For 33kV 26MW load, load current will be 454 Amp for pf=1. For pf=0.8, it would be 568Amp. So you can use a CT having ratio of 600/1. If 600/1 is not available, use 800/1.
Recommended Videos: 1) Power Transformer Nameplate Details Explained in Hindi: ruclips.net/video/6HrTgIOZC5k/видео.html 2) Tan Delta testing of Current Tranformer (CT) : ruclips.net/video/iFWFyM3rhuo/видео.html
Great information, thank you bro
Tanks sir for more information given through your video
Please tell How to calculate (Ith) Rated thermal short circuit current?
Sir if rayed dyanamic current is 65.5KAP
Then why short time current is only 26.2 which flow only 1 minute
what is the ratio of weight of copper and core used?
Short time current means what..u said that RMS value of rated primary current that we did not get
1400(1-1-1) what is full form ct
Tell me sir
How to understanding example: 1250/1+1+1+1A 1600/1A like this ratio
bhai esa kyu lag raha koi gunpoint pe aapke pass ye video shoot karva raha hai ?
Hi There, u gave me a gud information.
Could you please let me know steps for selection of a CT for 33KV feeders 26MW of load.
For 33kV 26MW load, load current will be 454 Amp for pf=1.
For pf=0.8, it would be 568Amp.
So you can use a CT having ratio of 600/1.
If 600/1 is not available, use 800/1.
May i know the formula please
I = P/( sqrt(3) * V * pf)
very nice vdo
Excellent. Thanks
How parimary current and short time current related by using one example..
great job bro...thanks a lot
Super sir