AC Not Working Unusual issue

Поделиться
HTML-код
  • Опубликовано: 3 окт 2024

Комментарии • 103

  • @SuburbanDon
    @SuburbanDon Год назад +23

    The only thing that should be in an attic is insulation.

  • @j-randall2972
    @j-randall2972 Год назад +14

    I live in the southeast. When my house was being built the builder said the Air Handler would be in the attic. I told him to put it in the unfinished basement. The HVAC guys said thank you thank you thank you. Many years later when I had to have a new air handler, they thanked me for having it put in the basement.

  • @JackS425
    @JackS425 Год назад +13

    I like that Ted wears loafers to work. Really brings something to the whole laid back vibe of his videos

    • @5822huron
      @5822huron Год назад +1

      Why not! It's his company

  • @albertmcalister9066
    @albertmcalister9066 Год назад +45

    The Honeywell thermostat has a five minute time delay every time you power it up. 5 minutes seems like 5 hours when sitting in the attic waiting.

    • @AdamWBush
      @AdamWBush Год назад +2

      Step 387 reduce delay to 1 minute

    • @bryansimon4072
      @bryansimon4072 Год назад +3

      You can go into settings and reduce delay to zero. Directions have the settings for it.

    • @albertmcalister9066
      @albertmcalister9066 Год назад +3

      @@bryansimon4072 The 5 minute delay is to prevent short cycling the compressor. It is a nuisance while you are servicing a unit but serves a purpose. Taking the time delay out puts the compressor at risk.

    • @5822huron
      @5822huron Год назад

      ​@@bryansimon4072correct

    • @Hvacmania
      @Hvacmania Год назад +1

      I watch RUclips videos if nothing else to do
      I look for a 10 minute video 😄

  • @billderby1527
    @billderby1527 Год назад +8

    Notice most techs covered their butts by always recommending doing a PM. This way the customer can't call back with the 'you were just here' excuse when the weak cap blows.

  • @tedbell4416
    @tedbell4416 Год назад +4

    I watch a lot of these videos yours by far are the best. No goofy music intros just straight to the video. So much nicer. Hope you make more of them.

  • @bobgallo3775
    @bobgallo3775 Год назад +5

    I envy you Ted. The way you are able to sit cross legged in front of the unit. Even when I was working, I had to kneel because of sore knees(I did use kneepads). Good post, hopefully they have you do some p/m.

  • @bmcc12
    @bmcc12 Год назад +13

    An idle question:why the emergency call when no one lives there?

    • @alanm2842
      @alanm2842 Год назад +2

      maybe not emergency. if i was working in attic i would not go there in the heat of the day

    • @Uneedhelp91
      @Uneedhelp91 Год назад +1

      Who is ever doing the reno might have said something and the owners called.

  • @GFlCh
    @GFlCh 2 месяца назад +1

    Another great video. Thanks for sharing. Go home and get some sleep...
    Then watch at 19:44 --- 20:02, 21:41 --- 22:25
    And come back in the morning to remove the tape on the interlock. =)

  • @curtwuollet2912
    @curtwuollet2912 Год назад +7

    I've seen an old Honeywell round mercury tstat that was 50 years old still working

  • @stevedemarest276
    @stevedemarest276 Год назад +12

    As a Joe Customer, my favorite part of these videos is that moment when Ted hunts for a piece of loose duct tape for the door switch. 😆

    • @edlijewski5356
      @edlijewski5356 Год назад

      Did Ted remove that tape over the door switch...if so I missed it.

    • @williekeener9604
      @williekeener9604 Год назад

      Go back and there is a piece of tape on the unit near the position of the door switch. IJS

  • @Alboalt
    @Alboalt Год назад +7

    Happy that I live in the northeast and have a basement with a drain where I have my HVAC so techs don't have to hurt their knees and sweat profusely from an airhandler in the attic.

  • @slabslayer258
    @slabslayer258 8 месяцев назад +2

    I don’t a call in the attic this summer of new home owners that purchased a existing home . Checked the A/C out got it working checked float it worked properly. Called it good . 2 hours later
    A/C failed again . Came back and the dam float switch had went out . Must been intermittent failing first time I was there and couldn’t catch it .

