 2 года назад +2

    Good channel

  • @ellsobrien
    @ellsobrien 2 года назад +2

    Great video. I don't think I could do that work with gloves on. LOL. One QUESTION: Why such the long tails in the non-GFCI receptacle?

    • @IceBergGeo
      @IceBergGeo 2 года назад

      Makes it easier to install or remove if you have to do just one.

    • @Sparkeycarp
      @Sparkeycarp 2 года назад

      Yep, try that much wire in a plastic box.

    • @IceBergGeo
      @IceBergGeo 2 года назад

      @@Sparkeycarp plastic or metal, doesn't matter. It's the size of the box that does. Just remember, you have to have a minimum length conductor able to pull out of the box, and he's got it for either receptacle, one at a time.

  • @AaronVillatoroLuna
    @AaronVillatoroLuna 2 года назад +1

    Cool video Bill.

  • @patrickcowan8701
    @patrickcowan8701 Год назад +1

    The cover is weather resistant but the sticker on the load side is important for the inspector otherwise it will all work fine.

  • @mdunbar008
    @mdunbar008 2 года назад

    So, code question. I wish I could post a picture of this thing. I'm looking at a nonmetallic old work box, that has been "converted" to new work by driving nails through it, there is a 7/8 hole drilled in the side for wiring with no clamp, and the switch is held in the box with wood screws. Any code violations here?

    • @harveylong5878
      @harveylong5878 2 года назад

      YEP. Homemade hack box isnt code compliant. the nails alone are a violation , the butchered make your own hole is another failure

  • @maggiedoolin4632
    @maggiedoolin4632 2 года назад

    I'm and old election when we ran a GFI circuit we had to ground the conduit to the GFI also things have probably changed it created lots of problems.

  • @charlesjohnson6073
    @charlesjohnson6073 2 года назад +1

    should they be tamper resistant as well? I read nec 2020 406.12 but I'm still not sure about outdoor locations.

    • @saberx08
      @saberx08 2 года назад

      Well, NEC 2020's 406.12 (1) talks about dwelling units listed in 210.52. 210.52 (E) specifically mentions outdoor outlets. So, I'd say "yes", they should be tamper resistant as well.

    • @charlesjohnson6073
      @charlesjohnson6073 Год назад +1

      That's what I thought. Thank you for the info saberx08.

  • @jamesmcguffey3569
    @jamesmcguffey3569 2 года назад +4

    The GFCI is a medical grade device, not rated for exterior applications. Also I see no WR stamp on the 20a Duplex Receptacle either.

  • @charlesmclaughlin8845
    @charlesmclaughlin8845 11 месяцев назад +3

    My customer was pissed that WT receptacles cost $10 more, but after i explained that it’s NEC code he came around to buying them

    • @SparkyChannel
      @SparkyChannel  11 месяцев назад +1

      I hear that!

    • @jimsummers487
      @jimsummers487 7 месяцев назад +1

      Wouldn’t a used fire extinguisher be cheaper?

  • @brucebo
    @brucebo 2 года назад

    I pulled 2 hot, one neutral and one ground wire through flex conduit to make a whip with 2 circuits (2 duplex outlets) on it. Can I still get GFI protection to these outlets/circuits? Or do they each need a dedicated nuetral? GFI recepticals, or GFI breakers?

    • @MrJohnpro7
      @MrJohnpro7 2 года назад

      They will both need a GFI outlet. But if they are somehow on the same breaker then replace the breaker with a GFCI

    • @foogod4237
      @foogod4237 Месяц назад

      Separate neutrals are not required on the feeder circuit. If this is just feeding two 120V receptacles (one on each hot leg) then you will need two GFCIs (one for each hot wire). If you will be using the GFCIs to protect other downstream outlets, then they will need to have separate neutrals going from the GFCIs to the downstream outlets (you cannot tie the neutrals from the "load" side of the GFCIs together).
      You can also use a single (dual-pole) GFCI breaker in the box instead, but that can be more expensive.

