HT Cable Size Calculation | Cable Sizing and Selection | Part 1

Поделиться
HTML-код
  • Опубликовано: 5 янв 2025

Комментарии • 22

  • @rakshit_elecrical_project_work
    @rakshit_elecrical_project_work 27 дней назад

    Sir what is reason for selecting 240 sq mm in nce

  • @mohamedkhalif1686
    @mohamedkhalif1686 Год назад

    salam which table is in bs7671 its similar to table 4h4a

  • @karampudisrihari6781
    @karampudisrihari6781 7 месяцев назад

    please share the clause for point of supply for public and private as per NEC

  • @sudarshanpobbati3947
    @sudarshanpobbati3947 Год назад

    👌

  • @andycanaan7161
    @andycanaan7161 3 месяца назад

    what about single core

  • @adilraza3645
    @adilraza3645 Год назад

    If the 25mmsq of cable arrivlved from table then why you moved to 240

  • @amarnathmishra1461
    @amarnathmishra1461 Год назад +1

    You are speaking of 100kva , but displayed as 1000kva.I am confused

  • @healingmeditation5970
    @healingmeditation5970 Год назад

    pleaee make part2 of HT side cable selection

  • @prlove3845
    @prlove3845 Год назад

    Why we take 100kva transformer

  • @sujitmorbale5043
    @sujitmorbale5043 11 месяцев назад

    HT SIDE YOU DISPLAYED IN DRAWING 100 KVA TRANSFORMER ,IS IT 1000 KVA OR 100 KVA ?

  • @shivlok20143
    @shivlok20143 Год назад

    Can you give nec ref code for 11 kV cable size

  • @noelfaithfulkari2857
    @noelfaithfulkari2857 Год назад

    Why is power factor not considered?

  • @nadim606
    @nadim606 Год назад

    seen

  • @mitech_mep
    @mitech_mep 9 месяцев назад +1

    Wrong! there is no cable under 35 mm2 in HT line,3 core...

  • @salmananwar8370
    @salmananwar8370 Год назад +1

    Cable sizing information is wrong.
    If u consider 1000 kva that's amp capacity is 52 amp
    Let's move further
    Include derating factor 0.65
    This is value of soil resistivity , depth of laying and temp factor
    52/0.65 = 87 amps
    Available size is 50 sqmm 3core xlpe / PVC swa/PVC
    1000 kva trafo short circuit is 0.85 ka another hand 50 mm cable short circuit rating is 7.5 ka
    Hence it's proof 50 mm square z sufficient.
    For safer side u can go for 70 sqmm

    • @ashokkumar-mk5uo
      @ashokkumar-mk5uo 8 месяцев назад

      Sir please give me your number sir I have lot of Dout give me ur number sir it's very helpful for me

  • @bagumaderick5491
    @bagumaderick5491 Год назад

    sizing simplified

  • @muhammadalimughal3488
    @muhammadalimughal3488 3 месяца назад

    GUYS.... THIS INFORMATION IS WRONG. PLEASE DON'T BE MISGUIDED TO SEE THIS VIDEO. OTHERWISE YOU WILL START BLASTING THINGS UP..

  • @MuhammadQasim-sc5gn
    @MuhammadQasim-sc5gn 5 месяцев назад +1

    Ur info is not confirmed in this vd because u r concept not clear

  • @Mohde666
    @Mohde666 Год назад

    voice is confusing voice 100kVA,written 1000kVA?

  • @abssakib2784
    @abssakib2784 Год назад +1

    False information