  • @bruceshepherd6217
    @bruceshepherd6217 Год назад +1

    Well if she running you better go catch it

  • @shawnhuk
    @shawnhuk 12 дней назад

    That HR switch….. it had the hots marretted and twisted and had a wago on the neutrals, implying they switched the neutrals….. dear god….

  • @plainrock-ik3se
    @plainrock-ik3se Год назад +2

    Good video sir I like how laid back u are keep up the good work

  • @andred1951
    @andred1951 3 месяца назад +1

    The tail comes off the lizard and wiggles so that the attacking animal will go after the tail while the lizard has a chance to get away. The lizard will grow a new tail

  • @jayjudd6518
    @jayjudd6518 Год назад +2

    😂 quick and easy Way . Ho Lee Chit that was painful. Not easy ,easy ,easy Peezy. Like you said . Like following most of the time.😊😊😊

  • @jovangrbic97
    @jovangrbic97 Год назад +10

    You left the duct tape on the panel switch disabling it, wouldn't it be best to have left it working as it was when you arrived? Or is it just a nuisance and best jumped out?

  • @watermanone7567
    @watermanone7567 Год назад +1

    Nice fix, I don't remember ever seeing a bad float switch before, unless it was damaged or mis-used. Thanks

    • @caru3257
      @caru3257 Год назад +1

      I ha d one easy trap switch not work out of the box.

  • @joeshearer1247
    @joeshearer1247 Год назад +6

    I’m not a big fan of those float switches they don’t trip until water is really high in the pan so you better hope you put it where the low spot is

    • @realSamAndrew
      @realSamAndrew Год назад

      What's your favorite method then? Also Joe, maybe you can explain why he heard the condenser when he only jumped red to green?

  • @brandonprice2897
    @brandonprice2897 Год назад +3

    I never knew that a bad float switch could cause a unit to not run if there is no water in the pan. Thanks for the tutilage.

    • @joeburner7120
      @joeburner7120 Год назад

      Float switch breaks wires to low voltage. When switch is activated by lifting up by water, it opens cutting off wire. Apparently one of the connections went bad and interrupted low voltage. When they malfunction, they act as though there is water in pan

    • @realSamAndrew
      @realSamAndrew Год назад

      *tutelage 🤠

    • @jima3129
      @jima3129 Год назад +1

      My knowledge is mostly from the roofing business in which I installed roofs, and designed roofs as an RCI registered roof consultant. I learned very Early on that you have to give water a place to go. Now take this to the bank: putting a mechanical device in the way of the water in a drain pan that can fail is just plain stupid. If there was ever a place where the admonition
      " keep it simple, stupid" fit, this is it. Put in a minimum 1.5 inch line in the bottom of the drain pan and run it to grade with the least number of turns. My condensate line runs right to a catch pan that drains right through my poured concrete floor into the gravel below. I squirt a little soapy bleach into the line exiting my evaporator coil from time to time to kill black mold, because I know that mold likes to form on the inside of plastic pipes. Running a small 3/4 inch pipe through a hot attic to grade is simply asking for trouble. Just because it's always been done does not make it right. It does, of course represent a lot of service calls for the HVAC industry. Maybe thats why they still do it?

    • @caru3257
      @caru3257 Год назад +1

      I just got one out of the box and my brand new install wouldn’t work. I picked up a new one and everything started working.

  • @zackmax7184
    @zackmax7184 Год назад +2

    You might be a Leaka Momma if You have to stay in that Attic for very long.

  • @lexlarkin
    @lexlarkin Год назад +4

    You left the tape on the door panel switch!🤦🏼‍♂️

  • @billderby1527
    @billderby1527 Год назад +1

    Makes me recall the nightmares of being on call.

  • @sylkelster
    @sylkelster 2 месяца назад +1

    Make you up some alligator clip test leads for the meter to keep alongside the regular set. I find they come in handy at times, along with several sets of jumpers.

