Siemens sinamics V20 VFD drive remote control, 2 wire and 3 wire control, parameter set up (English)

Поделиться
HTML-код
  • Опубликовано: 5 июл 2024
  • Siemens V20 VFD drive remote control, 2 wire control and 3 wire control, parameter set up. We will be working with macro 2 and macro 6 set up, full wiring and live testing. For manual parts and related videos please see below.
    Direct contact on Linked in: / ingus-sudints-1b2a2517a
    Website: www.igselectronics.co.uk
    Siemens V20 drive:igselectronics.co.uk/products...
    Siemens potentiometer: igselectronics.co.uk/products...
    Siemens V20 VFD drive local control, commissioning, parameter set up and Factory reset: https: // • Siemens sinamics V20 V...
    Run a 3 phase motor on single phase power, basics: • Run a 3 phase motor on...
    Single phase to 3 phase VFD drive home setup: • Single phase to 3 phas...
    Siemens V20 manual: cache.industry.siemens.com/dl...

Комментарии • 25

  • @dennisrubio2375
    @dennisrubio2375 Месяц назад

    Awesome DVF🎉

  • @wadehearn6230
    @wadehearn6230 3 года назад +1

    Great information. I've been trying to get the 2 wire control to work on one of these drives for a half a day. Took care of my opportunity in less than a minute.

  • @jezreelmatias8661
    @jezreelmatias8661 3 года назад +1

    Muito obrigado, me deu uma grande ajuda👏👏👏👏👏👏👏👏

  • @IGSElectronics
    @IGSElectronics  3 года назад

    Hello Fellow colleagues. If you enjoy the video please click that like button and if you did not, dislike it and let us know in comments, what was, that made you not happy with the content, so I can learn from it and make better videos for you in the future. Have a great day everyone.

  • @demurch0
    @demurch0 2 года назад

    Typically you shouldn't put a contactor in the load side of an inverter, as you may damage it. These are usually used on the line side to disconnect power in case of Thermal Overload.

  • @naifalaywa3372
    @naifalaywa3372 3 года назад

    Hi . Thanks for the explanation it was really helpful.
    But please can u zoom on the wiring of the macro cn002 but it was not so clear

    • @IGSElectronics
      @IGSElectronics  3 года назад

      HI There. Can you tell me what part you were struggling to understand, so i can see if i can help.

  • @michaelgreenvalley9567
    @michaelgreenvalley9567 Год назад

    Hi mate i had a micro master junior 6se9112 my old drive used 12345 terminals and 13&14 on the junior ok terminal 1 o to 10v t2 ov t3 an+ t4 an- t5 di 1 then 13 &14 relay on mmj i was told I could use a sinamics v20 im having trouble to set it up any help would be great

  • @dextermazuka5022
    @dextermazuka5022 3 года назад

    Hi,
    I want de run a sinamics V20 with external contactor and potentiometer.
    Please I need to know which Macro to use and which parameters to sit up.
    Thank you

    • @IGSElectronics
      @IGSElectronics  3 года назад

      Hi Dexter, have you checked out the other 2 videos of this drive, were i work with macros.

  • @rentelisrentelis3340
    @rentelisrentelis3340 Год назад

    Подскажите,часто частотный преобразователь выдает ошибку f23
    Error f 23 .в мануал данной ошибки не могу найти . подскажите что делать?!

  • @abhishekchauhan9614
    @abhishekchauhan9614 2 года назад

    Hello.... I'm facing Little issue with auto run of vfd since i did some mistake in programming.....vfd is connected to plc via D1,D2,D3 input and D01 and D02 as output now in p700 what should i select please let me know the parameter setting of it to run the vfd in auto mode

  • @jamesowusu-ansah595
    @jamesowusu-ansah595 3 года назад

    If I get you right, if you want to change the macro group, for instance from Cn001 to Cn003, you would first have to reset the drive and then go through the commissioning process again, where you input the nameplate readings of the motor into the drive.. I'm i correct?

    • @IGSElectronics
      @IGSElectronics  3 года назад

      Hi There. Yes that is correct.

    • @jamesowusu-ansah595
      @jamesowusu-ansah595 3 года назад

      @@IGSElectronics thanks ....what does the MOP in the manual stands for?...i can't seem to find the meaning

    • @IGSElectronics
      @IGSElectronics  3 года назад

      @@jamesowusu-ansah595 it’s for using digital inputs for frequency control. Check out the third video.

  • @helymodelismo
    @helymodelismo Год назад

    Boa noite, alguém pode me ajudar, como tem o status ligado ou desligado no variado modelo V20 Siemens?

  • @saifullah4412
    @saifullah4412 2 года назад

    hello, If my AI setpoint is coming from a PLC (AO , 0-10V) and not from potentiometer, then how can I do my wiring of AI and do I have to change any parameter as well?

    • @IGSElectronics
      @IGSElectronics  2 года назад +1

      HI There, analog output will be outputting 0 and 10, just use the terminals that are designated for them inputs. 0 go to 0 and 10v to 10v. Analog card will be changing the voltage instead of potentiomater.

    • @saifullah4412
      @saifullah4412 2 года назад

      @@IGSElectronics Thanks

  • @mr.bright684
    @mr.bright684 3 года назад

    you can really faster then 50 hz with that inverter

    • @IGSElectronics
      @IGSElectronics  3 года назад

      Yes, up to 400Hz. Parameter name Max Frequency