  • Опубликовано: 13 авг 2024
  • UPDATE: I made a mistake on my YVAA rundown. There is not a drain valve after the flash tank. It uses the "condenser drain valve" aka the feed valve only.
    In this hvac training I explain the refrigeration cycle of a York chiller. YCIV & YVAA are great hvac system for any building air conditioner. This hvac training videos goal is to help hvac technician better understanding these AC systems.
    Check out Merch Store! my-store-b413f...
    You can contact me at Hvactimetx@gmail.com
    You can also follow me at,
    Instagram
    / hvactime
    Facebook
    / hvactime
    Support the channel through,
    venmo.com/code...
    Zelle @ Hvactimetx@gmail.com
    #refrigerationcycle #chiller #hvactrainingvideos #york #ac #hvac #hvactechnician
    00:00 Intro
    00:24 Visual Explanation
    05:56 Main Panel Readings Explanation
    09:38 YCIV Drawing Explanation
    20:38 Evaporator Design Changes
    22:38 YVAA Drawing Explanation
    28:44 Closing & Tech Support

Комментарии • 78

  • @Noypihvac
    @Noypihvac 3 года назад +7

    Eductor part is wrong mate.. illustration should be 1 from liquid goes to eductor, 1 line from buttom of the barrel or evaporator and 1 line back to suction line.. this kind of oil management is almost the same of rtac unit. Oil from buttom barrel then back to compressor

    • @HVACTIME
      @HVACTIME  3 года назад +9

      Thank you, after I finished it and released it I realized I made a mistake on that part. What I will have to do is make a separate correction video doing a better job on that.

    • @Noypihvac
      @Noypihvac 3 года назад +1

      @@HVACTIME yvaa has some changes depends on coil either copper coil or micro channel. Copper condenser coil the drain valve control by liquid level sensor at evaporator whereas with micro channel coil they dont have liquid level sensor at evaporator. I have few yvaa unit that i maintain here in the island

    • @HVACTIME
      @HVACTIME  3 года назад +1

      All of mine have micro channel.

    • @brianwolf9860
      @brianwolf9860 2 года назад

      Economizer opens based on comp frequency. Our YVAA now does not have check valves in the econ pipe, because our newer software allows for Economizer backflow control.

    • @Noypihvac
      @Noypihvac 2 года назад

      @FILIPINO WONDER'S yvaa sir?

  • @HVACTIME
    @HVACTIME  3 года назад +6

    I made a mistake on my YVAA rundown. There is not a drain valve after the flash tank. It uses the "condenser drain valve" aka the feed valve only.

    • @Drak7282
      @Drak7282 2 месяца назад

      I was going crazy looking for that thing lol. Glad I came to comments

    • @HVACTIME
      @HVACTIME  2 месяца назад

      Lol my bad

  • @rudrapratapsingh367
    @rudrapratapsingh367 2 года назад +3

    after watching this video, my basic dx chiller cycle clear , thanks a lot HVAC time

  • @lauderdalechad
    @lauderdalechad Год назад

    Ran into a yciv today for the first time. I'm used to working on rack refrigeration, needless to say I was all kinds of turned around. This video made it all so clear to me now. I'll be working on it again later this week... Atleast I'm armed with some knowledge now. Thanks a ton! 🍻

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 2 года назад +1

    I hope to one day understand and be proficient at troubleshooting equipment like this. This type of equipment is what i get up and get going for. I love this trade

  • @EA91HVAC
    @EA91HVAC 3 года назад +2

    You posted this at a perfect time for me ! I just finished going over a few yvaa’s with my journeyman this past couple days. Love the videos keep it up!

  • @wata_laf
    @wata_laf Год назад +1

    Love the video! Everything was perfectly explained but I would like to add, there is not a “DRAIN VALVE” on the flash tank leaving line to evap. Now there is a shut off but not an eev device.

  • @onemischiefmaker7032
    @onemischiefmaker7032 8 дней назад

    I love your videos. Great info!!

