  • @RizwanKhan_99
    @RizwanKhan_99 Год назад +1

    Hello Andrej! Hope you're doing good!
    I want to know how to get all three phases of a triple pole (3 element) OC CDG electro-mechanical relay trip and flag and get their times, of all three phases/poles, recorded by DRTS64? Using Manual mode, I use all three current channels, phased 120degree apart, and connect them to each phase/element of my CDG relay. Then I use C1-N connection so as to stop the current injection/testing when the relay trips/flags. Problem is that although three discs of the three poles/phases/elements start to move at the same time, they do so at slightly different speeds, varying by 1or 2 seconds. This time difference is enough to causes one disc to trip and flag before the other two, which then causes C1 to stop the current injection/testing and time of only that phase/pole/element is recorded which tripped/flagged first, while time of the remaining two is not recorded. To avoid this we then resort to testing all 3 phases/poles/elements separately, one after the other, which uses up our time.
    So, is there any way to test all 3 poles/elements simultaneously such that times of all three phases is also recorded? Would appreciate a lot.
    Thanks
    Rizwan

    • @sheppo17
      @sheppo17  Год назад +1

      Dear Rizwan ! I have answered you in an email. Please confirm that you have recieved it. Thank you !

    • @RizwanKhan_99
      @RizwanKhan_99 Год назад +1

      @@sheppo17 recieved. Thanks for the prompt response Andrej.

  • @RizwanKhan_99
    @RizwanKhan_99 Год назад

    Hi Andrej,
    I'm using DRTS64 in Manual mode thru' TDMS. I wanted to know if TDMS can record the trip time (and also display the time in report) when i manually stop the testing using the red stop button, provided on top next to play button? I know the trip time is recorded and displayed on report when i use the binary input "C1" (as wet 110Vdc), but no trip time is recorded , i.e., "time-out" is seen when i manually stop the test. Basically I test relay installed on switchboard, so i don't require C1 contact, and so i manually stop the test when i visually see the relay operating/flagging. Is there any option to get that trip time? Will help us a lot. Otherwise we'd have to carryout rewiring of the installed relay to incorporate C1 contact.
    Thanks

    • @sheppo17
      @sheppo17  Год назад +1

      Hi Rizwan, can you write me an email to asepcic@doble.com

    • @RizwanKhan_99
      @RizwanKhan_99 Год назад

      @@sheppo17 ok

  • @nacsid9397
    @nacsid9397 5 лет назад

    When we try a test by ISA DRTS. a fault message appear it's 75-overload v1. v2 and v3 then v generator dc overload ! Can you give us an idea and what we hav to do !

  • @DK-sd3uk
    @DK-sd3uk Год назад

    Dear Andrej! Any template for autoreclosing testing??

    • @sheppo17
      @sheppo17  Год назад +1

      Hi DK ! Please send me a mail to asepcic@doble.com to have a proper exchange of ideas. I can help you with AR

    • @DK-sd3uk
      @DK-sd3uk Год назад

      @@sheppo17 Hi! We have sent to you our contact. Thanks

  • @sheppo17
    @sheppo17  5 лет назад +1

    Hi Sid ! Which device do you have ? DRTS 6 or 3 or 3 + or 33/34/64/66 ? Also what were you doing just before the fault appeared ? Please write to me to andrej.sepcic@altanova-group.com