How to rectify Electric shock touching the wall? | Electrical Express | TAMIL
HTML-код
- Опубликовано: 15 сен 2024
- Please visit our website for more information
vkjsolutions.com/ Electric shock touching the wall
1.What are the Reasons?
2.how to trace failure place?
3.How to rectify?
4.awareness video
Wet Walls and Electrical Shocks:
If the water comes in contact with live electric wire either in a switch plate or naked joint, the conduction of current will start via water through earth. The entire wet wall will start giving shock. If earth path through building walls and floors has considerable resistance, the amount of current will be less. If the supply is on, the water touching with naked wire will cause the same shock as with live wire.
Join my face book group
click link. / 558083051460112
LIKE | COMMENT | SHARE |
SUBSCRIBE
**************************************************************
CONTACT DETAIL
**************************************************************
Email : vijayakumarariyur@gmail.com
**************************************************************
Hello friends, Welcome to "Electrical Express Tamil" My Channel motivation is Easy to Understand, Electrical Tech Videos in Tamil, and Get Latest Tech Updates in Tamil , We do Tips and and also Innovation, I wanted each and every Individual whoever is interested in electrical technology to be able to understand it in the easiest possible way,
Thanks.
-Vijayakumar.K
**************************************************************
உங்களுக்கு எது போன்ற வீடியோகள் வேண்டும் என்பதை கமெண்ட் - ல் குறிப்பிடவும்.
மேலும் பல விடியோவுக்கு சப்ஸகிரைப் செய்யுங்கள் நன்றி ..
**************************************************************
DISCLAIMER: This Channel DOES NOT Promote or encourage Any illegal activities , all contents provided by This Channel.
Copyright Disclaimer Under Section 107 of the Copyright Act 1976, allowance is made for "fair use" for purposes such as criticism, comment, news reporting, teaching, scholarship, and research. Fair use is a use permitted by copyright statute that might otherwise be infringing. Non-profit, educational or personal use tips the balance in favor of fair use.
**************************************************************
/ allinonejana Shopping online BUY using the links below & Support Us
amzn.to/3hau4qt
Good explain but ceiling fan body achunalum antha complaints varum thank you so much
நன்றி சகோ
Rubber bush also should be in damaged condition at that time.
Enga veetulayum wall la current varudhu ceiling fan regulator la spark adchi smoke varudhu idhuku enna reason epdi sari panna
@@ElectricalExpressTamil 0
Thank you same problem
Romba nalla explain pannika anna thanks 👍👍❤❤
Super sir my home also same problem
Post more videos sir like that
அருமையான விளக்கங்கள் மற்றும் தகவல்கள் 👌👌
உங்கள்.சேவைக்கு.நன்றி.நன்பரே
Neat analysis, various causes in depth explanation.Thank you Sir
Useful information Supper anna
Super explanation sir.... Thank you.... Continue doing the best....
உங்கள் தகவலுக்கு நன்றி
Good explanation. best wishes
அருமை எளிமை....
Great explanation sir, thank you so much
Thanks sir very useful information
I will see your every video sir, amazing and that was very useful, I know about roof piping but I am confused sometimes to do that
Already i saw your comments in my previous video.
I will help you in any form
Feel free to contact me 7010223071
very good Explanation
Sir intha mathiri problem vantha rccb trip agatha
Can you upload a video about big house roof piping?
Pls call 9790091294 for details 😎
Use FULL information
Sir, good information.
db and switch box wire termination பற்றிய வீடியோ போடவும்.
Good one. Nice info
Good effort sir
Good avernes thankyou sir...
Good information
Super explain good
Thanks
Sir house wiring &home applance wiring பற்றி course நடத்துங்க sir. நன்றி sir.....
Good explain
அருமை
Super video sir
Super
Fan or light switch on or off pannumpothu LED tv off agi on aguthu ithai eppadi sari pannamudium
HDMI cable port a replace pannunga.. sari airum...
அண்ணா electrical wiring quotation anupunga 1 point yevlo agum yella detailsum anupunga......
shop la shutter ah thodum podhu eppavachi earth adikidhu enna aachu nanba
Super bro
Joint kalai pattri video upload pannungal.
Enga veetla ceiling fan regulator spark agi smoke vanthuchi so na main switch and fan switch rendayum off panniten but adhuku apromum fan suthite iruku why?
Two. Separator single phase line how to one summerself motor ficx pls tell connection
Super Sri
What's the minimum size wire to be used for 5, 15 & 20 amps sockets.
