@@electricaltech4u45 The opinions of customers like you are very helpful in producing better products. By all means, I would like to ask for advice and exchange of opinions in the future. Would it be possible to exchange opinion? Are there any emails, website or sns I can exchange?
Assalamo Alikum Bhai bahut Achch video banaya tha or vi koiss kare video Bana ne ke lea Allah Talah Aap ki hedayat de Allah Hafizzz All cable ki check Ker ne ke lea 500 DC voltage ka paryug Kiya jatah hai
ASALAM O ALIKUM sir mery 2 question hain 1.jaisy ap ny kaha ky ye cable 500 voltage tk ky liye ha to kaisy pta chaly ga ky kitny mm ki cable ko kitny voltage py use kiya ja skta ha? 2.cables ki resistance kinty ohm/mega ohm honi chahiye
W Salam dear bro. Thank. Low voltage cable me hum 500 voltage tak use karsakty hy q agar ap us ko higher voltage par use karengy us ka insulation harabe hoga. Har wire k oper us ka complete details or amp and resistance per foot avaliable hota hy. 2. Har wire ka resistance alag hota hy ye calculation during design me hoti hy .magar during testing hum cable ke resistance jitni up hogi utna us ka insulation good hoga .magar low resistance weakness shows karta hy. Cable selection and resistance par video banaoga later up ke sari confusion finsh hogi.Insha Allah
Thanks bro. Yes bro agar open hao ye try me cable hao .otherwise agar down cable sirf cable locator Device say he pata laga sakta hy faults area ka. Mostly joint or heavy equipment he cable to damage karty hy
Hi sir copper ya aluminium 4 core cables ki minimum megger IR value kitni honi chahiye jis minimum IR value ko sahi & safe maan kar cables ko electrical panel,motor me connect karke use me le sakte hai. Please explain
Dear both are good during the work because multimeter doesn't measure amp nd clamp meter doesn't measures some electronice quipment,but if testing the cable megger requires.
@@electricaltech4u45 sir ager 1k. meter Lambi cable Zameen k Ander 4 Cor cable damage short circut ho TU kese maloom Hoga k ye kis jaga see fulty ha .sir aap ki Rehnumai chahie
Question: jab ham megger meter se dc voltage apply krtey hain to kia wo megger ki dono wires se voltage jatey hain yan aik hi wire se aur jab cable ka dosra end open hota hai voltage reture keisy atey hain Pls ans
Dear bro dono me voltage hota hy jab aapase me short hota hy tab meter detect karta hy .magar jab last end open hoga to return nahi hoga reading up hogi. Agar leakage hy insulation me to meter detect karlega au readings low hogai.
Thanks bro. Bro amp par depends karta hy aur voltage level par .example 70 mm low me be hy au medium voltage me be hy magr hum medium k lie xlpe cable select karty hy insulation ke waja sy.
thank you.. sir .. q k hamein complete information mil jae.. fault doodna aur teek krna. agr fault ka pata chal jae aur phr teek karna adhoora reh jaya. then no advantage.. I subscribed your channel and waiting for your best videos
Bhai cable ka issue hy ya load ka issue jab trip howta tab technician na check kiya ? Ap ko kiya bola issue ya pir load distribution me problems. Ya pir details Mere sath share kary .plz
Dear bro. Ye mm par depends nahi karta ye cable k rating par hota hy.like 120 mm low voltage me ap 500dcv say zida inject karogy to insulation damage hoga .ap agar 120 mm mv cable ko hotpot testing karty hy its up to 10kv. Low voltage separately Medium voltage separately High voltage separately.
Sir g .dc apply kow da kit da lasa device design vi kho ac dangerous di example phase ground di us chai mong volt apply ko nu break trip ke do ke time aalie au resistance hum na show kawi.
Thanks bro. Dear bro if joint available so remove cable separately and check otherwise need cable locator without this device didn't possible if cable underground. We also request for device if we receive we make again video regarding this
Mashallah very important video
Very informative video sir
MashaAllah... Very informative video... JazakAllah Khair...
