gas boiler leaking water out relief valve

Поделиться
HTML-код
  • Опубликовано: 15 окт 2024
  • gas boiler leaking water out relief valve
    LAVIMONIERE PRODUCTIONS,LLC
    subscribe to my channel
    / @stevenlavimoniere
    facebook
    / steven.lavimoniere
    web site
    lavimoniereplum...

Комментарии • 77

  • @strunch
    @strunch 2 года назад +2

    Here is a man that takes pride in his work. There is no one in my area like this unfortunately. They all show up and try to sell me a new boiler instead of performing any maintenance. I'm grateful for these videos to help give me confidence to get this job done myself.

  • @pauljamilkowski3672
    @pauljamilkowski3672 Год назад +2

    A tip I learned from Mikey Pipes - Hook up an automatic air inflator to the schraeder valve on the tank with the boiler drain open (after draining the boiler) to blow out the water from inside the expansion tank out of the boiler drain to make it way easier to remove without the mess!

  • @AndrewRankinNC
    @AndrewRankinNC 7 лет назад +9

    About spit my beer out laughing when that old tank dropped off, it was like a little fountain. Nice work Steve.

  • @edwardalugo
    @edwardalugo 6 лет назад +1

    Is it normal to have an expansion tank installed opposite (screwed downwards)? My system came with the home when purchased about 2 years ago. I changed the circulator pump, the expansion valve since then. Prior to changing those parts my basement was flooded due to all the pressure. I did the repair myself through these videos. I did have had heat since but during the summer I must have not known how to prep for non use of system. Unsure if I am supposed to drain system when it in use and so forth. I just started the system today for the 1st time since last winter and I have my relief valve letting water out within 3 minutes. What do you suggest it can be? I know the tank is one part I have yet changed since I moved in 2yrs ago. Can it be full of water even if the previous installer placed it upside down unlike how I see them installed regularly. Thanks for your response in advance.

  • @timmo6113
    @timmo6113 6 лет назад +2

    hey steve i really enjoy your videos question
    hi, i've seen videos from expansion tank manufactures [ watts ] who say you have to match the tank pressure with the water pressure in the house. i've never seen a plumber do that infact i have ask many plumbers about it and they never heard of it. is this not necessary?

  • @hvacman77
    @hvacman77 7 лет назад +8

    I always take the schrader core out and drill a hole from the bottom. helps rid of the pressure

    • @markmaccione6757
      @markmaccione6757 7 лет назад +2

      hvacman77 That's exactly what I do as well. Steve likes to do things the old school way for sure. I would also stick a small Rubbermaid container under the tank if need be.

  • @bradford216
    @bradford216 7 лет назад +6

    Good job. I just don't understand why people finish a floor right near a boiler. They can let go at any time and the floor is then junk, especially this engineered flooring today.

  • @jamesshanks2614
    @jamesshanks2614 7 лет назад +2

    Thank you as I have to change out my expansion tank on my hot water heat system. I discovered 18 months ago when the nozzle plugged up ( I live in a trailer park ) that maintenance was using a 1.85 gallon per hour nozzle in a standard 7 gallon boiler oil fired. I asked to see the plugged nozzle while he went to the truck for a replacement. When he came back in I asked to look at the new one and said wrong nozzle. I asked if he was trying to get me to burn more oil? He said the bigger nozzle did a better job and used less fuel besides he said that is what the boiler calls for. Imagine his surprise when I showed him The manufacturers specifications sticker and pointed out it requires no larger than a 0.85 gallon per hour nozzle. He went back out and got the correct nozzle and installed it and my consumption has decreased by near 40%.
    Then he tells me that 1.85 GPH nozzle is the standard for the entire park! There are 330 units here. When I informed the owner he thanked me but said it didn't matter anymore as he had converted the entire park to propane guns. Yikes! Expensive way to fix a rising cost of fuel that was brought on by a couple of ill informed so called techs.
    I'm in derry, New Hampshire and the coldest it got was -7 for a week and my heating system kept me nice and warm burning one gallon less per hour.
    Ever run into that with your customers?
    Thanks for your informative and entertaining videos.
    Jim

  • @k20aa
    @k20aa 7 лет назад +5

    steve i dont mess around lifting them tanks any more just drill them and catch the water save your back

    • @nicholasdriver5120
      @nicholasdriver5120 2 года назад

      I save money on drill bits by shooting a hole in the tank.

  • @dannywilkins887
    @dannywilkins887 7 лет назад +14

    The tension unscrewing tank...like defusing a bomb lol

  • @katherinebruno616
    @katherinebruno616 3 года назад

    Water comes out my gas boiler sometimes...Is it the pressure relief valve on the gas boiler or the expansion tank??? I knocked on my tank and it seems hollow

  • @Chaser1971sss
    @Chaser1971sss 6 лет назад +1

    Steven Hello! Tell me what you use thread sealant? Mark? Thank you!

  • @angelocasio8972
    @angelocasio8972 2 года назад

    Hi I want too thank you for your video I wish you where from New York I will call you but thank god I learn from your RUclips thanks.

