  • I cover the full procedure on how to change IGBT on VSD in a York air cooled chiller. These components are also known as an inverter and VFD. This is a step by step guide for this repair. HVAC Training for HVAC Technician
    hvactimetx.com
    You can contact me at Hvactimetx@gmail.com
    Support the channel through,
    venmo.com/code...
    Zelle @ Hvactimetx@gmail.com

Комментарии • 56

  • @knowledgeunderstanding4192
    @knowledgeunderstanding4192 2 года назад +10

    All the screws on wires and IGBT have torque specs. Use them. Will cause high base temp lockouts in the future. And you must clean the bus lami ate structure with alcohol pads, until its clean.

    • @brianwolf9860
      @brianwolf9860 2 года назад +2

      If there is not a consistent spread/layer of heat compound it can cause high baseplate temp faults as well.

    • @knowledgeunderstanding4192
      @knowledgeunderstanding4192 2 года назад +2

      @Brian Wolf Yes, that is a 7,000 dollar board. And almost a 20k job depending on what part of the country you're in. Just need to use best practices

    • @REFEREEMOUSE
      @REFEREEMOUSE Год назад

      @@knowledgeunderstanding4192 are you referring to the plate under the board with the old paste?

    • @hvacwithlife5262
      @hvacwithlife5262 Год назад

      Agreed bro

    • @keshakio2079
      @keshakio2079 5 месяцев назад

      where can you find the torque specs?

  • @paradoxfox4431
    @paradoxfox4431 7 месяцев назад

    I appreciate you taking the time to show your apprentice and explain the process.
    You've also helped me when it came to writing my final. All the extra little tidbits of info really help make thinks click

  • @tinymanthebeast
    @tinymanthebeast 2 года назад +1

    These guys are blessed buy God working with this guy.

  • @patrickdwyer4874
    @patrickdwyer4874 2 года назад +1

    Thanks I have this repair coming up once parts come in. Thanks for sharing I know what to look forward to now.

  • @saadeddineghesmoune4684
    @saadeddineghesmoune4684 2 года назад

    Brother, thank you very much for the real great information. We will meet, God willing, in America,,, I am from Algeria🇩🇿🇩🇿🇩🇿💖🇺🇸🇺🇸🇺🇸

  • @listodemo
    @listodemo 2 года назад +1

    thanks for sharing your skills and knowledge much appreciated

  • @hvacinthecity9369
    @hvacinthecity9369 9 месяцев назад

    In most variable frequency setups it goes Ac voltage, rectifier(diodes), capacitor, igbt switches. And the controller handles the hz. It's definitely interesting to see the many applications of variable frequency.

  • @nandarairi9870
    @nandarairi9870 7 месяцев назад

    Wow nice

  • @emailfilters
    @emailfilters 2 года назад +4

    What was the fault or error that indicated an IGBT board changeout on this unit? Great detailed presentation of changing the board.

    • @HVACTIME
      @HVACTIME  2 года назад +2

      Gate fault

    • @REFEREEMOUSE
      @REFEREEMOUSE Год назад +1

      @@HVACTIME what troubleshooting did you take to find this? Gates lead you to the VSD but what actual check? Output voltage, something physical or just the growling sound? I am guessing the capacitors were good, the snubber is good and the only thing left was the board?

    • @user-wx5ml7cc2r
      @user-wx5ml7cc2r Год назад +1

      I'm also changed igbt in York chiller when chiller show alarm vsd c plate high temperature.. and problem found base plate C not show temperature then I'm changed new igbt now chiller properly running

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 2 года назад +1

    Thanks again for the videos!!!
    🥃🥃🍺🍺🍺👍🏻

  • @user-nh6xr5cw1w
    @user-nh6xr5cw1w Год назад

    Good thanks for knowledge

  • @HVACChillin
    @HVACChillin 2 года назад

    Nice uniforms my office uses the same ones

  • @LWPANTEX
    @LWPANTEX 7 месяцев назад

    What are causes for the IGBT to fail? We have had one supposedly fail but cannot get a definite answer as to the cause of its failure. The unit is 6 years old and a YVAA power pole assembly is not cheap to replace without an answer. Thanks for the great knowledge you provide!

  • @thesilentonevictor
    @thesilentonevictor 2 года назад

    Great job tech

  • @_mo_5169
    @_mo_5169 Год назад

    Thank alot for this video

  • @argimoussa2270
    @argimoussa2270 2 года назад +1

    Hi. My system fuse 20FU still keep blowing. could it comes from relay board failure or..?