Thanks bro
Good sir good lecture
Very good information for me and others
Thanks 😊
Great work👍
Der awla bahi, great work.
Thanks for your love ❤.
Masha Allah
Shkryia sir g
Thanks bro
VERY NICE EXPLAINATION.
Thanks bro 💙
VrY Inf0rMaTivE Vide0 Sir Thnk y0u s0 MuCh❤
Thanks bro
Amazing sir
Thanks bro
Nicely video
Thanks bro
Very good and video
Thanks bro
Very helpful video ❤️
Thanks bro
Nice information sir 🙏
Thanks dear bro.
Thanks for making such an informative videos Sir. Thank you so much.
Thanks for your love
GOOD EXPLANATION KEEP ON GOING
Thanks bro
Thanks four video
So super very helpful vedeo
Thanks bro
@@electricaltech4u45 heartily most welcomewel come
Good work
Thanks bro
Thank you Sir.
Real practical knowledge .
Thanks bro 💙
MAASAALLAH Bhut khub sir
Thanks sir g
@@electricaltech4u45 please check flatform you used in your account's *About*
Goood work! Bahut badhiya.
Thanks bro
good sir
very interested video
Thanks sir
very good
Good
Wonderful Video
Thanks dear bro
Good information
Thanks
walaikum assalam ..bhai jaan
Thanks bro 💙
Walaikum Assalaam bhi..
nice vai
Thanks bro
thank you sir
God bless you .. brother
Thanks bro for your love ❤️
Very useful
Thanks bro
Nice
Bahot sundar sir
Aur banaye video electrical
Thanks for love
Salaam, Bhai Hyderabadi dekhrein..ma sha Allah
Thanks bro. Me from pk
Thinks
Thanks bro
Tks very useful mes 👍👌💐
Thanks bro
So good sir
V good
thanks
Nice information thanks but please explain of three wire connection 3125A Earth Guard Line
Thanks 😊. Ok I will try make another video related of your query
Thank sir
My name is Kusaka of Kyoritsu Electrical instruments works, ltd.
Thank you for using our product.
How was the usability of the product?
Thanks Mr kusaka .yes we are satisfied from your products 😊 .
@@electricaltech4u45
Thank you very much for your reply.
I am glad that 3125A seems to be useful.
Do you work as an electrician?
Electrical Engineer
@@electricaltech4u45
The opinions of customers like you are very helpful in producing better products.
By all means, I would like to ask for advice and exchange of opinions in the future.
Would it be possible to exchange opinion?
Are there any emails, website or sns I can exchange?
@@user-uu8pg7gb7q yes bro. ayarkhan140@gmail.com
Megger pa bara k mazeedara video jora ka sir g
Ok bro
Assalamo Alikum Bhai bahut Achch video banaya tha or vi koiss kare video Bana ne ke lea Allah Talah Aap ki hedayat de Allah Hafizzz All cable ki check Ker ne ke lea 500 DC voltage ka paryug Kiya jatah hai
Thanks bro. 😊
Very informative, thanks for explaining each step.
Dair kha rora zabardast yar, kamzy job kae ?
Saudi ke rora
nice bro
Thanks bro
ASALAM O ALIKUM sir mery 2 question hain
1.jaisy ap ny kaha ky ye cable 500 voltage tk ky liye ha to kaisy pta chaly ga ky kitny mm ki cable ko kitny voltage py use kiya ja skta ha?
2.cables ki resistance kinty ohm/mega ohm honi chahiye
W Salam dear bro. Thank. Low voltage cable me hum 500 voltage tak use karsakty hy q agar ap us ko higher voltage par use karengy us ka insulation harabe hoga. Har wire k oper us ka complete details or amp and resistance per foot avaliable hota hy.
