Cable Size Calculation for Medium Voltage or 11kV Electrical Systems

Поделиться
HTML-код
  • Опубликовано: 23 окт 2024

Комментарии • 58

  • @olalekanmagbade8763
    @olalekanmagbade8763 8 месяцев назад +1

    Thanks for making this video. It's the best I have found on this topic. Can you please provide info on how the reference materials used on this video? The derating factors and cable size tables will be especially helpful.

  • @amiselectricals5553
    @amiselectricals5553 Год назад +2

    Thanks for sharing these valuable details.
    Kindly send the link to get this chart.

  • @juanlotta2925
    @juanlotta2925 2 года назад +1

    It would be helpeful if you share the standards you're taking into account

  • @karthickd.n8403
    @karthickd.n8403 Год назад +2

    de rating factor reduces the current carrying ability of the cable , so 187A x 0.76 = 142A , as the FLA of transformer = 131A, selection of the cable size of 50sq.mm is good. correct me if iam wrong.

    • @adamdhible5704
      @adamdhible5704 Год назад

      That is what I thought myself. De-rating means reducing the rating of something and they should be multiplied.

    • @cedarxeda2665
      @cedarxeda2665 3 месяца назад

      You re wrong

  • @akbarshokrifirouzjaee1837
    @akbarshokrifirouzjaee1837 Год назад +2

    آفرین جوان

  • @martync8724
    @martync8724 2 года назад +2

    Very thorough and clear - thx.

  • @sniperchanel3917
    @sniperchanel3917 3 года назад +1

    Thanks for share verry interesting content

  • @faisalbukhari4119
    @faisalbukhari4119 Год назад +1

    Very Good. Keep it up. Make more videos.

  • @foras87
    @foras87 2 года назад +3

    Do you know about any software for a medium voltage cabling calculations?

    • @electricalknowledge2654
      @electricalknowledge2654  2 года назад

      Softwares are usually rough estimates and calculations vary according to the Cable manufaturers specifications or tables. So you must understand the cable size Calculation for right selection of cables.

  • @charinath5445
    @charinath5445 Год назад +1

    what is the difference between HV and LV cable sizing?

  • @MuhammadAwais-ob2ib
    @MuhammadAwais-ob2ib 2 года назад +2

    Appreciate your effort.

  • @tariknawazkhan3764
    @tariknawazkhan3764 2 года назад +3

    Thanks Man... really appreciate

  • @hidayahsahudi4567
    @hidayahsahudi4567 Год назад +1

    How to calculate if we want to use 2 or 3 nos of cables per phase?

  • @sumedhaweb1809
    @sumedhaweb1809 Год назад +1

    how can u add Rcos@ and X sine@ .these are complex numbers. it should be

  • @azhar204
    @azhar204 Год назад +1

    hi sir, i gave one doubt if the length is 15000 MTR as my able length is 15KM shall i need to divide it my 1000 or 10000..

    • @electricalknowledge2654
      @electricalknowledge2654  9 месяцев назад +1

      Brother you need to divide by 1000 if you are taking length in Meter. If your length is already in KM, then no need to divide by 1000. Means if you are taking 15km then no need to divide by 1000

  • @pradeeppoojari2786
    @pradeeppoojari2786 8 месяцев назад +1

    Current after derating factor why it is devided by 0.76..it should be 131*0.76 apprximately 100 Amp

    • @electricalknowledge2654
      @electricalknowledge2654  8 месяцев назад

      When you divide with derating factor, you will get the value of current, including derating factor margin. When you multiple with derating factor, you will get a value of current after deration which means you need to add additional derating margin to find out the value of current to be selected from cable table.

  • @tuleanhvt
    @tuleanhvt 3 года назад

    Hi H N, As I have known for the motors, we should be aware of voltage drop in both steady state & starting of motor. Could you explain for these cases of Motors?

    • @electricalknowledge2654
      @electricalknowledge2654  2 года назад

      Please watch my separate video on cable size Calculation for motors and group of motors

  • @foras87
    @foras87 2 года назад +1

    many thanks

  • @thrinadnadh9125
    @thrinadnadh9125 2 года назад

    Hello Sir, what are you showing the tables to calculate HV/MV Cables from which IEC Code?

  • @zubairali744
    @zubairali744 2 года назад

    from where you get the cos@ & Sin@ value? respectively 0.8 &0.6 please clear.

