What Stall is in Centrifugal Compressor

Поделиться
HTML-код
  • Опубликовано: 21 май 2024
  • Understand what stall is in a centrifugal compressor. I expalin the process of what a stall does to an centrifugal impeller and what conditions to look out for.
    Chiller Training at chilleracademy.com
    Troubleshooting Guides at hvactime.shop
    TruTech Tools Promo: HVACTIME

Комментарии • 14

  • @HVACTIME
    @HVACTIME  Месяц назад

    Learning chillers can be tough, so I created an accessible training that can go on-site with you! Finish your chiller course understanding chiller systems and terminology at your pace to advance your career! chilleracademy.com

  • @keithto5990
    @keithto5990 Месяц назад +1

    Very happy and lucky to see this teaching.

  • @brandondb2618
    @brandondb2618 4 дня назад

    We run a York. It’s been in service for about 10 years, it has thousands of stall counts through its service . I’ve never really been able to get a good answer as to if these are design to protect from surge or an actual problem, we do run them at low load at times just because of the design of the facility it’s necessary. But we’ve never had any issues or failures of the machine.

  • @JohnChuprun
    @JohnChuprun Месяц назад +1

    A stall is usually a local event (not the full compressor), a full compressor stall is going to result in a surge - and this can be a cyclical event causing damage.

  • @espinozajc64
    @espinozajc64 Месяц назад

    Excellent

  • @Stevehevessy
    @Stevehevessy Месяц назад +1

    Could non condensables cause a stall ?

  • @matthewarndt7770
    @matthewarndt7770 Месяц назад

    Psid of DT? 60psid is a big difference in temperature when talking about in example of 123?

    • @HVACTIME
      @HVACTIME  Месяц назад

      Correct, i am speaking in context of high pressure systems.

  • @mallkomoha6823
    @mallkomoha6823 Месяц назад

    Thanks sir,
    Please can you clarify one point.
    Surge occurs when pressure ratio is higher than the maximum pressure ratio. Here is maximum pressure ratio a parameter set by engineer on software monitoring tool or is it something else? Thanks

    • @adamhorn8414
      @adamhorn8414 Месяц назад

      It's a parameter capped by motor hp and impeller compression ratio at full load on motor. When the pressure gets higher downstream of the compressor than your compressor can produce at max it will flow backwards.

  • @kevinmithnick9993
    @kevinmithnick9993 10 дней назад

    surge: Like the elephant in the room

  • @forcebewhithyou94
    @forcebewhithyou94 Месяц назад

    A video talking about technical,without number is empty prose, number, data, is tech.