How to take Backup of Siemens S7 1200 PLC ? Upload project from S7 1200 1500 PLC using TIA Portal

Поделиться
HTML-код
  • Опубликовано: 6 окт 2024
  • Siemens TIA PORTAL Complete Tutorial series for Beginners
    • Siemens TIA PORTAL Tut...
    Upload station to PG
    Upload project from S7 1200 1500 PLC using TIA Portal || Backup of Siemens S7 1200 PLC
    upload S7-1200 program
    s7 1200 backup
    Siemens s7 1200 programming tutorials

Комментарии • 71

  • @christianfehner405
    @christianfehner405 Месяц назад

    very clear, use- and helpful video, thank you so much for this excellent content.
    Greetings from Switzerland.

  • @michatomczyk7866
    @michatomczyk7866 3 года назад

    Thank you from Poland

  • @JasonMislang
    @JasonMislang Год назад

    Excellent video sir. thanks

  • @runbou3485
    @runbou3485 2 года назад

    អរគុណThank 👏

  • @plctrainings5400
    @plctrainings5400 2 года назад

    excellent explanation .Thankyou sir.

  • @moniruzzamanshohag
    @moniruzzamanshohag Год назад

    Great 👍

  • @Ganeshkambali
    @Ganeshkambali 11 месяцев назад

    Good video

  • @felixflores8134
    @felixflores8134 4 года назад

    Thank you

  • @rsinurat2144
    @rsinurat2144 4 года назад

    Great jos

  • @ENGRMDRAKIBULHASAN
    @ENGRMDRAKIBULHASAN Месяц назад

    I have CPU S7-1500 & ET200-SP 04 Nos, how can I take backup from PLC to PC. ?

  • @bahaagamal4995
    @bahaagamal4995 2 года назад

    Thank you ....How can i know the software version that the CPU is programed with? specially if the machine is working from 2 or 3 years and we dont have contact to the manufacturer.

  • @samirtaha4
    @samirtaha4 2 года назад

    hello ,, are you sure when you upload program from cpu ,, you found the tags identification symbols uploaded with the input output list ????

  • @besteebox5894
    @besteebox5894 4 года назад

    Sir very well, but here my one question, when we upload data on software then how save it in laptop and after save how to download another PLC...

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  4 года назад +2

      Just go to file .... save as .... that's it

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  4 года назад +1

      Connect new cpu and just click down project to cpu .... that's it

    • @besteebox5894
      @besteebox5894 4 года назад

      Thanks Sir

  • @gameeducation1343
    @gameeducation1343 3 года назад +1

    What is DIAG LED in analog module?
    What is meaning when it is on?
    And
    What is the meaning when it is blinking?
    And
    What is the meaning when it is off??

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад +1

      Diag means diagnostics LED .... THERE are many reasons to turn ON this led ..... most common is wrong hardware configuration..... but you must go online and open the PLC diagnostic buffer to check the diag error

  • @tharun2498
    @tharun2498 2 года назад

    How to know, in which version the program was created?

  • @sansudhar1
    @sansudhar1 3 года назад

    What is the use of Flash LED clicking during uploading of hardware and software blocks

    • @dontbesocool1991
      @dontbesocool1991 3 года назад

      To check whether your accessing the right CPU.

  • @UK211
    @UK211 4 года назад

    bro many thanks, when the machine works, can we take upload without problem or any stop ?

  • @parthaproteemroy9742
    @parthaproteemroy9742 3 года назад +1

    In one of our S7 1200 we didnot have the source file. We tried to access the project using TIA V13 where we could see the project blocks but the upload button was inactive. Then we tried to access using TIA V12, but doing so we didnot find any project in S7 1200. Could this be due to using lower TIA version?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      Yes ... contact your OEM and confirm which tiaportal version they have used to program , and also which modules like safety and drives they have used in TIA portal.
      If you want to take back up only you can use simatic automation tool also

    • @parthaproteemroy9742
      @parthaproteemroy9742 3 года назад

      @@EASYPLCTRAINING is there any chance the project getting erased due to accessing using lower version TIA portal?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      No chance

    • @parthaproteemroy9742
      @parthaproteemroy9742 3 года назад

      @@EASYPLCTRAINING if there is no memory card in the PLC we try to insert memory card is it possible the plc may get factory restored .

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      Normally it doesn't happens like this .... but if we insert a card in plc slot and power cycle it , it will take program from the memory card and run it .

  • @ahmeraslam9276
    @ahmeraslam9276 4 года назад

    Where I find CPU firmware number I read at CPU description there's showing only CPU 1214C

  • @assemelamirelmasri8739
    @assemelamirelmasri8739 2 года назад

    Hello guys
    I have old code for the programmer who programmed old machine the same type of the machine that I would like to upload the program from the PG to CPU which also consist of two inverter and HMI as well can anybody assist me how is the procedure will follow in steps for example at the beginning I have to connect the PG to the CPU with ethernet then I click the CPU inside the TIA Portal and click up load the program after can I download the HMI program from the same connection where all the nodes connected together with switch and the inverter is connected to the switch as well, because it is first time for me to download machine from scratch so I didn't know exactly how to proceed in such situation, and I don't know if I need to make some adjustment to the PLC CPU hardware or just when connect immediately will communicate with the computer or there's a different IP address already exist, sorry for my long comment but to be honest this is first time I do such stuff so I am worried if I will ruin the hardware of the machine the matter is a little bit sensetive and I wish that the probability of error will be as much as minimum .
    Please guys if someone could assist me in this matter will be highly appreciated thank you all.
    There is possibility to contact me directly in whatsapp in case you would like to assist me .
    Whatsapp: +218915492544

  • @youthtubeplanet8925
    @youthtubeplanet8925 3 года назад

    Where you took backup....?