  • @chadschafer1723
    @chadschafer1723 4 года назад +4

    You cant realize how heavy they can be until you take a full one off

  • @stevemarkovic9326
    @stevemarkovic9326 7 лет назад +1

    steve!! I look forward to each video you put out! reminds me of working with my dad!!

  • @sydsyd
    @sydsyd 7 лет назад +1

    Great place for the sports memorabilia! What a tight place!

  • @mikelygren9229
    @mikelygren9229 7 лет назад +1

    Gonna be going to tech school for hvac, found your videos looking into the trade. I deliver food in Dartmouth and Westport. Small world haha.

  • @vincentherman468
    @vincentherman468 7 лет назад

    Baby dog is a mean lean window washin machine yall! And an ice cream truck security guard at that. Ever hear from that guy on the bridge that got a lil too close to the ice cream truck, lol?.....Great videos as always.

  • @joeb8114
    @joeb8114 Год назад

    I replaced my expansion tank relief valve and water feeder valve. My boiler pressure is still high. Any idea?

  • @veil67
    @veil67 7 лет назад

    steve , something as a tip that might help you when you anticipate a big water mess , try a funnel the same size as when changing the motor oil to capture more water dripping , of course if you have space to use it :)

  • @williamsizemore98
    @williamsizemore98 3 года назад

    What in the world are you driving man? That's a loud truck. Love the Dog though. Thanks for the info. I recently changed my circulator pump; but I'm wondering if theres another problem that caused the pump to go bad as the pump that went bad was only 3 yrs old.

  • @imaguglielmo
    @imaguglielmo 5 лет назад

    What is the stuff you put on the expansion tank before you plugged it back in? Thought you are supposed to use teflon tape. Thanks

    • @surgio98
      @surgio98 2 года назад

      Likely Teflon paste. Looks like blue devil brand (I think that's the brand)

  • @Fireship1
    @Fireship1 7 лет назад +1

    Great job Steve!

  • @acusticsix
    @acusticsix Год назад

    nice job....very cool doggie

  • @larry81
    @larry81 4 года назад +1

    you think you can do a video on how to drain the system?

  • @olivergodbout3827
    @olivergodbout3827 7 лет назад +1

    Great camera work Steve!

  • @RayRay-nb7tn
    @RayRay-nb7tn 5 лет назад +4

    The next expansion tank you replace can you cut it open so young techs can see whats inside? Thank you.

  • @benstanski
    @benstanski Год назад

    homeserve, COMPANY PLUMBING INSURANCE FROM GAS COMPANY NEW YORK ; was here and ball type valve has expansion tank that needs to be replaced ana aquastat. ball valve has notch on left and right and wobbles like nylon base is warped with red tv knob handle. both plumbers used it but refused to put new ; now leaking more after leaving;no nut to tighten unless is under red knob;i subscribe under another email for years;HAPPY NEW YEAR ;ALWAYS QUALITY WORK ; SUGGESTION ?DOES KNOB COME OFF

  • @katherinebruno616
    @katherinebruno616 3 года назад

    How did you know it was the expansion tank?? And not the pressure valve on this gas burner/boiler??

  • @gyver471
    @gyver471 7 лет назад

    At first glance it looks like the beginning of a horror movie. Great job though lol

  • @davidwark9971
    @davidwark9971 3 года назад +1

    We drill a hole in the bottom of the expansion tank, and use a Shop-Vac to suck out the water that's pressurized. Just another way of doing it ...

  • @fiberzip
    @fiberzip 5 лет назад

    what is the correct pressure that needs to be set inside that expansion tank...? is it the same as water pressure coming out garden hose ?

    • @surgio98
      @surgio98 2 года назад

      The tank has a guide. You are supposed to match the pressure from water pressure in the same house (yes garden hose) though I have left it at factory without any problems myself.
      Essentially there is a rubber diaphragm with a space for air underneath. As water pressure builds up in your boiler/hot water heater, the air gets compressed in the tank by the expanding water. As
      the water starts moving/cooling the air pushes the water back out of the same opening. It's a safe space where the water can expand without damaging your lines or setting off the relief valve.

  • @haroldlm64
    @haroldlm64 Год назад

    Nice..

  • @mjg263
    @mjg263 4 года назад +1

    Why not just push in or remove the Schraeder core then either loosen the tank enough to let air in or drill a small hole in it and drain some of the water out? Seems easier than wrestling with a full tank.

  • @johnzangari3432
    @johnzangari3432 Год назад

    Pay attention to the direction sheet the Amtrol ex30 has a 7 year warranty, save your invoice.

  • @erikj.2066
    @erikj.2066 7 лет назад +4

    Nek level!
    Hope you remembered to grab your wrench off the top of the water heater when you were done. Hate giving people free tools!

