Allen Bradley ControlLogix Redundancy System 1756 Part 5/5 - Program Download and Sync

Поделиться
HTML-код
  • Опубликовано: 8 фев 2025
  • If this video is helpful, please like, share and subscribe to my channel!
    Thank you.
    ControlLogix Redundancy System:
    2 PLC/CPU Racks:
    1756-L72 or 1756-L72K;
    (Same hardware, “K” is for additional conformal coating)
    1756-EN2T or 1756-EN2TK;
    1756-RM2 or 1756-RM2K;
    1 IO Rack:
    1756-EN2T or 1756-EN2TK;
    1756-IF16 or 1756-IF16K.
    Software:
    Studio5000 Logic Designer;
    Control Flash;
    Rslinx Classic.
    Allen Bradley ControlLogix Redundancy System 1756 Part 1/5 - Hardware Set Up
    • Allen Bradley ControlL...
    Allen Bradley ControlLogix Redundancy System 1756 Part 2/5 - Firmware Flash with Control Flash
    • Allen Bradley ControlL...
    Allen Bradley ControlLogix Redundancy System 1756 Part 3/5 - Config. on redundancy module 1756-RM2
    • Allen Bradley ControlL...
    Allen Bradley ControlLogix Redundancy System 1756 Part 4/5 - Programming Studio5000 Logic Designer
    • Allen Bradley ControlL...
    Allen Bradley ControlLogix Redundancy System 1756 Part 5/5 - Program Download and Sync
    • Allen Bradley ControlL...

Комментарии • 50

  • @AbdullahAhmed-vj2vi
    @AbdullahAhmed-vj2vi 3 года назад +3

    Thanks a lot. there is no video like that on RUclips. You are amazing
    We need lesson about how to create faceplate in factory talk view

  • @quoit99training83
    @quoit99training83 2 года назад +1

    Very good. Hope to see more videos from you like this one

    • @SYPHOANG
      @SYPHOANG  2 года назад

      @quoit99 training: Thank you for subscribing to my channel.

  • @fossilfire6511
    @fossilfire6511 3 года назад +1

    Thanks. This was helpful.

  • @julius64
    @julius64 2 года назад

    Seen several times.. Thank u.

    • @SYPHOANG
      @SYPHOANG  2 года назад

      @Julius: Is this video series helpful for what you’re looking for? Thank you for subscription and your support to my channel.

  • @banci1100
    @banci1100 10 месяцев назад

    thanks for this english spoken video

    • @SYPHOANG
      @SYPHOANG  10 месяцев назад

      @banci1100: It's my pleasure. Thank you for your support to my channel.

  • @danielesinwoke9851
    @danielesinwoke9851 Год назад

    This video is very helpful, thank you.
    Please kindly confirm this, don't we have to download the program to the secondary CPU?

    • @SYPHOANG
      @SYPHOANG  Год назад +2

      @Daniel Esinwoke: First, Thank you for your support to my channel. I confirm that we do NOT have to download the program to the "SYNC" PLC. I thought I mentioned the reason in the video. If not, the reason is it is to ensure 100% the exact program downloaded to "PRIM" PLC will be synchronized/downloaded to the "SYNC" PLC automatically once it is powered up. For redundancy system, you should not do anything to the "SYNC" CPU. All the program, setup, and configuration should be done on the "PRIM" CPU. For the "SYNC" PLC rack, the only we need to ensure is all its modules, including the CPU have the exact same firmware compared to what is on the "PRIM" PLC rack. Hopefully my response is clear, informative and answer all your concerns.

    • @danielesinwoke9851
      @danielesinwoke9851 Год назад

      @@SYPHOANG Excellent explanation; Thanks Bro

    • @SYPHOANG
      @SYPHOANG  Год назад +1

      @Daniel Esinwoke: Thank you for subscribing and your support to my channel.

    • @danielesinwoke9851
      @danielesinwoke9851 Год назад

      ​@@SYPHOANG Please, can you make a video on how to Pull data from SCAME F&G Panel to ControlLogix PLC via AnyBus HMS-EN2SE-R EtherNET IP / Modbus RTU Module?

    • @SYPHOANG
      @SYPHOANG  Год назад

      @@danielesinwoke9851: Unfortunately, I am not familiar with the ones you mentioned.

  • @Bentimmy5
    @Bentimmy5 4 месяца назад

    Do I need two fiber optic cables to connect between modules? Will one cable work?

    • @SYPHOANG
      @SYPHOANG  4 месяца назад

      @Bentimmy4: Yes, you do need 2 cables. It still works with one but you will no longer have the redundancy if that only cable fails.

  • @MenOfCulture8991
    @MenOfCulture8991 9 месяцев назад

    hello i know its been a while since you uploaded this video. You dont need to download the program to the secondary plc rack?? thank you

    • @SYPHOANG
      @SYPHOANG  9 месяцев назад

      @MenOfCulture8991: No, you should never and cannot download any program to the secondary PLC. The program in the primary PLC will be automatically synchronized or downloaded to the "SYNC" PLC (secondary PLC) once it is powered up to ensure no difference in programming between the 2 PLC's. That is why they are called "PRIM" and "SYNC" instead of "secondary". Thank you for your comments.

  • @HelloWorld-lt5oc
    @HelloWorld-lt5oc Год назад

    Hello, thanks for the videos. Did you download both projects to both racks (didnt look like it), because the second rack says “no project”. When you boot the second rack into secondary mode, does it automatically get the program from the primary system?
    Also, what happens if you disconnect the ethernet cable from the primary or secondary rack? is checked/maintained through a ping or so between the two racks while program syncing is done through the fiber? Thanks a lot

    • @SYPHOANG
      @SYPHOANG  Год назад +1

      @HelloWorld: Thank you for your support to my channel. If you watched this whole series of Redundancy Set up, you would have seen that I never downloaded the program to the second PLC rack. To download the program to the secondary PLC rack, it should be done automatically by the primary PLC rack, not manually from the PC. When both PLC racks have the program, loosing the Ethernet cable between possibly make both become primary. However, I never tried it before.