  • @saddam2251
    @saddam2251 3 года назад

    How to find out sw version when we upload program

  • @mahersajidali9159
    @mahersajidali9159 4 года назад

    How to know the version of installed program in cpu, whether it is v11,v14 or C15?

  • @dontbesocool1991
    @dontbesocool1991 3 года назад

    Can you upload project even PLC in RUN mode? Thanks

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      Yes we can upload from plc , even in run mode

    • @dontbesocool1991
      @dontbesocool1991 3 года назад

      @@EASYPLCTRAINING i tried awhile ago. The upload is not clickable.

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      Because you are not using the same version of the tia portal, means the same version in which this project file was created .

  • @kalaia8602
    @kalaia8602 3 года назад

    What is the difference between tia portal v13 and v12

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      Nothing .... but just a new version.... with new features

    • @kalaia8602
      @kalaia8602 3 года назад

      @@EASYPLCTRAINING some more question for plc can u help me sir....

  • @gilbertdevera3339
    @gilbertdevera3339 2 года назад

    hi sir how to know if the Software used in siemens PLC is V14 or V16 just upload or Backup it to a Laptop?

  • @dnyaneshwarchavanke3186
    @dnyaneshwarchavanke3186 3 года назад

    Dear sir,
    When I start search when connect plc to laptop after completely search show error no device found use s7 1214 dcdcdc plc and ethernet connect
    How I can solve this problem

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      You set ip address of PC? And do you know the ip address of the plc ?

    • @dnyaneshwarchavanke3186
      @dnyaneshwarchavanke3186 3 года назад

      @@EASYPLCTRAINING yes myself set lp adress pc and I don't know ip address PLC

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      See first you should know the ip address of the PLC, atleast first three for example 192.168.1.? ...... only than you can be able to search the plc.
      Or more easily you try simatc proneta. With this software you don't need to set ip address on the PC just leave it blank. And it will search the network for you

  • @tayyubindustrialcontroleng8447
    @tayyubindustrialcontroleng8447 3 года назад

    How to backup of tia portal firmware 3.0 of s7-1200 plc

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      Less than 3.0 you can't take .... if this plc have memory card you can copy it .... using tia

    • @tayyubindustrialcontroleng8447
      @tayyubindustrialcontroleng8447 3 года назад

      @@EASYPLCTRAINING ok thanks,can you make how to download in memory card aslo in my laptop tia 2013 software firmware v4.0 but plc is s7-1200 cpu 1212c ac/dc/rly of 6ES7212-1BE31-0XB0 of firmware v3.0 so plz can you tell me how to uplaod program in pc

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад +1

      @@tayyubindustrialcontroleng8447 I will make a video , to copy project from the memory card , but it is little risky 😬

    • @tayyubindustrialcontroleng8447
      @tayyubindustrialcontroleng8447 3 года назад +1

      @@EASYPLCTRAININGtry it, thank a lot ...

  • @blbl8786
    @blbl8786 3 года назад

    Hello how can we upload from s7-1200 cpu that has firmware 1.0

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      Bro only chance is to upgrade the firmware to 3.0 .... once updated you can take backup

    • @blbl8786
      @blbl8786 3 года назад

      @@EASYPLCTRAINING okay but how they used to program it with that old firmware

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      Because they have project file with them .... they use TIA Portal project to edit the program ....

    • @rishinathreghu579
      @rishinathreghu579 2 года назад

      @@EASYPLCTRAINING if we update the firmware will it effect the programme?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  2 года назад

      It will not effect

  • @ahmeraslam9276
    @ahmeraslam9276 4 года назад

    How I find IP address? After that I make manual IP

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  4 года назад

      If you dont know ip address of plc .... it is very simple and easy to find out using proneta software from siemens

    • @ahmeraslam9276
      @ahmeraslam9276 4 года назад

      @@EASYPLCTRAINING normally we don't have IP address because manufacturers given us machine ready to work how I can use proneta

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  4 года назад +1

      @@ahmeraslam9276 I will make a video to find out ip addresses.

    • @ahmeraslam9276
      @ahmeraslam9276 4 года назад

      @@EASYPLCTRAINING I shall be grateful you

    • @mahersajidali9159
      @mahersajidali9159 4 года назад +1

      @@EASYPLCTRAINING I am waiting for the video.

  • @stalinsubbiah3238
    @stalinsubbiah3238 4 года назад

    Full Form of ET200S

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  4 года назад

      ET is an extension module.... it is used to expand the no. Of inputs and outputs in field .... simple words it is an extra card connected to PLC mostly by ethernet or profibus

    • @stalinsubbiah3238
      @stalinsubbiah3238 4 года назад

      Thank You for your Reply