  • @DasSnakeBoy
    @DasSnakeBoy 2 года назад

    Also was the back plug screw caulked? Nice video

    • @SparkyChannel
      @SparkyChannel  2 года назад

      No, the competitors weren't given any caulking.

    • @milantrcka121
      @milantrcka121 2 года назад

      @@SparkyChannel Supply chain problem or "I forgot"?. I thought this should to be a demo how to do things right.

  • @chevinbarghest8453
    @chevinbarghest8453 2 года назад +1

    The earlier shot in the vid showed both items to be marked 'WR', but the items at the end of the vid were not -----hence the infractions. That threw me for a minute. There earlier shot must have been 'how it should be'...

    • @SparkyChannel
      @SparkyChannel  2 года назад +2

      Yes, the earlier photo was from a previous video of mine.

  • @88yo88
    @88yo88 2 года назад +1

    i will give you a like and subscribe for an excellent video and for the spanish translation (white/blanco), very very good, well done!

  • @seabass22
    @seabass22 2 года назад +2

    Are the bands for code? Never seen them before.

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      Yes, they are UL listed for their purpose.

  • @ExecOpsN7
    @ExecOpsN7 2 года назад +2

    The shop I worked with never wrapped devices in tape like that. I know florida code requires it. Is that a stat to state thing? As for the supply chain problems, can cornfirm jobs were held up by lack of bath fans and breakers.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Yeah, the show had to go on with what they had.

    • @ethelryan257
      @ethelryan257 2 года назад

      Inspectors here like to see tape or those expensive ArmourBand wraps. I don't regard code as the maximum limit, if it's not required but good practice, we do it.
      I want people to look at my work fifty years after I'm gone and say, 'yup that was old Ethel. Despite being a woman, she was good. And, yes, the sexism won't ever leave the trades.

    • @patrickobrien4322
      @patrickobrien4322 2 года назад

      Not to mention its safer if you have to get in the box while live

  • @Sparky-ww5re
    @Sparky-ww5re 2 года назад

    I noticed these are NEMA 5-20 receptacles. Are these connect to a 20 Amp rated circuit, if not, that's a code violation, but 15 or 20 amp 125 or 250 volt receptacles shall be permitted to be used on a 20 Amp circuit.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Correct. It was connected to a 20A breaker.

  • @dakotavaughan3768
    @dakotavaughan3768 2 года назад +2

    So was this competition participant supplied devices or competition supplied devices?

    • @SparkyChannel
      @SparkyChannel  2 года назад

      He was supplied devices but they had supply chain problems.

  • @EgadsNo
    @EgadsNo 2 года назад

    Got it right, but I never like to tighten down on the 10/32's to push the receptacle into the outlet. Sometimes that can force unintended damage onto wires inside a box. Not really a big concern with this box not being overloaded with wires, but still part of my common practice.

  • @hangngoaigiare
    @hangngoaigiare 2 года назад +3

    I think you wrong about the marking. The marking as gfci protected only apply when you replace none grounding type (2 prongs) with grounding type receptacle (3 prongs). In this case I don’t think you have to say this receptacle is gfci protected because it has to have gfci protected no matter what when installing outside per current code. Still thanks much for sharing I don’t think anyone know everything about the NEC. I see even the whole inspector department of a big city (5 inspectors total) miss understood about 210.12(D)(2) exception too.

    • @BlueCollarGaming11
      @BlueCollarGaming11 2 года назад +1

      This was my thought. That code is in reference to replacing a 2 wire non grounded receptacle with a gfci, or putting one at the start of the line to protect plugs downstream

    • @songsfromnowhereproject
      @songsfromnowhereproject 2 года назад

      Yeah you are absolutely right

  • @antony1m
    @antony1m 2 года назад

    What gauge wire should you use on a 20 amp receptacle @SparkyChannel

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      12 gauge or bigger if necessary due to voltage drop.