    • @HelloWorld-lt5oc
      @HelloWorld-lt5oc Год назад

      @@SYPHOANG great thanks a lot. I did watch all the videos and just made sure I didn’t miss it. Thanks for doing this, it’s very difficult to see redundancy done and Rockwell barely provides training for it. There are other videos on RUclips but no talking…which is not helpful

    • @SYPHOANG
      @SYPHOANG  Год назад

      @@HelloWorld-lt5oc Once again, thank you for your kind words and your support to my channel.

    • @carlosmascarenhas4905
      @carlosmascarenhas4905 7 месяцев назад

      @@SYPHOANG I downloaded to the 2nd PLC already, as I am new to Rockwell and used to doing this process on Yokogawa. Will it create any issues for me? Do I need to factory reset the 2nd controller?

  • @NSintegraciones
    @NSintegraciones 2 года назад

    Gracias por su aporte

    • @SYPHOANG
      @SYPHOANG  2 года назад

      @Alejandro Parra: Thank you for subscribing and your support to my channel.

  • @emg1233
    @emg1233 Год назад

    If you make an online change to the primary plc program will it automatically sync to the secondary plc or do you need to toggle power?

    • @SYPHOANG
      @SYPHOANG  Год назад

      @emg1233: It's best to turn off one PLC rack. Redundancy system might automatically sync only the data values, not the logic. Thank you for your comments.

  • @BrainyBytes_shorts
    @BrainyBytes_shorts 11 месяцев назад

    Hello. Please do you have videos on VFD powerflex ?

    • @SYPHOANG
      @SYPHOANG  11 месяцев назад

      @Nicofish2023: Unfortunately, I am not familiar with Powerflex.

  • @TechComRockwell
    @TechComRockwell Год назад

    In the same redundancy config, analog input card is blinking, showing FieldPowerOff set to bit, resulting fashing green, what should be solution?

    • @SYPHOANG
      @SYPHOANG  Год назад

      @Md Sallam Ansari: Unfortunately I have never experienced this. But I think it might be from the analog input module itself or the power issue on the IO rack. It’s either from the rack itself or the power supply of the IO rack. When your PC are online with the system, let’s check status/fault under properties of the module.

    • @TechComRockwell
      @TechComRockwell Год назад

      @@SYPHOANG Sir, indicating running ok status, No fault showing, also checking power supply to the module, found its ok

    • @SYPHOANG
      @SYPHOANG  Год назад

      @Md Sallam Ansari: Unfortunately I have never experienced this. How about the other modules? Are they operational as normal? If so, you should check the properties of the analog input module in the PLC program (such as revision).

  • @sujay_entertainmant_vlog
    @sujay_entertainmant_vlog 3 года назад

    How to receive data from ml1400 to micro820 through Modbus TCP?

    • @SYPHOANG
      @SYPHOANG  3 года назад

      @jitendra singh: Not sure what your question is. Below videos might be what you are looking for
      ML1400 Modbus TCP Client
      ruclips.net/video/Vsztd7BMmdA/видео.html
      micro820 Modbus TCP Server
      ruclips.net/video/Adoe6SVMFO8/видео.html

  • @bimalpadhan4970
    @bimalpadhan4970 2 года назад

    Redundancy module showing disqualify...what is the solution please..

    • @SYPHOANG
      @SYPHOANG  2 года назад

      @Bimal Padhan: Have you watched the other videos in this series?
      Allen Bradley ControlLogix Redundancy System 1756 Part 3/5 - Config. on redundancy module 1756-RM2
      ruclips.net/video/xqF7rsclrtI/видео.html
      Allen Bradley ControlLogix Redundancy System 1756 Part 4/5 - Programming Studio5000 Logic Designer
      ruclips.net/video/--d_CVbWxIo/видео.html

    • @bimalpadhan4970
      @bimalpadhan4970 2 года назад

      @SY P HOANG yes sir..but in a ring network rapid ring fault detected and disqualify sync. Module

    • @SYPHOANG
      @SYPHOANG  2 года назад

      @Bimal Padhan: I am not sure what you are experiencing but the secondary PLC rack always starts with disqualifying, then qualifying and sync. If you are online with both PLC racks, you can check the module status.

    • @bimalpadhan4970
      @bimalpadhan4970 2 года назад

      @SY P HOANG check module status shows physical module doesn't match module configured in project. What should be done..sir also show module identity mismatch..

    • @SYPHOANG
      @SYPHOANG  2 года назад

      @Bimal Padhan: You can change the modules in the PLC program to match with the actual modules you have on the PLC racks. However, all modules on the 2 PLC racks must be identical. Also the module firmware needs to be exactly matched between the 2 racks.

  • @BrainyBytes_shorts
    @BrainyBytes_shorts Год назад

    Teach me

    • @SYPHOANG
      @SYPHOANG  Год назад

      @Nicofish2023: How can I help you?

    • @BrainyBytes_shorts
      @BrainyBytes_shorts Год назад

      Teach me how to program ladder logic

    • @SYPHOANG
      @SYPHOANG  Год назад

      @Nicofish2023: You might want to check out the below channel. It has a lot of videos about ladder logic that you are looking for.
      youtube.com/@TimWilborne?si=RVu27v382dXNpJ7H