Siemens sinamics V20 VFD local control, commissioning, parameter set up and Factory reset. (English)

Поделиться
HTML-код
  • Опубликовано: 2 окт 2024
  • Siemens sinamics V20 VFD drive local control, commissioning, parameter set up and Factory reset. Look in to haw to use control panel and do auto tune. All the manuals, parts and related videos, see below.
    Direct contact on Linked in: / ingus-sudints-1b2a2517a
    Website: igselectronics...
    Siemens drive: igselectronics...
    Siemens V20 VFD drive remote control, 2 wire control and 3 wire control, parameter set up: • Siemens sinamics V20 V...
    Run a 3 phase motor on single phase power, basics: • Run a 3 phase motor on...
    Single phase to 3 phase VFD drive home setup: • Single phase to 3 phas...
    Siemens V20 manual: cache.industry...

Комментарии • 53

  • @IGSElectronics
    @IGSElectronics  4 года назад +1

    Hello Fellow colleagues. If you enjoy the video please click that like button and if you did not, dislike it and let us know in comments, what was, that made you not happy with the content, so I can learn from it and make better videos for you in the future. Have a great day everyone.

  • @tknaved
    @tknaved Год назад +2

    I found this video when I was in stress, and after watching it, all my problems are solved....explained very well.

  • @JulienBaut
    @JulienBaut 3 года назад +6

    Thank You! Helped me a Lot! You could Talk a Bit slower and clearer. Thumbs up from Germany :-)

    • @IGSElectronics
      @IGSElectronics  3 года назад +1

      Hi Julien. Thank you for your kind comment. Glad it helped you out. Regarding speed of talking, it is something that i am working on.

  • @aman_khoja8820
    @aman_khoja8820 16 дней назад

    How to get digital output from V20 for run fb and trip fb

  • @Motoanexo
    @Motoanexo 2 года назад +1

    Thanks a lot mah dude I work as a electromechanical technician inside the paper craft industry and your explanation was so useful 🇲🇽

  • @naturelover721
    @naturelover721 2 года назад +1

    Sir please make a video ....how to remove F72 error alarm

  • @bashabasha04
    @bashabasha04 2 года назад +1

    hi friend , in my equipment it says that i have a VFD fault , and my 50hz decreases to 45hz , what could be the reason ?

    • @kevin00861
      @kevin00861 2 года назад

      Hi dear,
      Did you find the solution to the problem,
      Please share us Sir

  • @dennisrubio2375
    @dennisrubio2375 4 месяца назад

    Thank you Sr

  • @aliasgharnazari5650
    @aliasgharnazari5650 Год назад

    thank you for making this video, i was wondring if you can my question. is it possible to for this inverter to show the current AC motor i using?

  • @everythingexplained
    @everythingexplained 2 года назад

    Thanks, I was looking for how to "auto tune" the vfd.
    I've only worked with ABB drives previously, there it was several modes for tuning. And now I bought a V20 for a band saw project at home, but didn't understand that P1900 was the tuning function :)
    Was a bit disappointed when the motor made a bit much whine when accelerating, I guess that tuning the drive will silence it a bit.

  • @modernelectricelectronics4896
    @modernelectricelectronics4896 2 года назад

    hi my simens v20 vfd showing fault 3 , any possibility for reset

  • @ajayprajapati9533
    @ajayprajapati9533 3 года назад

    Sir I have Siemens v20 drive,
    In singl phasing problem my drive not trip it is runnin condition but my recruitment is in single phasing problem my drive trip so how parameter change

  • @abubakarsiddique7795
    @abubakarsiddique7795 2 года назад

    also i can't find P1110 option in CN001 mode....will u please help me out with this?

  • @mohammedalbaba828
    @mohammedalbaba828 2 года назад

    Hi there and thanks a lot for this beneficial video, I have a problem which is how to solve the error of A504?

  • @pquantum199
    @pquantum199 3 года назад +1

    hi mate thank you for the tutorials can you make one for setting up speed ref using USS and modbus protocol

    • @IGSElectronics
      @IGSElectronics  3 года назад

      Glad you like it, regarding USS and Modbus, I shall look in to that.

    • @pquantum199
      @pquantum199 3 года назад +1

      yes man thank you, im strugling to replace an obsulete Siemens micromaster 420 with V20 . Its controlled by S7-200 using USS protocol.

  • @user-hy6rp8ho6mmahamb
    @user-hy6rp8ho6mmahamb 2 года назад

    نرجو الترجمه لفظيا وليس كتابه 😢😢

  • @ManojKumar-oe6zl
    @ManojKumar-oe6zl Год назад

    How to reset 3 phase motor drive

  • @hendisupriadi9524
    @hendisupriadi9524 3 года назад

    Hy iam from indonesia (borneo) and iam a teknicial elekctrik in a small industri. And i want say thankyou so much for your education is simple with translate indonesia.