  • @robalexander7348
    @robalexander7348 Год назад +1

    Nice video Ted, try and keep cool over there, its a cold afternoon here 120 km south of Sydney, it's 14C now and it may even rain ☔ Au

  • @bryansimon4072
    @bryansimon4072 Год назад

    That’s a good one, don’t see float switches go bad often. Nice reminder for everyone. Thanks

    • @Austin23191
      @Austin23191 Год назад

      I had that reminder last year. The float switch would let 24v to the stat but only enough current to run the stat. As soon as it would call for ac, the stat would die. Replaced the stat and had the same problem cause I thought that was the issue. Ended up replacing the float and everything worked fine

  • @jonesjl99
    @jonesjl99 Год назад +1

    And leaves the tape on the door switch for the next tech…

  • @clivejoyce9437
    @clivejoyce9437 Год назад

    Hi Ted, brilliant job, keep it up, best regards from the UK.

  • @sknight0391
    @sknight0391 Год назад +4

    We all float down here. 🤡🎈
    😎👍

    • @Mrs.SusieDunn
      @Mrs.SusieDunn Год назад

      Classic 😂 shannon I wear my sunglasses at Knight

    • @sknight0391
      @sknight0391 Год назад

      @@Mrs.SusieDunn I'll try Susie, I try. 😎👍

  • @craigbraswell4269
    @craigbraswell4269 Год назад +2

    I dont know about you ted, but I personally don't care for those aqua guard float switches. I hate that the pan will have to fill nearly to the top before it trips. I've also seen many that wouldn't trip on a full pan of water, ruining a ceiling.

  • @rogerf3622
    @rogerf3622 Год назад +1

    Looks like you left the duct tape on the interlock switch when you replaced the cover.

  • @rtoweprojects
    @rtoweprojects Год назад

    Sometimes simple is overlooked as being something hard from my experience as a tech. Great job 👍 enjoy your videos 😊

  • @tommyweaver3540
    @tommyweaver3540 Год назад +2

    You forgot to take the tape of the switch, Doesn’t make a difference since you put the door back, but obviously you were tired

  • @pilotboba
    @pilotboba Год назад +3

    Why a late night call if they aren't even living there yet?

  • @zunar_j5_933
    @zunar_j5_933 Год назад +1

    Yay, new Ted video! Been too long. :)

  • @millenialmemoirs
    @millenialmemoirs Год назад

    Hey I recognize that truck! Fellow upstate service tech here checking in.

  • @yamaha4015
    @yamaha4015 Год назад +1

    Nice job, how ever, there is always a how ever, left the tape on de switch.

  • @MrAfdasdfa
    @MrAfdasdfa 2 месяца назад

    Your tips on electrical diagnosis and the process by which one covers basic things first then moves on are invaluable. Do you have any other channels you would recommend for apprentice HVAC techs trying to get the knowledge base of how all this clicks together?

  • @blakesmith2101
    @blakesmith2101 Год назад +12

    Exactly what you don't want to hear "I just moved here from California".

  • @gabrielstern4992
    @gabrielstern4992 Год назад

    Thanks Ted as usual you just seem to know how to fix things. Even if you don't like the brand.
    Maybe you can give us an update on your trane mini split.
    And ted maybe you can test out and do a Video on the new trane side discharge units.
    That are supposed to compete with the gree flex units with the conventional air handler but have side discharge units.
    Ohh and the Mr cool universals are rebadged gree flex units I took off the covers on the front and the compressor said gree on it.
    Began to figure that out 6 months ago after watching an install video for a gree flex.
    But verified this Saturday.
    So if you get one of those calls on those units you can order parts from gree.
    Since Mr cool seems to have terrible service.
    Anyway I wish trane would listen to you.
    They were a great brand along with Lennox and carrier and York back in the 1980s and 1990s, but sadly today the quality control is lacking with parts made too cheaply and that seems to happen with a lot of companies today.

    • @111000100101001
      @111000100101001 Год назад

      Sadly the Chinese companies are overtaking by making the suitcase condensers for all the American companies:(

  • @TheSimba86
    @TheSimba86 Год назад

    always a good idea to record stuff like this even if you're not going to post it on youtube. could save you from a lawsuit when they accuse you of something you didn't do

  • @AaronPowellvox
    @AaronPowellvox Год назад

    That is an odd ball thing to go bad.

  • @danwittels5542
    @danwittels5542 Год назад

    Good job Ted!