  • @johnhanson974
    @johnhanson974 2 года назад +2

    Whose fault were the code violations? Did he have a choice of devices or did he have to use what he was given?

    • @SparkyChannel
      @SparkyChannel  2 года назад +2

      Supply chain problem. The show had to go on with what they had.

  • @bretgreen5314
    @bretgreen5314 2 года назад +1

    Good info. I would argue that the "GFCI Protected" label is only required where there is no equipment ground present. The typical scenario is replacement of a non-grounding type receptacle with a GFCI-protected grounding type receptacle (in this scenario the receptacle itself can be a GFCI type, or it can be protected by an upstream GFCI device). Then both "GFCI Protected" and "No Equipment Ground" labels are required.

    • @saltsidellc
      @saltsidellc 2 года назад

      No, when the down stream receptacles have a ground and are GFCI protected they get that sticker, when they don't have a ground they also get the no equipment ground sticker.

    • @bretgreen5314
      @bretgreen5314 2 года назад

      @@saltsidellc Could you please reference where this is stated in the code? Thank you

    • @dazeman27
      @dazeman27 2 года назад +2

      Agreed. His reference was directly referring to a branch circuit without a ground being protected with a gfci

    • @yourelectricman
      @yourelectricman 2 года назад +1

      Realistically, imagine those labels in a millionaires home? Not a chance. (they will have them removed instantly.) Even at anyones home, you think the homeowners going to replace that sticker that was on that plate ? Nah. Besides, if your a pro and don't have a gfci tester when troubleshooting, tgan you no pro. I Think that code was for well before the days of having said tester.. We now have breakers arc/ground fault that protect whole floors mainly basements. That code is so outdated.

  • @anko7574
    @anko7574 10 месяцев назад

    Can you explain the reason to ground recepticals with green wire if self grounding recepticals are used with metal box (outlet).

    • @foogod4237
      @foogod4237 Месяц назад

      NEC does not allow using the box itself as a grounding conductor.
      This is because the ground bonding of the box and the screw connections from the receptacle to the box are not designed, tested, or rated to support the current carrying requirements of a full protective grounding path. That's just not how they're intended to be used.

    • @pld8993
      @pld8993 Месяц назад

      @@foogod4237 Incorrect. Read the NEC, box is allowed as bonding means for devices.

    • @foogod4237
      @foogod4237 Месяц назад

      @@pld8993 i'd be happy to. What subsection does it say that in?

  • @jesseestrada4290
    @jesseestrada4290 2 года назад +1

    So in competitions all that technical codes do not apply then?

    • @SparkyChannel
      @SparkyChannel  2 года назад

      The NEC code definitely does apply. They had to make a few exceptions for supply chain issues though.

  • @willembos8367
    @willembos8367 2 года назад

    so different from like the EU. iam an sparky in the netherlands. all our circuits have gfci protection [30 mA]. and the breaker disconnects both live and neutral. so we cant mix neutrals.

  • @libertarian1637
    @libertarian1637 2 года назад

    Seeing this I had to double check the code, something that I haven’t done in some time as on the commercial side we install a lot of conduit and use the conduit itself as the equipment bonding conductor and rarely pull grounds; it’s been so long that we’ve done it that way I thought maybe the code changed and I didn’t even realize but nope still in 2020 NEC §358.60. For us it’s all a money thing as it saves 1,000s of feet of copper by using the conduit. I like the wet location boxes though, over say 4” JBs for receptacles and switches as they are solid; I’ve always been worried about reachable knockout boxes and kids pushing a knockout in with their little fingers. While the wet location boxes cost more they’re what’s in my basement and garage as they just offer a better level of protection, and with a nice stainless cover they don’t look to shabby either.
    As I’ve had to diagnose my fare share of de-energized receptacles only to find out they’re controlled by a GFCI I appreciate the marking and must say it’s one I notice is rarely done. I once saw a bathroom outlet not work because a GFCI was tripped; the GFCI though was located outside under the deck, despite having another GFCI in the bathroom some 6 feet from the first outlet, they wired the newly added outlet off the deck GFCI. May have been for more direct wiring but without labeling it, not that a simple label would have told you which GFCI controls is, would have helped much. One big thing you see in the commercial space that residential could benefit from is labeling and keeping track of additions to help with tracing.

