Why Your Boiler Pressure Relief Valve (PRV) is Leaking / Dripping - ConBraCo, Watts, Apollo - 30 psi

Поделиться
HTML-код
  • Опубликовано: 29 ноя 2024

Комментарии • 22

  • @tommycastro7357
    @tommycastro7357 18 дней назад +2

    This is by far the best video I have ever seen explaining everything. Thank you very much. I saw one drip hanging off. The pressure Relief valve. And I got worried. Just because I was testing my heating system over the weekend. So heating system has been off for at least 6 months

  • @melodicapex860
    @melodicapex860 Месяц назад +2

    This is a great video! I used to install boilers but never got into servicing them until i have my own. Just turned it on and the blowoff keeps popping and i got half a bucket of water on the floor already. I just replaced the fast fill/pressure reducing valve last year and tested everything else, all was fine. Those only went bad when you touched them but i havent yet. The temperature is fine, mine sits at 17 psi for three floors. I will test my expansion tank but the only thing left is the pressure reducing valve AGAIN or the seat of the blowoff not right. But the seat is still experiencing extra pressure and going off so the 'seat' doesnt seem to be the cause.

    • @realhouseDIY
      @realhouseDIY  Месяц назад +1

      @@melodicapex860 yes, possibly the expansion tank not doing it's job!

  • @LyleHughes-i6p
    @LyleHughes-i6p Месяц назад

    Thank You, great explanation in simple layman's terms, great job

  • @TrojanStarryNight
    @TrojanStarryNight 7 месяцев назад +1

    Great video and very detailed in discussing possible causes. Thanks

  • @nld-bl5ct
    @nld-bl5ct Месяц назад +1

    Excellent video, 100% useable!!

  • @matthewm3328
    @matthewm3328 Месяц назад +1

    This is gold

  • @michaelcorcoran1707
    @michaelcorcoran1707 6 месяцев назад +1

    a great easy to understand and helpful video, thanks

  • @jonathanneumark8411
    @jonathanneumark8411 Месяц назад +1

    Thank you. What a great simple explanation.

  • @cristianrivas7540
    @cristianrivas7540 6 дней назад

    So prv has a constant drip and psi is @ 15 it’s safe to say i have to change out the prv ?!

    • @realhouseDIY
      @realhouseDIY  6 дней назад

      If it's over 10 years old it's a good idea. It may just have some scale build up and manually opening the top a couple times may clear it and reseat the valve.

    • @cristianrivas7540
      @cristianrivas7540 5 дней назад

      It’s has to be ten maybe less but I opened and closed the valve several times it has a steady drip and psi is at 15 and goes up to 19 temp is 180

    • @cristianrivas7540
      @cristianrivas7540 5 дней назад

      I would like to send you a picture or video of my unit if that’s ok with you I don’t have the funds to spend on a repair man and if I can do it on my own I would definitely fix it without jeopardizing the safety of myself or anyone in my household .

    • @realhouseDIY
      @realhouseDIY  5 дней назад

      @@cristianrivas7540 if you want, you should be able to upload a RUclips video and post a link to it here in the comments. What is the prv's psi rating? And constant drip regardless of pressure? How much water collecting per day?

  • @yubemful
    @yubemful 16 дней назад

    The oil boiler PRV has a leak and the valve is rated at 30 psi but our boiler technician wants to install the one that has 125 psi. Is this correct?

    • @realhouseDIY
      @realhouseDIY  15 дней назад

      Oil boiler? I'm not sure but doesn't sound right. What psi does the gauge normally read?

    • @yubemful
      @yubemful 15 дней назад

      @realhouseDIY Right now it's at 50psi. I didn't check in the past.

    • @realhouseDIY
      @realhouseDIY  15 дней назад

      @@yubemful what psi is your pressure reducing valve listed for? And is there a label on the boiler stating max working pressure?

    • @yubemful
      @yubemful 15 дней назад

      @@realhouseDIY All I'm seeing on the label is the pump pressure: 150 psi. It's Weil-McLain QB-180 model. We moved in 2 years ago,

    • @realhouseDIY
      @realhouseDIY  15 дней назад

      @@yubemful that's the burner. I looked it up and the boilers that match to it. Certainly looks like the 30 psi prv for the hot water is the correct one.