5amps socket 1.5 sqmm wire
15 Amps socket 2.5 sqmm wire
20 Amps socket 4 sqmm wire
Above sqmm is enough rating
Hi star delta starter pathi practicals podunga
How to set molde pipes set very easy pls tell me sir
Super anna
Enga veetlauum sevuthila current pass aguthu enna reason pls sollunga
Enga veetlaium dha
Solve pananitingla
Wet grinder motor க்கு earth wire connect செய்வது எப்படி என்று சொல்லுங்க ஜி
🙏wet grinder இன் 3pin socket இல் earth connection கொடுங்க நண்பா
9790091294
Thanks you sir
வீட்டு Meter connectionல் இருந்து மின் கம்பத்திற்கு எடுத்து செல்லும் wire size எத்தனை square meter இருக்கனும். அது aluminum or copper எது சிறந்தது. Single phaseக்கு எத்தனை square meter பயன்படுத்தலாம். Three phaseக்கு எத்தனை square meter பயன்படுத்தலாம். விரிவாக விளக்கம் வேண்டும்
Singlephase 4sq.mm threephase6sq.mm
அண்ணா எர்த் வயரில் ஷாக் அடிக்குமா மீட்டர் வழியாக பூமிக்கு செல்லும் கம்பியில் ஷாக் வருமா வந்தால் என்ன செய்வது
3 phase wiring diagram podunga
Induction stove is 1800 watts, 1.5 ton AC is about 1800 watts. Then why we use metal clad socket & top for AC only.
Main reason is due to, "shoddy workmanship". Refer dictionary for Tamil meaning.
Why we face low voltage problem during summer.
1.Ambient temperature goes to high
2.All transformers in full load
3.Usage of electricity in summer season high
@@ElectricalExpressTamil so you are telling that due to higher ambient temperature, the lines are not able to carry the rated amps. Moreover due to peak load the transformer also loses its full capacity. As a result voltage drops. During winter the ambient temperature is within limits for the transformer & lines, and also load is less. So we get normal voltage. This is eg on practical Ohm's law.
Regards
Sorvs 2 singles phase neutral 2 link ok ?
MCB, RCP, பைபாஸ் ❓ என்றால் என்ன ங்க ஐயா ❓
What is el point explain
சிங்கில் பெஷ் ஒயரிங் வீடு சர்வீஸ் வலிக்க வேண்டிய மெட்டிரியல் சோல்லுங்க
Hi
Metal box use pannum podu company scerw elama kurmiyana scerw podum podu supply wire la murukum podu metal box suply erukum but metal box earthing pannum podu supply ground ku poguma sir&wall la suply erukuma sir
Sollunga sir
இரண்டுமே
சுவர் ஈரமா இருந்தா சவற்றில் ஷாக் அடிக்கும்
@@ElectricalExpressTamil thank you sir
@@s.j.suresh4274 this problem is due to shoddy workmanship. Fuse won't blow and MCB doesn't trip, because the leakage is sensed as load. Leakages are not shorts. Only RCCB's can sense this type of faults.
That's why new wiring should be meggered before energizing.
If you have doubt please post.
இண்டிகேட்டர் ஐ ஃபேஸ் ல்
வைத்தால் பச்சை லைட் ம்
சிவப்பு லைட் ம் எரிகிறது
ஏன்
SIR UPS VIDEO PODUGA
பாடியர்த் லா எனி ப்ரோலம் உயிர்க்கு
Im getting earth from veedu oodu bero 3pin plastic outside wire
Wanterfulk sir
Rccb bye pass endral enna sir
Pls reply
வீடு வயரிங் பன்னும் போது. நாம் எப்படி ரூபாய் கனக்பன்னி வாங்குறது. பைப் போடுறதுக்கு எவ்வளவு ,வயர் இளுக்குறதுக்கு எவ்வளவு என்று சொல்லவும்
9790091294 😎
Sar enka veedula suvitsh of pannu nalum karandu vaeuthu ethanala sar koncham sollunka. Sar
Phase neutral reverse
சப்மெர்சிபிள் மோட்டார் ஆன் செய்யும் போது மோட்டார் ஓடி தண்ணீர் வருகிறது ஆனால் மூண்று நிமிடம் கழித்து அந்த மோட்டார் பேனல் போடிலுள்ள mcb ஆனது டிரிப் ஆகி விடுகிறது
தினந்தோறும் இந்த பிரச்சனை வருகிறது
காரணம் என்ன ?
மோட்டார் ஒடும் போது அம்மீட்டரை பாருங்க MCB ratting பாருங்க
Under level எனில் Mcb higher ratting போடுங்க
Capacitor check செய்யவும்
Hello main off water tap shock
Load down appuram normal marubadium Down reason pls
👍👍👌👌🙏🙏
இந்த Short circuit and earth leakege
Multimeter use பன்னி பார்க்கலாமா? Ple explain tkq
Megger vaithu test seyya vendum.
Multimeter aal mudiyathu.
E v Raghavendra Rao
என்னோட Computer CPU வை தொட்டால் Shock அடிக்குது...CPU மேல் tester வைத்தால் light எரியுது ...நான் Switch Board ஐ கழட்டி பார்த்தேன்..உள்ள Earth pin கு connection இல்லை...அதனால் neutral ஐயும் Earth ஐயும் link பண்ணலாமா ?