  • @stevethomas5849
    @stevethomas5849 2 года назад

    How often are the Codes updated due to an ever-changing technology. In Britain we have the Wiring Regulations officially BS7671. Every 10 years but with Admenments of which 3 are allowed with that 10 years duration. Presently we are on 18th Edition ( 2018)Admenment 1.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      We revise our NEC every 3 years. The last revision was 2020 and the next one will be 2023.

    • @harveylong5878
      @harveylong5878 2 года назад

      the NEC Is updated but each state can be on whatever version of the NEC. plus states, jurisdictions modify the NEC. NY is notorious for amending the NEC

  • @smacpost3
    @smacpost3 11 месяцев назад +1

    Why you got the panel "outside"?

    • @TomCee53
      @TomCee53 7 месяцев назад +1

      This is an exercise setup, not a real home.

  • @TheForgottenMan270
    @TheForgottenMan270 2 года назад +1

    Paused the video at 6:26 to point at what looks like violations. Neither receptacle appears to be weather resistant nor tamper resistant.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      They are not WR. I think they are TR though. They had supply chain problems.

  • @stanleykeith6969
    @stanleykeith6969 Год назад +2

    Sparky, Hello. Can you tell me why the ground should be on the bottom. I have seen it done both ways. Tell me why it should be up on down. A lot of people do it both ways, which way is right. Also can I use two GFCI outlets in the same box and have them controlled by a switch ? Thanks !

    • @IzaguirreC
      @IzaguirreC Год назад +2

      Any particular reason why you want two GFCIs in the same box? One GFCI should be enough to protect a regular outlet used as load.

    • @TomCee53
      @TomCee53 7 месяцев назад

      Up and down doesn’t matter. There are many videos arguing this point. The only wrong way is if it is specified by the homeowner or contract.

    • @TomCee53
      @TomCee53 7 месяцев назад

      You can switch them with no problem if you wanted then on separately you would need two switches and two GFCIs.

  • @benjurqunov
    @benjurqunov 2 года назад +2

    I spotted the non WR devices. But only after I noticed the GFCI was Hospital Grade, then I thought ”wait a minute...”

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      Supply chain issue, but you're correct!

    • @Maatson_
      @Maatson_ 2 года назад +1

      Exactly what I spotted , the green dot. Dead giveaway hospital grade 20 amp outlet

  • @michaelsteakley1331
    @michaelsteakley1331 2 года назад +1

    The load receptacle had its own ground wire attached, so I don't understand the third violation.

    • @gonzomalan
      @gonzomalan 2 года назад

      the third violation is not marking the grounded receptacle as GFCI protected, such as using the blue sticker seen at 7:57.

    • @wingerrrrrrrrr
      @wingerrrrrrrrr 2 года назад

      Still missing the required No Equipment Ground marking-
      "An equipment grounding conductor shall not be connected between the grounding type receptacles."
      That implies the ground should remain unconnected.

  • @atmacm
    @atmacm 2 года назад +3

    I definitely don’t recommend taping or installing the ideal bands on outside GFCIs. Moisture can collect on the tape/band and create a path from the phase to ground, causing a nuisance GFCI trip.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Interesting!

    • @atmacm
      @atmacm 2 года назад

      @@SparkyChannel not saying this will always happen, just my experience with the humidity here in Kansas. If the box is sealed well it might not be an issue.

  • @sparky7146
    @sparky7146 2 года назад

    Nice video. If it’s residential application they would need to be TR. I think the screw terminals should be torqued?