    • @electricalknowledge2654
      @electricalknowledge2654  2 года назад +1

      Power factor assume to be 0.8 in the selected case study, however the value may changes according to your requirements or conditions. The value of @ will be be calculated from cos@ which further derive the value of sin@.

    • @foras87
      @foras87 2 года назад

      @@electricalknowledge2654 could you please clarify the 'The value of @ will be be calculated from cos@ which further derive the value of sin@'?

  • @foras87
    @foras87 2 года назад

    Could you please advise how we can find the Max. Load Allowed on 1 Feeder @ HT = 5MW or 6.25MVA or 328A?

    • @electricalknowledge2654
      @electricalknowledge2654  2 года назад +3

      Hi Artemois, It all depends on how much your concerned utility or electrical distribution company allowed on one feeder.
      I have shared the allowable load limit that is 5MW on one feeder referring to what allowed in Pakistan. It varies country to country.

    • @foras87
      @foras87 2 года назад +1

      @@electricalknowledge2654 Thank you very much!

    • @amarnathmishra1461
      @amarnathmishra1461 2 года назад

      It depends upon the current carrying capacity of the conductor used.with ACSR dog conductor, you may transmit 5 MVA load at 11kv

  • @joginderpal4461
    @joginderpal4461 2 года назад +1

    120Kw motor need to cable size , with copper and aluminum, please brief example with formula

  • @dank9625
    @dank9625 7 месяцев назад

    Hello! May I ask the references for the derating factors Tnx

  • @gamalhassan2769
    @gamalhassan2769 Год назад +1

    thx

  • @mohamedali-tx4sb
    @mohamedali-tx4sb 2 года назад

    How many transformers can feed from m v switchgear in one loop

    • @electricalknowledge2654
      @electricalknowledge2654  2 года назад

      Ali, It depends upon what rating of transformer you are connecting to one feeder. However, 5MVA can be allocated on one feeder usually by WAPDA.

  • @hanhan2921
    @hanhan2921 2 года назад +1

    Hi , Can you please send us the table for single core cables please ?

  • @ScholarshipTamil
    @ScholarshipTamil 2 года назад +1

    Could possible to share supporting documents

  • @saeedahmed4651
    @saeedahmed4651 2 года назад +1

    can you please share the excel sheet for the easy calculation for pakistan.

  • @engr.saddamahamed4009
    @engr.saddamahamed4009 2 года назад

    I think 2nd slid calculation is wrong. it will be only 2500KVA or you need to divided 1000 also. thank you

    • @electricalknowledge2654
      @electricalknowledge2654  2 года назад +1

      Saddam, Answer is correct i.e 131A. However, you are right, the voltage is 11000V instead of 11kV thus to ensure the units are same.

  • @aymankazem6982
    @aymankazem6982 2 года назад

    current for low voltage side is incorrect because short circuit current must be calculate for medium voltage network 500 MVAS.C

    • @electricalknowledge2654
      @electricalknowledge2654  2 года назад

      Ayman, These calculations are for medium voltage cables and short circuit fault current calculated at specified duration of time.
      I think you are mentioning about fault current of system which are require to be calculated on base MVA of system.

  • @aizazrahim8313
    @aizazrahim8313 2 года назад +1

    Sir, plz share this cable catalog

  • @arun4846
    @arun4846 2 года назад

    👍😉

  • @osamasadekadam321
    @osamasadekadam321 5 месяцев назад

    Ok

  • @nadim606
    @nadim606 10 месяцев назад +1

    seen

  • @transientmatter6088
    @transientmatter6088 2 года назад

    when you size mv cable , only short circuit power is enough ,

    • @electricalknowledge2654
      @electricalknowledge2654  2 года назад

      You must comply three criteria i.e. Current Carrying Capacity, Voltage Drop and Short Circuit Current.

    • @transientmatter6088
      @transientmatter6088 2 года назад

      @@electricalknowledge2654
      Experience of 30 years says
      Short circuit power enough for mv cable..

    • @electricalknowledge2654
      @electricalknowledge2654  2 года назад +1

      ​@@transientmatter6088 It depends, you may be right. What would be your reference for short circuit current before selecting a MV cable.
      I would recommend to comply all the three criteria.

  • @ZarghamAli-i7c
    @ZarghamAli-i7c Год назад +1

    Hi. Can you please share your email id for a project?