அது தவறான செயல்
தணியாகவோ அல்லது வேறொரு சுவிட்ச் போர்டில் இருந்து எர்த் வயர் கொடுக்கவும்
@@ElectricalExpressTamil Ok Sir
@@ElectricalExpressTamil sir enga v2la eb bill athigama varuthu enna pandrathu sir
Sir oru taple fan sutthi patha suthuthu but switch on seithal humming sound kutkuthu en sir pls
Capacitor problem
Change new one 2.5 mfd
@@ElectricalExpressTamil thanks you sir
Tabel fan 1.5 mfd and Celing fan 2.5 mfd ... Capacitor change pannallaum humming sound vantha tabel fan ku Motor ode Shaft and bush change pannanum . Celing fan ku baring change pannanum nro
@@selvamranjiths8751 corect bro
1 HP motor earth lekeage
Bypass meaning enna nanpa
Goog
Stay wire i earth udan link pannalama?
கூடாது ஏனெனில் ஓருவேளை மின்கசிவு ஏற்பட்டால் அந்த ஸ்டே வயரை தொட நேர்ந்தால் மின் அதிர்ச்சிக்கு உள்ளாவீர்
கன்டிப்பாக எல்லா வீடுகளிலும் RCCB பயன்படுத்தவும்
Apdina enna
@@sankaranarayanan4762 உங்க உயிர் காப்பாற்றும் உபகரணம்😎
அண்ணா நான் கிராமஎலக்ட்ரீசியன் வேலைசெய்கிறேன் ஆனால் ஒன்னும்மட்டும் தெரியவில்லை தெளிவாவீடியோபோட்டால் உதவியா இருக்கும்.என்னவென்றால் டிரான்ஸ்பார்மலருந்து கிராமங்களுக்கு செல்லும் HT வயரில் அனைத்து மின்கம்பங்களுக்கும் தெருவிளக்கு இனைக்கபட்டிருக்கும் அந்தஅனைத்துதெருவிளக்கிற்கும் கிராமத்தில் ஒரு On/off சுவிட்ச் இருக்கும் அந்தசுவிட்சை அடிக்கடி இடத்திற்குஇடம் மாற்றுகிறார்கள் அப்படிமாற்றினால் சில தெருவிளக்குகள் வேலைசெய்யாதே அதைஎப்படிசெய்கிறார்கள் கூறுங்கள். மற்றும் டிரான்ஸ்பார்மலருந்து தெருவிளக்குக்கு தனியா பேஸ் எப்படிவருகிறது. இந்த சந்தேகம்மட்டும் ரொம்பநாளா இருக்கு எந்தChannelம் பதில்சொல்லவில்லை.நீங்களாவது சொல்வீர்களா நன்றிஅண்ணா
நீங்கள் நன்றாக கவனியுங்கள்
உங்களுக்கு புரியும்.
இது ஒரு சின்ன விசயம்.
ஒரு வேளை கவனித்தும் புரியவில்லை எனில் என்னுடைய இன்ஸ்டாகிராம் க்கு வாய்ஸா மெசேஜ் பண்ணுங்க.
இல்லை எனில் மீண்டும் இங்கேயே கமெண்ட் பண்ணுங்க நான் பதில் கொடுக்கிறேன்
@@ElectricalExpressTamil anna voicemsg yeppadi pannuvathu
எழுத்துபூர்வமாக அறிவித்தால் நல்லாருக்கும் அண்ணா நன்றி
உங்க எண் கொடுங்க நானே அழைக்கிறேன் சகோ
+965 50697102 இது என்னோட வாட்ஸ்சப் அண்ணா
3 please series lamp eappadi neutral illamal bulb earikiraththu sir
Potential difference the two conductor.
Either phase and neutral
Or phase to phase
Serious lamp la light Ku netural direct aha connect pannittu , phase serious aha check pannanum
Nan katpathu 3 phase series lamp neutral thavai padathu
Ethai videovaga potal nalla irukum sir demo
Current leakage in home so eb bill high
Check wiring with megger for leaks.
Employ experienced electrician.
Check 24 hours running appliances like fridge.
Check neutral and earth are not linked.
யேன் காக்கா குருவி ஷாக் அடிக்கமட்டேன் குது கரெண்ட் லினில்
Brother ungal watch app number anuppa mudiuma.
9543199321 What's up number
@@ElectricalExpressTamil Brother ungal watch up number connect aakuthilla. Ennudaiya numberai add panni our SMS anuppunka. +97477499838
Brother innum ungal watch app number anuppavillaye.
@@nowferahamedkhan5304 🙏 நண்பா நீங்க கொடுத்த மொபைல் எண் 11 உள்ளது சரியான நம்பர் ஐ 9790091294 க்கு அனுப்பவும்😊
@@sathyakumarr6738 Nanba ithu Qatar number intha number ai add panni parunka. 0097477499838
👍👍👍👍👍👍👍👍👍👍👍👍
உங்கள் பொன் நம்பர் அனுப்புங்கள் Bor
அண்ணா ஊங்க Whats app phone Number. தாங்க அண்ணா please
Super
Super