Actuator/Motorized Valve|Wiring|Connection|Working|1way&2Way|Manually Control BMS Control Eng Sub/CC
HTML-код
- Опубликовано: 21 апр 2020
- #actuator #motorizedvalve #valve
Subscribe Now ruclips.net/user/hbtv2020?sub...
Here are more Interesting video about HVAC System, Please have a look.
#Ducting for Bigger Area along with VAV & VCD, Adjusting Flow Rate L/s as per Area with Eng Sub/CC • #Ducting for Bigger Ar...
#VAV Controlling with Thermostat & BMS System along with Occupancy Sensor Wiring with DDC Eng Sub/CC • #VAV Controlling with ...
What's ETS Room? What are the Equipment's Inside & their Purpose? Chilled Water Pipe line Network. • #ETSRoom What are Equ...
Chilled Water #PressurizationUnit |Explanation about #PressureSwitch & #PressureVesselTank • Chilled Water #Pressur...
Plate #HeatExchanger in the #DistrictCoolingSystem Primary & Secondary Pipe line Purpose/Working All • Plate #HeatExchanger i...
Chilled Water Automatic & Manual Chemical Dosing System in the District Cooling System full Detail • Chilled Water Automati...
FAHU|Exhaust Air & Supply Air System|Heat Recovery Wheel|Filter Types|Cooling Coil| Air Blower| • FAHU | Fresh Air & Exh...
Air Handling Unit works |Different Types of Filters|Chilled Water System Along with Temp&Pressure| • Air Handling Unit work...
Chilled Water #PressurizationUnit |Explanation about #PressureSwitch & #PressureVesselTank • Chilled Water #Pressur...
HVAC Chilled Water Pumping System|Controlling of CHW Flow|Pipping#Strainer Motor Plate Info #ETSRoom • HVAC Chilled Water Pum...
Actuator/Motorized Valve|Wiring|Connection|Working|1way&2Way|Manually Control| BMS Control | • Actuator/Motorized Val...
How does Thermostat works, Connection, Addressing and Operation Full Detail • How does Thermostat wo...
BMS Control Panel which apply to FCU, How Devices are been wired & DDC Card Full Detail • BMS Control Panel whic...
Differential Pressure Transmitter/Air Velocity meter Working Principle, Installation & Wiring Detail • Differential Pressure ...
BTU Meter/Water flow meter/Temperature meter their units of measure/Installation/Connection all here • BTU Meter/Water flow m...
Explanation about Fan Coil Unit, FCU parts, Actuator and DRV Valve with English Substiles • Explanation about Fan ...
Thanks for Watching !
Please like & Share !
Please Support me by Subscribing my Channel
ruclips.net/user/hbtv2020
Dear sir
Surpass company K motorized valve ki video bnaen settings ki samj ni aa rahe
How to operate manual
Brother open close terminal me 24ac connection dhegatho chalega actuator
Pls explain eletrical connection
I will upload connection video very soon stay tune thanks for watching
In case fully open, close valve not opereted..when connection is ok...
What is problem..
How to check actuator condition...
How to check whether it is working or not. When I connect 24vac supply to it then then little bit humming sound coming.
you need to give 0 to 10 DC voltage as well then it will move only
From where 0 -10 v comes?
Where it will be convert?
from DDC Card analogue output this Actuator is being controling by BMS very soon upload that video aslo in which i will show you how this voltage comes
24V Ac or DC
Sir iski main power supply 24V AC h to kya isme transformer ka use Krna hoga and sir please conection k bare me repeat kro
Yah motorised valve 24 DC voltage operated Hai
0 to 10 DC voltage is ki position ko change karte hain
yah DDC panel ke sath connected hota hai jo isko voltage provide karta hai
Yes
What is bms
Building management System
I have ML7420A, when i connect 24VAC, motor starts rotating but actuator is not moving what's the reason
There is a coupling between mechanical valve and actuator valve, please check the coupling most of the time coupling get loose and actuator not able to link with two valve way or three way valve
@@HBTV2020 at this time I had not connected with valve, just monitoring only its liver. manually by hand rotation liver moves up/down, motor is continuously rotating jut by connecting 24VAC, but liver is not moving
@@HBTV2020 only 4 wires required for this model, 2 for supply (24VAC) and 2 for control (0-10VDC) 0V of both supplies will be common
@@AbdulHaseeb-pp2kb Actuator's Motor connects with Gear System Maybe Gear system has been damaged