  • @dh5594
    @dh5594 Месяц назад

    You forgot to take the tape off the door switch

  • @Eddy63
    @Eddy63 Год назад

    Great vid as usual Ted ... Thx

  • @jjllooggiicc
    @jjllooggiicc Год назад +1

    It doesn’t look like you restored the door switch by removing the tape

  • @jamescarter7752
    @jamescarter7752 Год назад +7

    Let's hope they leave their politics in California. Enjoyed the video.

  • @dixiebrick
    @dixiebrick Год назад +1

    Soooooo what’s the combination to the lockbox?

  • @549BR
    @549BR Год назад +13

    More people fleeing crazy California; yep, they'll probably want a high tech thermostat. Like Ted's favorite brand, Nest. lol

    • @gabrielstern4992
      @gabrielstern4992 Год назад

      Don't like nest or ecobee at all.
      Honeywell makes a wifi thermostat for 170 dollars that is just smart enough like giving humidity readings and outside tempetures without bieng too over the top or complicated.
      Who knows maybe Alexa will make a bad comeback don't like them either.

    • @mattb1967mb
      @mattb1967mb Год назад +1

      Yeh... my high dollar Honeywell failed after 8 months.

  • @bills6946
    @bills6946 Год назад

    Those time delays can throw you.

  • @josephgrassa3085
    @josephgrassa3085 Год назад

    My units have “ wet switch” water detectors. They seem to be pretty reliable

  • @drohvac4583
    @drohvac4583 Год назад

    Why would they pay for Afterhours call if no one living there yet? Won’t it been fine to wait till the next day?

  • @Bill_CBR
    @Bill_CBR Год назад +1

    BTW, did you intend to leave the tape on the door switch?

  • @Dillonmechanical
    @Dillonmechanical Год назад

    Nice work

  • @carlossaenz4075
    @carlossaenz4075 4 месяца назад

    Sir , what camera are using great videos

  • @negan454ss
    @negan454ss Год назад

    Thanks Ted

  • @joeburner7120
    @joeburner7120 Год назад

    Just jump one wire lead from float switch to the other or tie them together. If unit gets power, there’s your problem.

  • @rocker8692
    @rocker8692 6 месяцев назад +1

    Hope he doesnt bring his woke California ideas with him.

  • @rogergregory6512
    @rogergregory6512 Год назад

    Can they wait until next April for their check up?😊😊😊

  • @Suncast45
    @Suncast45 Год назад

    I have a 2 year old Trane smart thermostat with wi fi. Never been connected to the net and I hate the thing! Can I have a normal like Honeywell thermostat installed on our Trane system?

    • @ctrlzyx2
      @ctrlzyx2 Год назад

      Probably. I don't know the trane product line, but unless the system uses a proprietary communicating protocol, any conventional thermostat will work. If your system supports multistage cooling or heating, or you have a heat pump, your new thermostat will need to support that. Most do. Sounds like you need an hvac contractor to do this for you, since you omitted some essential info from your question.

  • @kevinh6098
    @kevinh6098 Год назад

    are those steel toed slippers that you are wearing ?

  • @nomadismileseeker6611
    @nomadismileseeker6611 Год назад

    If it’s an aqua dog anything, drown it.

  • @97Napkins
    @97Napkins Год назад

    why are you there? nobody is there> do you just want fix machines when you can be at home relaxing? Now I suspect he dont want to be home lol

  • @pauldusa
    @pauldusa Год назад

    Yellow break

  • @10speed4
    @10speed4 Год назад +2

    I hope the Californian moving in doesn’t vote to ruin your city too.

  • @RichB0330
    @RichB0330 Год назад +5

    Tell her to leave her politics in Cali

  • @larrysmith9359
    @larrysmith9359 Год назад +1

    Is it a normally closed or normally open switch, Ted?

    • @realSamAndrew
      @realSamAndrew Год назад

      Normally closed

    • @rcf8367
      @rcf8367 Год назад +1

      I’m not Ted but FS is normally closed, so by definition it’s a supervised circuit.

    • @boeing757pilot
      @boeing757pilot Год назад

      Those float switches are normally closed (NC).

  • @nomusicrc
    @nomusicrc Год назад

    Last

  • @timcat5614
    @timcat5614 Год назад +1

    Why are you anti DIY. We can do better than any HVAc guy.

  • @walterrifle2725
    @walterrifle2725 Год назад

    The very worst neighbors you can have in your community are moving from California