  • @tobydavis1148
    @tobydavis1148 10 месяцев назад

    I have a ycav 150 ton with VSD communication loss. They have replaced the VSD board I checked trigger board per spec. So we had an extra micropanel board just need eprom & sd card programmed from JCI. On the right track?

  • @justinneumann1492
    @justinneumann1492 2 года назад +1

    Great video. I’ve got an issue on one of these where the overload setting on circuit two keeps changing to 175A from 225A and trips the chiller out on overload. OL potentiometers are glued and have not been changed. I’m guessing a new a main board?

  • @ArshadAli-wf1nq
    @ArshadAli-wf1nq 2 года назад

    Very.NICE

  • @boediman360
    @boediman360 10 месяцев назад

    Like this

  • @brianwolf9860
    @brianwolf9860 2 года назад +2

    Typically resistors are bled within 5 mins. Always worth a meter check but no need to wait 10-15 mins

    • @HVACTIME
      @HVACTIME  2 года назад +4

      Ive had them take 15 minutes to fully discharge. If im not mistaken the factory spec's call for 20 minute discharge cycle. Id rather my techs play safe on it.

    • @FrenchBeefCDN
      @FrenchBeefCDN 2 года назад +2

      FWIW If one of the bleed resistors has failed, there is no safe time to wait. ALWAYS check DC and AC in multiple points on any piece of equipment before sticking hands in. Anyone with a license has been told this countless times.

    • @alekmartinez576
      @alekmartinez576 Год назад

      @@HVACTIME absolutely!

  • @otmaneelati4400
    @otmaneelati4400 Год назад

    Peace be upon you, my friend, how are you? I want a solution if you have an idea for this problem YORK brand chiller displayed barrier control lock problem

  • @sumonhossain4209
    @sumonhossain4209 Год назад

    Same chiller alarm is "high dc bus voltage" why this alarm & how to repair this alarm ..plz help me, I am from Bangladesh. Thanks

  • @mahadevan5370
    @mahadevan5370 10 месяцев назад

    Sir,I have one doubt York air cooler chiller capacitor busted vendor changing new capacitor replaced but again capacitor busted,what reason sir capacitor busted?

  • @jonnymac31
    @jonnymac31 2 года назад

    Hell yeah man

  • @Practicing_HVACR
    @Practicing_HVACR 2 года назад

    Thank you for the video. What’s up with the board to the left? What’s that called? Noticed some snubbers on that one too.

    • @HVACTIME
      @HVACTIME  2 года назад +2

      That is another circuit IGBT. There are a total of 3 IGBT (1 per compressor) on this drive kit. They share the same capacitor bank and SCR's.

  • @nighty2936
    @nighty2936 2 года назад +2

    Kinda curious about the reason you change it ?

    • @HVACTIME
      @HVACTIME  2 года назад +3

      It was creating harmonics in the compressor which makes a loud growl sound. When the gates get weak they can start doing that.

    • @nighty2936
      @nighty2936 2 года назад +1

      @@HVACTIME interesting, does it happen often ? Thanks for the reply ^^

  • @dazzykhan786
    @dazzykhan786 Год назад

    What is the reason vsd burn out?

  • @severinogarcia5753
    @severinogarcia5753 Год назад

    Sir i have paste from YORK name is HEAT TRANSFER PASTE. And THERMAL PASTE is same...Because brand is defferent

  • @vinithkumar9209
    @vinithkumar9209 Год назад

    How troubleshoot high flash tank level in York chiller

    • @ahoernke21
      @ahoernke21 10 месяцев назад

      First thing you need to do is check the sight glass on the flash tank and check the liquid level. It should be around the middle of the site glass. Ifyou can’t see the level it os either below or above the sight glass. If you point a laser into the sight glass you will see the laser streak goong through the liquid, if it is low you will only see a dot. If you confirm the level is high you will need to manually crack open the flash tank drain valve on the controller allow the liquid to drain to midpoint of the sight glass and recalibrate the level sensor.

  • @KashifKhan-jg6gs
    @KashifKhan-jg6gs 2 года назад

    Sir please tell me York screw chiller fault low discharge suprheat alarm please tell me solution

  • @shravanhvac8301
    @shravanhvac8301 2 года назад

    hi sir tel me one think trane chiller RTA210 alaram lachad fulat tell me solustion plz

    • @HVACTIME
      @HVACTIME  2 года назад +2

      Thats not an alarm, need to keep scrolling to see actual alarm.

  • @rajugundas9288
    @rajugundas9288 Год назад

    How much new IGBT bord

  • @hvacwithlife5262
    @hvacwithlife5262 Год назад

    TRANE guys are doing YORK 🤔

  • @MohammadAli-zx6bs
    @MohammadAli-zx6bs 2 года назад

    Hi How Are you sir