  • @saifiquadir739
    @saifiquadir739 3 года назад

    Hi this is from India and I am a biggner.. I have a same drive. I am using extranel start stop push button and for frequency using push button for up down Hz. Now i want to ask when I start vfd then it runs up to last running frequency. But I want when ever i stop and press start it should be running on 0 Hz. Means every time I want to adjust frequency from zero.. I hope u got it plz reply if possible...

    • @IGSElectronics
      @IGSElectronics  3 года назад +1

      Hi there, please watch the third video of this drive, it should help.

    • @saifiquadir739
      @saifiquadir739 3 года назад

      @@IGSElectronics yaa i visited ur channel.. All r very interesting and helpful videos...👌 👌 👌 👌
      And I watched 3rd video of simenc helpful but still problem not solved

  • @chelebelarkhala
    @chelebelarkhala 2 года назад

    Thank you

  • @adamasoumaoro5746
    @adamasoumaoro5746 2 года назад

    Explication en français

  • @abubakarsiddique7795
    @abubakarsiddique7795 2 года назад

    Hey....great video and great explanation....thanks a lot brother....but can you please explain or add how to run your motor in the reverse direction in CN001 mode???
    is it even possible?

    • @IGSElectronics
      @IGSElectronics  2 года назад

      Check the other videos for this drive I have maid.

    • @abubakarsiddique7795
      @abubakarsiddique7795 2 года назад

      @@IGSElectronics yes i checked..i saw....did not solved my problem

    • @everythingexplained
      @everythingexplained 2 года назад

      @@abubakarsiddique7795 Haven't tried it yet, but with "Cn001 - BOP as the only control source " I guess the only way to reverse the direction is by pressing both up and down arrows on the panel as described in the manual 5.1.1 Introduction to the built-in BOP.

  • @rishinathreghu579
    @rishinathreghu579 2 года назад

    hi can u tell by which method i can copy parameter from the drive.can i do it with pc ?

    • @IGSElectronics
      @IGSElectronics  2 года назад

      I might do video on that in the future, so far have not worked on that, so not sure how it is done yet.

    • @rishinathreghu579
      @rishinathreghu579 2 года назад

      @@IGSElectronics thank u for the replay, love ur videos

  • @gurrajkenya037
    @gurrajkenya037 3 года назад

    Can you set the output frequency to 100Hz? Or is 50Hz is the maximum?

    • @IGSElectronics
      @IGSElectronics  3 года назад

      Yes you can go up to 400hz. There is run frequency and base frequency. Base to always be to you country base frequency. Run can go up to 400Hz.

    • @primepyro6304
      @primepyro6304 2 года назад

      With Poti I only can go to 50 hz, how can I change that?

  • @user-xz2bt2px5p
    @user-xz2bt2px5p 2 года назад

    Good day! we buy Sinamics v20, 3 phases L1/L2/L3/PE. I think, we are stupid, because we even couldnt turn on it. We only connected cable 4 wires. As result, converter doesnt work, screen doesnt work too, only indicator LED blink by red. Is converter can be damaged or we are stupid? Thank you.

    • @IGSElectronics
      @IGSElectronics  2 года назад

      Hi There. Is your drive singe phase or 3 phase?

    • @user-xz2bt2px5p
      @user-xz2bt2px5p 2 года назад

      @@IGSElectronics 3 phase

    • @IGSElectronics
      @IGSElectronics  2 года назад

      @@user-xz2bt2px5p what did you connect to PE?

    • @user-xz2bt2px5p
      @user-xz2bt2px5p 2 года назад

      @@IGSElectronics TN-C system. PE=N

    • @IGSElectronics
      @IGSElectronics  2 года назад

      @@user-xz2bt2px5p PE is earth my friend, 3 phase drives don’t have neutral going to it. Just 3 phases and earth. Remove any wire from PE for now and start up the drive, if still red check all 3 phases to make sure you get from 380 to 415( depending were you are in the world) between phases using electric meter. Attach earth to PE once you confirmed all test.

  • @rabeaezzategypt561
    @rabeaezzategypt561 3 года назад

    i want to modify pid control in cn008

    • @IGSElectronics
      @IGSElectronics  3 года назад

      Hi There. I have never done PID control on this drive, so wont be much help to you on this matter.

  • @jasonjesmislang8929
    @jasonjesmislang8929 3 года назад

    Thanks a lot

  • @ricolauersdorf687
    @ricolauersdorf687 9 месяцев назад

    super confusing. i hate the device