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Thanks! 14-18 in-lbs suggested on the receptacles.

  • @joeturnip4216
    @joeturnip4216 2 года назад +1

    As most of the outlets available these days are Tamper Proof which makes it impossible to plug anything into them, might as well call the power company and terminate the account.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Some TR receptacles really are difficult to work with, true.

  • @davidgagnon2849
    @davidgagnon2849 2 года назад

    Two comments; didn't see a nylon bushing on the box connector in the panel. Also, since he was supposed to label the GFCI with a GFCI sticker, was he also supposed to label "No Equipment Ground" as well? When reading that section of the Code it is unclear to me.
    Thanks, Sparky for another great video!

    • @illestofdemall13
      @illestofdemall13 2 года назад +1

      Why would he label it no equipment ground? There is an EGC (notice all the green ground wires he connected). He just needed to label the receptacle with "GFCI Protected" sticker.

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      @@illestofdemall13 Hi Kris! That's the way I see it as well.

    • @mattolson7037
      @mattolson7037 2 года назад +4

      @@illestofdemall13 Actually you don’t need to label the other receptacle at all. That only applies to receptacles without an equipment ground. It seems like he misinterpreted the code

    • @stevens4826
      @stevens4826 2 года назад +1

      @@mattolson7037 This is also my take on it. That code section is for replacement of ungrounded receptacles.

    • @robert-ne1835
      @robert-ne1835 2 года назад +1

      Also, a connector bushing is not required for wires smaller than #6 (or is it #6 and smaller?).

  • @michaellindell737
    @michaellindell737 2 года назад +1

    I’m not a professional electrician, but why is there a green grounding conductor to the panel if you’re using EMT? That’s not a requirement, is it?

    • @joshdoeseverything4575
      @joshdoeseverything4575 2 года назад +1

      to my knowledge you are correct

    • @billrobert3226
      @billrobert3226 2 года назад +1

      correct but maybe the competition specifies a separate grounding conductor

    • @ethelryan257
      @ethelryan257 2 года назад +1

      I never trust EMT as my sole ground in new construction. I want my path to ground to have the least resistance possible, today and decades of rust from now. Ohm it out, you'll be unpleasantly surprised how poor the connection often is.

    • @richclark5478
      @richclark5478 2 года назад +1

      EMT connectors may not be rated for bonding

  • @joeyponomarev9883
    @joeyponomarev9883 2 года назад

    Weather resistant plugs necessary for exterior.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Yes, a little silicone caulk on the threads works.

  • @deepPuddlesarefun
    @deepPuddlesarefun 2 года назад +4

    Looks like the armor bands took the most amount of time to install...

    • @SparkyChannel
      @SparkyChannel  2 года назад

      LOL!

    • @Sparkeycarp
      @Sparkeycarp 2 года назад

      Never seen them in 20 years of being an electrician. Just tape.

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      @@Sparkeycarp They're fairly new.

    • @ethelryan257
      @ethelryan257 2 года назад

      @@Sparkeycarp They're up and coming but way too pricey. Two quick wraps do me just fine.

  • @donl1410
    @donl1410 2 года назад

    Hey Bill. You covered the labeling of down stream GFCI protected receptacles in your video, "Do Stickers Need to be Placed on Grounded Receptacles Protected by GFCI and AFCI/GFCI?". I agreeded that labeling is not required. The article quoted here, as mentioned by others, is for installing grounded receps on non-grounded systems protected by GFCI devices.
    The only obscure reference might be, 110.3(B) listing/instructions. Leviton GFCI instruction say to install labels on protected devices in the testing documentation. The only time I've labeled is per 404.6 (D)(2)(C). I've never been called on general labeling. Our inspectors test for protection on required receptacles.
    Corrections are always appreciated to my statements.

    • @SparkyChannel
      @SparkyChannel  2 года назад +4

      I understand what you're saying. If you know your inspector won't require that the protected receptacle be marked then that's OK with me. I always put on the stickers, then the users know that the receptacle is protected. Thanks Don!