2. Har wire ka resistance alag hota hy ye calculation during design me hoti hy .magar during testing hum cable ke resistance jitni up hogi utna us ka insulation good hoga .magar low resistance weakness shows karta hy. Cable selection and resistance par video banaoga later up ke sari confusion finsh hogi.Insha Allah
Thanks assalamualaikum
Thanks bro. W Salam
good
Thanks bro
bahot achi video bnaai aap ne mgr aik question hai iss fault ko dooor kaisy kia ja sakta ha jo trip ho raha breaker kindly btaa dijyee
Thanks bro. Yes bro agar open hao ye try me cable hao .otherwise agar down cable sirf cable locator Device say he pata laga sakta hy faults area ka. Mostly joint or heavy equipment he cable to damage karty hy
very informative
Thanks bro
Thank you so much sir
Thanks bro
Nice booss
Thanks bro
🤩🤩🤩🤩🤩🤩
subscribed to your channel.
Thanks bhai
Sir transformer testing per ekn video... Banaye...
Masha Allah bless you un educat will do this
Thanks bro
🌹🌹🌹
💖💖💖
thank you sir ji
please sir ht cable ka video bnaye
Thanks bro. Insha Allah soon
Thanks
Thanks bro
D. B check Kar ne ka tarika Megger se
thanks
Thanks bro
Make an video on Testing Of cable
Thanks bro. Yes soon
Earth Guard or Line tino probe ko connect kar ke aek video banao
Ok bro.
@@electricaltech4u45 me wait kar raha hu please pakka banana bhai thanks
Kitne pe kitna voltage dete he or kitne time tk krte he maggering
Hi sir copper ya aluminium 4 core cables ki minimum megger IR value kitni honi chahiye jis minimum IR value ko sahi & safe maan kar cables ko electrical panel,motor me connect karke use me le sakte hai. Please explain
I solve same matter
Alhumdulilah v good bro
Sir,which one better. multimeter or clamp metre. give me advice
Dear both are good during the work because multimeter doesn't measure amp nd clamp meter doesn't measures some electronice quipment,but if testing the cable megger requires.
Sir plz loads change over connection DG and grids
Thanks bro. Regarding load changing and dg videos available on channel grid changeover soon.
Hi I’m looking for advice…I have a conduit with a bundle of 190 #14 control cables I need to megger test. How do I megger test 190 cables?
Dear bro, can you explain your inquiry because 190 ???
Agr connection na khola Jay aur phuse nikal ke kar sakate hai sir
Yes bro agar koie connection connect na hao aur grounding separate hao.
Sir i have one dout what about the onther cable end we have to short the end or what plz clarify
Look bro.
When we test insulation, it should be all open, but when you check R,Y,B similar one with another
Cable copper ya alu ki hai minimum magge value kitna honi chahiye copper cable k liya
I will upload another video soon
If required urgently plz share your contact details
Aslamo alikum sir pak me 4 Cor cble under ground foulty ho sir koi sasta idea ya detector k bare me agahi de .shukria
Yes bro make series lamps 200w and check
@@electricaltech4u45 sir ager 1k. meter Lambi cable Zameen k Ander 4 Cor cable damage short circut ho TU kese maloom Hoga k ye kis jaga see fulty ha .sir aap ki Rehnumai chahie
@@electricaltech4u45 ? Ye kese Hoga
@@electricaltech4u45 200 w? help me sir
Sar Mera yah sawal hai ground aur Newton mein metar ke pass Mila de jaaye Aage current different aaega yah same
Thanks bro. Bhai agar ap unko milaodo phir be same reading aayegi mager separately.
Bulb lagkar v check kar sakta hai ,if no maga metrr
Thanks bro. Yes in series me lamp say low voltage acceptable if small distances.magar ap insulation ke strength ka pata nahi lagasakty
Meggering testing ke Bad m short n kiya uska tarika bataen.
Plz clear kary apna question
Sir 95sq.mm or 185sq.mm ke cable mein konse size ka lug lagega please bataye
Dear bro same when send the cable number to for purchase they given same lugs.
For complete details I make a video soon.
