HOW TO CONFIGURE FST PARAMETER OF DIXELL / EVAPORATOR FAN MOTOR WILL START AT DEFAULT VALUE
HTML-код
- Опубликовано: 3 ноя 2021
- Wrong settings will result to declare the control as defective or you will run the evaporator fan motor with compressor thus stressing the output relay of compressor.
#DixellFanStopTemperature
#OCTTV
#OnCallTechnician
#HVACR
My Dixell Programming and Alarm Fixing:
• DIXELL PROGRAMMING, AL...
The author is a top notcher in Refrigeration and Air-conditioning and in Consumer Electronics, a certified Diesel Mechanic, Welder (SMAW), Cellular Phone Servicing and experienced Computer technician. - Наука
Great
Sir thanks sa video tutorial..Sir pwede ko po ba malaman value nang sensor? salamat ulit..
Ntc between 7-10k ohms sir
may isa freezer kami na ang set point ng fst 2 ang temperature negative na pero hindi pa rin mag on evaporator fan, anu sira
Follow nyo nasa video sir, or taasan mo value ng FST mo 15 - 20°c no issue po yan. Or baka deactivated ang evaporator sensor mo
Salamat master....danfoss po ba meron ka for settings? Salamat
Ala tayo danfos controller sir✌️
hello sir..pano po kapag frozen na yung evaporator pero di parin umaamdar yung fan?
Default value ng fst is 2°c sir, kung goodang control mo aandar sya dyan sa value na yan