    • @ethelryan257
      @ethelryan257 2 года назад

      In my jurisdiction, it is a bug-a-boo which inspectors love to fail you on. I insist on it, my apprentices think I'm a daft old lady, but arguing with inspectors over the fine points of code is only going to result in the digging until they find something.

    • @donl1410
      @donl1410 2 года назад +1

      @@ethelryan257 I don't argue. I just have them prove me wrong. If I'm wrong , I'm wrong, I'll accept it. Some inspectors have nothing better to do than pick some obscure code reference, like GFCI labeling, and see who they can nail. I don't buy it. We have cross trained inspectors in Oregon for residential, ie building inspectors who take an electrical course to do electrical inspections. They pick some building code that reflects upon the electrical code and can enforce it. like light fixture encroachment into stairwells...Like I really was aware of that! But it proved me wrong.

    • @ethelryan257
      @ethelryan257 2 года назад

      @@donl1410 It just depends on how much your local code authorities let inspectors deviate from UBC and NEC. In my county, they are demi-gods and there is no recourse. They are also vengeful and petty.
      There is no 'prove you wrong' to it - they can and do red tag and slap up the orange 'stop work' orders on a whim.
      Now, one county over, totally different. I had an inspector get upset a few years ago because I used Wago 221 connectors. He demanded every one be pulled and wirenuts used. I asked why, when they were not only code but made for a safer and cleaner install on old work.
      He said they were just like backstabbed receptacles. I pulled the code book, and the listings on the Wago 221s and he realized he'd just been listening to nonsense, it was the first time he'd seen them.
      Passed.
      In my county? One does not argue, one does not 'let be proved wrong' one thanks the god for pissing on us and calling it warm rain.
      Lucky you.
      As to labeling, I regard it like that rock band who put a clause in their contract that no M&Ms of a certain color could be in their break room - it's a sign of conscientious workman like attention to detail.

  • @mdunbar008
    @mdunbar008 2 года назад

    Well I learned something. I've never heard of or seen these WR devices, nor have I ever seen one installed by a professional.

    • @SparkyChannel
      @SparkyChannel  2 года назад +2

      They say that any day you learn something new is a good day!

    • @ethelryan257
      @ethelryan257 2 года назад

      I don't imagine box stores carry them in stock, though our local Walmart does!

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      @@ethelryan257 Yes, they are a little harder to find.

    • @mdunbar008
      @mdunbar008 2 года назад

      @@SparkyChannel So are the WR required for indoor wet or damp locations as well? Specifically looking at locations where the receptacle could be expected to be sprayed with water from a hose.

  • @cadewey6181
    @cadewey6181 2 года назад +3

    Don’t forget the arc fault breaker in the breaker box. With GFI and arc fault, that sucker will never work. There is nothing safer than that!

    • @suspicionofdeceit
      @suspicionofdeceit 2 года назад +4

      Of course it will function properly, a GFCI installed on an arc fault circuit will indeed work.

    • @ethelryan257
      @ethelryan257 2 года назад

      ? I don't see the problem?

    • @cadewey6181
      @cadewey6181 2 года назад

      @@suspicionofdeceit Just do not plug in a freezer or other cap start device since the GFI sees power charging the capacitor and not returning which may trigger it.

  • @mikefochtman7164
    @mikefochtman7164 2 года назад +3

    That paragraph (c) quoted is for replacing non-grounding receptacles with GFCI fed ones. I'd say it doesn't apply since he wasn't doing that. If you DO think it applies, then why didn't you mention the 'No Equipment Ground' label? The paragraph you cited says BOTH labels.
    Now before you start to reply, I'm sure there IS a paragraph somewhere that says it should be labeled 'GFCI Protected' and it should be labeled. Just NOT the paragraph you show in the video.

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Thanks, good attention to details!

