If the combustion fan never turns on and the unit immediately goes into a two flash code you may have an open circuit in the gas valve or a loose wire on the gas valve. Check the wires connected to the gas valve for a secure connection.
@@Allpartsinc. Yes the 4 flashes code. I tested the sensors and they were all working. The flue gas blower starts, the gas valve opens, the flame ignites, and then the fan never kicks on. After a few minutes, the burners turned off from a high temperature alert, and then I get four flashes on the board.
@@st3v3stich Typically this happens from a bad control board not sending power to the blower fan, but the board needs to have the signal sent from the flame sensor telling the board that there is sustained flame and a call for the blower fan to come on. Most people in this case choose replace both the control board and the flame sensor.
My green light doesn’t light at all. The induction fan starts and the igniter goes on and I smell gas but it doesn’t start. What could it be when the green light doesn’t go on?
There's a chance you might need a new board, we can confirm that before you order if you give us a call (269-685-4123). The board we are using can be found here: www.allpartsinc.com/60105-ignition-control-board-for-mr-heater-heatstar-enerco.html ... but we will also want to make sure it is compatible
I have power to the furnace just as you showed, but nothing is happening. The operation light never turns on. Fuse is good and I replaced the transformer. Any ideas?
If you give us a call at 269-685-4123 we can go through some troubleshooting questions. The light should always work, so there is a chance you may need a new board.
I have the 2 lighht flash, and I thought you were going give possibilities of what might be wrong, and how to fix it! You didn't. What a waste of time.
Hi, thank you for watching, this is just an intro video to this subject. A two-flash code means that your system failed to detect a flame. This can be caused by a variety of issues, so we’d need to know more about your unit to help you. You can give us a call at 1-269-685-4123 and one of our technicians can walk through your problem with you, make sure that you are getting 120V to the unit. You can also text us at 269-447-0412
Could be a gas valve or the orfices maybe obstructed or a build up of carbon in the burner at the screens inside the burners. I blew mine out with the air compressor at 50 psi and we now have heat again for 2 days. You can call tech support at the manufacturer and get help as well. There number can be found in the operators manual! Hope this helps!
Thanks for watching! If you have any questions about the video or other heater issues, comment below!
This is a great video. Thanks for making!
Hey, I'm having trouble figure out my heater, my fan never turns on and code flashes twice... Any help would be greatly appreciated
Hello, if you call us at 269-685-4123, one of our technicians should be able to help you out!
Here for the same answer. l hope he responds
If the combustion fan never turns on and the unit immediately goes into a two flash code you may have an open circuit in the gas valve or a loose wire on the gas valve.
Check the wires connected to the gas valve for a secure connection.
What fault would prevent the heater blower from turning on?
Are you getting a flash code?
@@Allpartsinc. Yes the 4 flashes code. I tested the sensors and they were all working. The flue gas blower starts, the gas valve opens, the flame ignites, and then the fan never kicks on. After a few minutes, the burners turned off from a high temperature alert, and then I get four flashes on the board.
@@st3v3stich Typically this happens from a bad control board not sending power to the blower fan, but the board needs to have the signal sent from the flame sensor telling the board that there is sustained flame and a call for the blower fan to come on. Most people in this case choose replace both the control board and the flame sensor.
My green light doesn’t light at all. The induction fan starts and the igniter goes on and I smell gas but it doesn’t start. What could it be when the green light doesn’t go on?
There's a chance you might need a new board, we can confirm that before you order if you give us a call (269-685-4123). The board we are using can be found here: www.allpartsinc.com/60105-ignition-control-board-for-mr-heater-heatstar-enerco.html ... but we will also want to make sure it is compatible
I have power to the furnace just as you showed, but nothing is happening. The operation light never turns on. Fuse is good and I replaced the transformer. Any ideas?
If you give our tech service line a call (1-269-685-4123), we should be able to help you out!
Did you figure it out? My green light doesn’t go on either. What should I do to fix it?
If you give us a call at 269-685-4123 we can go through some troubleshooting questions. The light should always work, so there is a chance you may need a new board.
I have the 2 lighht flash, and I thought you were going give possibilities of what might be wrong, and how to fix it! You didn't. What a waste of time.
Hi, thank you for watching, this is just an intro video to this subject. A two-flash code means that your system failed to detect a flame. This can be caused by a variety of issues, so we’d need to know more about your unit to help you. You can give us a call at 1-269-685-4123 and one of our technicians can walk through your problem with you, make sure that you are getting 120V to the unit.
You can also text us at 269-447-0412
Exactly my thoughts. 2 flash code and showed absolutely nothing to fix but yet other codes where showed, pointless video.
Could be a gas valve or the orfices maybe obstructed or a build up of carbon in the burner at the screens inside the burners. I blew mine out with the air compressor at 50 psi and we now have heat again for 2 days. You can call tech support at the manufacturer and get help as well. There number can be found in the operators manual! Hope this helps!
@@tankertanker7199 I blew mine with a leaf blower and has worked since. Been working perfectly for 5 days.