  • @perryjeff77
    @perryjeff77 3 года назад

    Bro thank you so much man. I just got a job as a facilities engineer and this stuff is hard for me to fully grasp. Thank you for breaking this down.

  • @smptbachu155
    @smptbachu155 2 года назад +2

    need a separate video on edector system

  • @mischieftommy1252
    @mischieftommy1252 2 года назад +1

    Thank you very sir, really fantastic explanation, could you please provide more theatrical explanation , how FD working and collect oil from the cycle.

  • @stlbrian33
    @stlbrian33 3 года назад

    Thank you for these videos. HVAC Gold.

  • @mahendrachoudhari9598
    @mahendrachoudhari9598 Год назад

    my best dear techar for my life great vidio for me.

  • @fathmasameer7523
    @fathmasameer7523 3 года назад

    Great video the chiller I have seen Model YVAA fix orifice instead drain valve (EEX)

    • @HVACTIME
      @HVACTIME  3 года назад +1

      You know I'm glad you said something, I made a mistake on my YVAA rundown. There is not a drain valve after the flash tank. It uses the "condenser drain valve" aka the feed valve only. I will need to make that correction some how.

  • @michaelhadera3024
    @michaelhadera3024 10 месяцев назад

    Amazing video man

  • @nathandaubis819
    @nathandaubis819 2 года назад

    after watching all the chiller videos on you tube, you have found where the BEAR SHIT IN THE WOODS...thank you. great VIDEO.

  • @michaelgonzalez1824
    @michaelgonzalez1824 2 года назад

    Great Video!

  • @michaelh3142
    @michaelh3142 3 года назад

    It would be awesome to see a video on a daikin screw. In particular how the capacity slides valves work in detail.

    • @donwilkes536
      @donwilkes536 3 года назад

      it may be superheat which controls the slide valve which is typically what loads a screw compressor

  • @chiller-on
    @chiller-on 2 месяца назад

    hi. do you have a video on the channel on how to properly replace the oil on the York YVAA chiller?

  • @Mybusiness1978
    @Mybusiness1978 2 года назад

    Thanks for really informative video.

  • @ramitbajrawar
    @ramitbajrawar 3 года назад

    Very useful information

  • @simohvac9222
    @simohvac9222 3 года назад

    great explanation

  • @ahmedalameendiy
    @ahmedalameendiy 2 года назад +1

    Awesome vedio :) i think the stupid thing in this system it dont have feed back in valve position

  • @hvacr3519
    @hvacr3519 3 года назад

    very useful information, thank you very much.

  • @shahidawaisee
    @shahidawaisee 2 года назад +2

    Pls. Look into enhancing the video lighting. Thanks

  • @anwarahmadkhan4469
    @anwarahmadkhan4469 Год назад

    How to remove suction line from the barrack or cooler can u explained me pls

  • @salehhamid
    @salehhamid 3 года назад

    Most helpfull ,,, Thanks very muck

  • @yup735
    @yup735 3 года назад

    good job

  • @mikefrantz8398
    @mikefrantz8398 2 года назад

    Good stuff

  • @bobparrott8130
    @bobparrott8130 3 года назад

    Great info thank you 👍

  • @khushimohammad5357
    @khushimohammad5357 9 месяцев назад

    How to change York chiller reciprocating oil heater old compressor

  • @rdheatingandair6973
    @rdheatingandair6973 Год назад

    Can you change the EXV motor on these chillers without removing the Freon

  • @HH-oi8hn
    @HH-oi8hn Год назад

    Hi please there is leaked in evaporater. How can I repair it only in Cerkit 1 thanks

  • @sreejithks625
    @sreejithks625 2 года назад

    Nice video brother...My VSD assembly in YVAA got burned. What could be the reason

  • @ziaarnie3694
    @ziaarnie3694 3 года назад +1

    Amazing video brother, kindly explain same to Trained cvhe or cvhf water cooled chiller . Thanks

  • @axltv3873
    @axltv3873 Год назад

    I have same unit YCIV micro channel cond coil.im facing problem in drain valve not giving the exact position when I put manually put it to 100% open and 0% closed,when it run it having alarm low suction limiting and unusual sound of the compressor.i suspect the stipper motor module so I tried to swap from other unit but still problem occur.unit shutdown low suction pressure. Any advice

    • @HVACTIME
      @HVACTIME  Год назад

      Extremely common for the exv gears to where out and stick causing it to get out of calibration. Recommend replacing exv.