Question: jab ham megger meter se dc voltage apply krtey hain to kia wo megger ki dono wires se voltage jatey hain yan aik hi wire se aur jab cable ka dosra end open hota hai voltage reture keisy atey hain
Pls ans
Dear bro dono me voltage hota hy jab aapase me short hota hy tab meter detect karta hy .magar jab last end open hoga to return nahi hoga reading up hogi. Agar leakage hy insulation me to meter detect karlega au readings low hogai.
Sir aap yeh bata sakte kitne mm ka cable kitna voltage lagi
Thanks bro. Bro amp par depends karta hy aur voltage level par .example 70 mm low me be hy au medium voltage me be hy magr hum medium k lie xlpe cable select karty hy insulation ke waja sy.
Kya ye system mobile app me maujud hai ??
Thanks bro. Some devices available WiFi or Bluetooth but this device no
Sir mccb breker ko meger kaise check karte hai
Bhai AK bat hay jetna ka cabal rahata hay utna volt say magar karsak Tay hay
ground may fault hai eee b video me show karo .. usko Kase teek karna hai?
Thanks bro. Ok if we get any faults regarding your inquiry we make insha Allah
thank you.. sir .. q k hamein complete information mil jae.. fault doodna aur teek krna. agr fault ka pata chal jae aur phr teek karna adhoora reh jaya. then no advantage..
I subscribed your channel and waiting for your best videos
Vcb rack out And full details please
Some video regarding VCB available on playlist some Insha Allah soon.
salam bro yar mera gar k cbale 35 mm he or bar bar trip krta he or ajeb bat a he k kni 2 din bad trip krta ya per din me 3.4 bar krta he
Bhai cable ka issue hy ya load ka issue jab trip howta tab technician na check kiya ? Ap ko kiya bola issue ya pir load distribution me problems. Ya pir details Mere sath share kary .plz
@@electricaltech4u45 bhai load ka masla nhe he or na cble ka masla he sub breker change kia or main breker b chang krda likn masla hal nhe hora he
120 sq mm kelie hum megger ko 5000 dc voltage range set krte hain lekn yahan ap ne as cable ko 500 v pr check kiya he sir, please explain it
Dear bro. Ye mm par depends nahi karta ye cable k rating par hota hy.like 120 mm low voltage me ap 500dcv say zida inject karogy to insulation damage hoga .ap agar 120 mm mv cable ko hotpot testing karty hy its up to 10kv.
Low voltage separately
Medium voltage separately
High voltage separately.
I know
Thanks 😊
السلام عليكم اخي الفاضل النبيل
لو تتكرم تضع ترجمه باللغه العربيه
آسف يا أخي ، لا أستطيع التحدث بالعربية
Megger value kitna aata he cable ka sir
Bhai ye fix nahi hy magar kuch acceptable hy like g.oh
Jitna increase hoga itna best hoga
sir taso D. c voltage wale apply kawae.... AC wale na warkawae
Sir g .dc apply kow da kit da lasa device design vi kho ac dangerous di example phase ground di us chai mong volt apply ko nu break trip ke do ke time aalie au resistance hum na show kawi.
@@electricaltech4u45 thank you Sir
Wlc bro .sir rana ma jora wa.sirf rore rata waya
@@electricaltech4u45 Inshallah sir ao ror dwra ba drta wayu che ezdakra Drna kao sir mo eee
Sir do video in English language
Thanks bro. Ok no problem
Dear sir good afternoon sir mere ko interview questions chahiye electrical technician ka interview of dubai
Ok bro. I do my best
Omega gega ma Aya to Sahi ha ager ohm ma Aya to short ha
Thanks bro. Bhai jitna low itna week jitna high utna good.
Mai naw digital meger h usme kise test kare
Kindly share pic or details after I do my best 👌
Sir Exact fault location kaise pata kre ?
Thanks bro. Dear bro if joint available so remove cable separately and check otherwise need cable locator without this device didn't possible if cable underground. We also request for device if we receive we make again video regarding this
App Ka Office Pakistan Mai kidar hai
Thanks bro. Sorry me in saudi arabia
Why you havent connected Guard?
Thanks bro. Dear bro some testing require guard and some cases no need. No problem I make separately video for All .