    • @brodieharley7040
      @brodieharley7040 3 года назад

      i know Im asking the wrong place but does anyone know of a trick to log back into an instagram account??
      I was dumb lost the account password. I would love any tricks you can offer me

    • @atlasreed281
      @atlasreed281 3 года назад

      @Brodie Harley instablaster ;)

    • @brodieharley7040
      @brodieharley7040 3 года назад

      @Atlas Reed thanks so much for your reply. I got to the site on google and I'm trying it out now.
      Looks like it's gonna take quite some time so I will get back to you later with my results.

    • @brodieharley7040
      @brodieharley7040 3 года назад

      @Atlas Reed It did the trick and I now got access to my account again. Im so happy:D
      Thanks so much you saved my account!

    • @atlasreed281
      @atlasreed281 3 года назад

      @Brodie Harley No problem =)

  • @georgesiatos9848
    @georgesiatos9848 7 лет назад

    great work

  • @gsh319
    @gsh319 2 года назад

    Dropping that expansion tank out,.. feel ya pain there. Doctors say, " should have been a plumber" ... Plumbers say "should have been a doctor"

  • @r.joseph8911
    @r.joseph8911 3 года назад

    Awww RIP Baby Dog 😩

  • @dracko2002000
    @dracko2002000 7 лет назад +1

    great job but those come recharged at most 35psi others 60psi and it's suppose to be charged to the psi of the incoming water to the house.

    • @alexgift4023
      @alexgift4023 7 лет назад

      throttle bottle, do most residential dwellings water pressure operate between 12 psi, cause it's usually set for inlet (system) water pressure? It's design is to not allow the expansion to go back, but buffer in the tank. Just curious :)

    • @alexgift4023
      @alexgift4023 7 лет назад

      Thanks for the clarity, throttle bottle.

  • @mikeyjohnson6610
    @mikeyjohnson6610 4 года назад

    Hey Steve what does this repair usually cost?

  • @juliocalvet9839
    @juliocalvet9839 7 лет назад

    steven great job

  • @mr.dahliaking.202
    @mr.dahliaking.202 6 лет назад

    can you put a valve before the relief valve, but to take the handle off so it would never be shut off, unless needed to change the valve without draining the whole system? Or is it strictly forbidden to put valves on relief valves and expansion vessels? I am only 19 yo. I am learning new stuff every day.

  • @kanepssantehnika268
    @kanepssantehnika268 7 лет назад

    why dont use special water tank tap.

  • @jasonmushersee
    @jasonmushersee 7 лет назад

    how about a umbrella for a catch can?

  • @joedugas9462
    @joedugas9462 7 лет назад +2

    I always drill a hole in the bottom of the expansion tank and drain it.....smashed my fingers too many times trying to hang onto a slippery full tank.

    • @Fireship1
      @Fireship1 7 лет назад

      Joe Dugas that's a great tip. I'm gonna use that next time I come across a water logged one.

    • @polishtheturdmickelson5473
      @polishtheturdmickelson5473 7 лет назад

      Nice tip Joe, especially when you have to room to catch it in a bucket.

    • @joedugas9462
      @joedugas9462 7 лет назад

      5 gallon bucket...thats where you smash the fingers...between the bucket and the tank...bloody knuckles and the rest of the day covered in glycol.

  • @picklerix6162
    @picklerix6162 5 лет назад

    Those expansion tanks don't seem to last very long in my opinion. Maybe five years at most?

  • @philipajarapoo7675
    @philipajarapoo7675 2 года назад

    That tank almost got away from you. She’s a leaker mama.

  • @randymathews3348
    @randymathews3348 7 лет назад +2

    just did a negleted triplex. new tanks, feeds and circ pumps. got the gas on, only to discover none of of tridicators are reading properly... fml 😢

  • @ptyptypty3
    @ptyptypty3 3 года назад

    okay, so is that Baby or Molly? :)

  • @robertcruz6974
    @robertcruz6974 2 года назад

    Looks to me like someone used iron gas pipe, in a water supply line to the expansion tank. Maybe I am wrong.

  • @stf2400
    @stf2400 7 лет назад +1

    I would hate to replace that water heater, it's so hard to get back there.

  • @jordanbryson1335
    @jordanbryson1335 5 лет назад

    One gallon of water weighs 8.3453 pounds. One cubic foot of water contains 7.48052 gallons. The weight of one cubic foot of water is 7.48052 gallons times 8.3453 pounds, which equals 62.42718356 pounds of water per cubic foot. Why not just drill a 3/8" hole in the bottom of the old tank once the pressure is off?

    • @surgio98
      @surgio98 2 года назад

      If it's empty then he just ruined a perfectly good tank.

  • @aircooledtx
    @aircooledtx 7 лет назад

    Quick one,Steve .. How the young chicks doing? Keep us up to date on progress.. .Got plenty of eggs to hide for kids.Y'all have a good Easter,from us in Texas.

  • @pelon542
    @pelon542 6 лет назад

    i know exactly how he felt when he was taking out that extrol tank,i hate replacing those things

  • @J-Colt
    @J-Colt 6 лет назад

    Need more crap in the way. Make it a challenge.