  • @aircooledchilleralltypes4938
    @aircooledchilleralltypes4938 3 года назад

    Sir chiller displays show vsd communication failure fault what is the problem

  • @shoaibmallabadkar3947
    @shoaibmallabadkar3947 Год назад

    Sir how to change oil in YVAA fladed chiller

  • @Tamilsongs2813
    @Tamilsongs2813 Год назад

    Pls how do oil charges this chiller pls make explain sir

  • @bryangillis2515
    @bryangillis2515 2 года назад

    Can you explain exactly what the economizer valve does? Is it cooling the compressor or reducing compression ratio?

    • @HVACTIME
      @HVACTIME  2 года назад +1

      Its pulling flash gas to reduce pressure on the flash tank.

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC 2 года назад

      That was what i was thinking as well

  • @fredrosas2575
    @fredrosas2575 3 года назад

    Hey, great video thanks for taking the time to do them.
    Question. if I'm understanding right the drain valve is the metering device?

    • @HVACTIME
      @HVACTIME  3 года назад

      At its core yes, It is the final flash point that is controlling evap superheat. But the feed valve also plays a critical role in that as well.

    • @fredrosas2575
      @fredrosas2575 3 года назад

      @@HVACTIME I understand now. Thanks for the quick response!

  • @jaymz0074
    @jaymz0074 2 года назад

    Wouldnt happen to have a York YCUL080 air cooled service manual you could email could you?

  • @allanfernando5358
    @allanfernando5358 3 года назад

    Sir i have carrier chiller with water cooled condenser is it possible to convert to air cooled condenser.

    • @HVACTIME
      @HVACTIME  3 года назад +3

      I would heavily advise not to try

  • @SombraLocs
    @SombraLocs 3 года назад

    Great video! Where did get training on these? I know York doesn't offer training to none JCI technicians.

    • @HVACTIME
      @HVACTIME  3 года назад +2

      School of hard knocks and manuals lol

  • @travisburks628
    @travisburks628 3 года назад

    Have you had a oil separator on a YCAV start to plug up?

    • @HVACTIME
      @HVACTIME  3 года назад

      No haven't ran into that one

  • @fathmasameer7523
    @fathmasameer7523 3 года назад

    Hello brother how to reset alarm on this chiller

    • @HVACTIME
      @HVACTIME  3 года назад

      You do it through the system switches menu

  • @hvacr3519
    @hvacr3519 3 года назад

    where the supper heat sensor installed?

    • @HVACTIME
      @HVACTIME  3 года назад +1

      There is a thermistor on the suction pipe.

    • @hvacr3519
      @hvacr3519 3 года назад

      @@HVACTIME thanks

  • @ferdinandbergonia6053
    @ferdinandbergonia6053 2 года назад

    How to drain the oil for YVAA? please for your advise.

    • @HVACTIME
      @HVACTIME  2 года назад

      At the oil service valve

  • @aircooledchilleralltypes4938
    @aircooledchilleralltypes4938 3 года назад

    Sir need help

  • @scottymcneill6516
    @scottymcneill6516 2 года назад

    Holden, the beginning is too dark, we can't really see components.

    • @HVACTIME
      @HVACTIME  2 года назад +1

      Sorry did the best I could at the time.

    • @scottymcneill6516
      @scottymcneill6516 2 года назад

      @@HVACTIME I know brother

  • @mahamudulhasan2149
    @mahamudulhasan2149 2 года назад

    Picture not so clear