    • @ethelryan257
      @ethelryan257 2 года назад

      @@SparkyChannel I admire your tact. I'm not a lady, my response would have been a bit...frostier.

  • @mattweeks2272
    @mattweeks2272 2 года назад

    Wouldn’t those receptacles also have to be tamper resistant?

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      Depends on the situation and commercial or residential. But good point!

  • @barrybentham5684
    @barrybentham5684 2 года назад +30

    With all due respect to my fellow electricians over the pond, watching this video, I think European/UK electrical installations are much better, "Simplification" is the word.

    • @markwison4286
      @markwison4286 2 года назад +2

      Ya no, nothing in Europe is better than America. 🤷

    • @tttarms1970
      @tttarms1970 2 года назад

      @@markwison4286 the food is....

    • @hangngoaigiare
      @hangngoaigiare 2 года назад

      How so?

    • @kornelsnow3639
      @kornelsnow3639 2 года назад +3

      @@tttarms1970 and we at least have healthcare america is literally a third world country with a Gucci belt

    • @josephpimentel4624
      @josephpimentel4624 2 года назад +1

      @@kornelsnow3639 we have healthcare

  • @chrisavcs
    @chrisavcs 2 года назад

    Never seen a fs box used with emt before.

  • @ip5232
    @ip5232 2 года назад +3

    All looks good to me but I see how he just push all the wiring to the back of the box , when I had seeing others and I do it my self to bend them nicely like in a accordion way to be able to be accommodated in the back or if they need to be pull out it can be easy ,my opinion

    • @SparkyChannel
      @SparkyChannel  2 года назад

      Thanks!

    • @jimbojames9370
      @jimbojames9370 2 года назад +1

      Hey J CM, just an explanation of why that technique is not used in this alplication: In your house you would be using romex (NMD-90) which contains solid wire. Here, he is using stranded THHN which won't bend or stay put the same way as solid wire. Cheers

    • @ip5232
      @ip5232 2 года назад +2

      @@jimbojames9370 I know , and agree but I still don't just push them in like that I try my best to accommodate them, it was a bit of a bother thinking he was doing it for a competition and people was going to look at it I would think he would do the best to "try " to bend them in nicer

    • @jimbojames9370
      @jimbojames9370 2 года назад +2

      @@ip5232 couldn't agree more. Part of the judging I'm sure is on speed... just as that seems to be all the customer cares about now... "how fast can you get that done?" At the end of the day it seems now the only one holding us accountable is ourselves... people don't tend to notice workmanship anymore....

    • @atmacm
      @atmacm 2 года назад +2

      He’s using solid wire in this video

  • @dennisnoone7427
    @dennisnoone7427 2 года назад

    Whats about a stranded ground wire, I thought those connectors were only for solid ones?

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      This video has solid wires.

    • @dennisnoone7427
      @dennisnoone7427 2 года назад

      @@SparkyChannel i see, i was watching on my phone and didnt noticed it thanks

    • @SparkyChannel
      @SparkyChannel  2 года назад

      @@dennisnoone7427 No problem.

  • @michaelbradley7529
    @michaelbradley7529 2 года назад +2

    So, the only violation that was in his control to correct was labeling the grounded receptacle as GFCI protected (labels come inside the box of the GFCI receptacle).

    • @JasonSmith-iz3xj
      @JasonSmith-iz3xj 2 года назад

      Also the devices were Not weather resistant type WR...

    • @michaelbradley7529
      @michaelbradley7529 2 года назад +1

      @@JasonSmith-iz3xj That was a supply issue and not in his control during the competition. From what the video said.

    • @SparkyChannel
      @SparkyChannel  2 года назад +1

      @@michaelbradley7529 True, that wasn't under his control.

    • @johnhill8958
      @johnhill8958 Год назад

      I think the video was cut off before he was truly finished. You didn't get to see him re-open the cover and put the label on. Just like Zenith TV's, the quality goes in the cover before the label goes on.