I tried this, but - - 06 code keeps appearing at times and motor stops running. I was using 2 wire control, 4 wire, 0 to 10VDC sensor given. L1 as start signal. Any clue why? And how to resolve the issue?
--06 stands for NST is not a fault but means the drive is in an freewheel stop condition. Causes and fixes : 1. VFD has an input assigned to Freewheel stop? Check to see if that the input is active. 2. The drive is in 3 wire control (201 =3C). LI1 must be active before the NST will clear. 3. The VFD is in 2 wire control (201 = 2C) Verify if the drive was powered with the run command active, if so cycle the run command or set 202 to 01 (LEVEL) IO menu, 2 wire type = level 4. If the drive is being controlled by serial communication, the drive will display --06 until the Hex value of 6 has been written to the command word. 5. If the 4-20 mA signal loss is programmed to freewheel stop and the drive has loss the signal. Check the 4-20 mA signal. 6. If the drive is running from terminal control and the stop button on the keypad or remote display is pressed, the drive will go to --06. Power cycle the drive to clear the --06.
Yes Single phase 400V use Step Up Transformer 220V to 400V But Ye Applicable Nahi hai… aap Iska Use Sirf Testing ke liye Kar sakte hain …. Ya Aapko Single phase se Drive Ko Application par Use karna hai … to Aapko 2 Cheejo Ki Jaroorat padegi … 1- Step Up Transformer 220V To 400V 2- Jitna Ampere Require ho Usse 1.5 Guna ampere ka Rectifier lena hoga ….
Fir Rectifier ka Input 400V hoga Or DC Output VFD Ke Positive + Negative - Terminal Par connect karna ….. then aap VFD Ko Single Phase par use Kar sakte ho
Sir namaste
Agar forward aur reverse ek hi jagah ek hi time chalne ka videos banaye aur parameter seting bataye
Ek he jageh hai... Aap kya kehna cha rahe ho...
Thankuu sir ❤️
😁👍
Kaha par hai sir aapka workshop?
Ghaziabad and Jhansi
Very nice
😁👍
I tried this, but - - 06 code keeps appearing at times and motor stops running. I was using 2 wire control, 4 wire, 0 to 10VDC sensor given. L1 as start signal. Any clue why? And how to resolve the issue?
--06 stands for NST is not a fault but means the drive is in an freewheel stop condition.
Causes and fixes :
1. VFD has an input assigned to Freewheel stop? Check to see if that the input is active.
2. The drive is in 3 wire control (201 =3C). LI1 must be active before the NST will clear.
3. The VFD is in 2 wire control (201 = 2C) Verify if the drive was powered with the run command active, if so cycle the run command or set 202 to 01 (LEVEL) IO menu, 2 wire type = level
4. If the drive is being controlled by serial communication, the drive will display --06 until the Hex value of 6 has been written to the command word.
5. If the 4-20 mA signal loss is programmed to freewheel stop and the drive has loss the signal. Check the 4-20 mA signal.
6. If the drive is running from terminal control and the stop button on the keypad or remote display is pressed, the drive will go to --06. Power cycle the drive to clear the --06.
@@troubleshoottech3605 thanks
Tq tq
😁👍
Sir ek speed me chalana ho forwar reverse 3 wire set kse kre
Speed change mat karo... Or 3 wire setting le parameters dekho jaisa ki video mei bataya gaya hai
Hello sir altivar vfd me laga huaa cooling fan nahi cha raha hai kaya kare
ATV VFD ka model bataiye
Altivar 310 model
Sir hme roteting switch hia use ke use krna ho control remote krna hia kaha se setting combine kre to chalega
Kuch samajh nahi aa raha sahi se type karo...
Terminal not working. How to solve this???
Check my other video ... For local(Keypad) and Remote(Terminal) mode
Posible run power
sigle phase..?
Yes Single phase 400V
use Step Up Transformer 220V to 400V
But Ye Applicable Nahi hai… aap Iska Use Sirf Testing ke liye Kar sakte hain …. Ya Aapko Single phase se Drive Ko Application par Use karna hai … to Aapko 2 Cheejo Ki Jaroorat padegi …
1- Step Up Transformer 220V To 400V
2- Jitna Ampere Require ho Usse 1.5 Guna ampere ka Rectifier lena hoga ….
Fir Rectifier ka Input 400V hoga Or DC Output VFD Ke Positive + Negative - Terminal Par connect karna ….. then aap VFD Ko Single Phase par use Kar sakte ho
Hlo sir
Hello