How to Measure a 4-20mA Circuit without Blowing Your Fuse

Поделиться
HTML-код
  • Опубликовано: 6 фев 2024
  • The key to measuring a 4-20mA signal is realizing that it is a current signal so to measure it, your meter must become part of the loop.
    Helping you become a better technician so you will always be in demand
    Get the full details of this lesson at courses.twcontrols.com/
    Items used in this video:
    PLC Trainer twcontrols.com/plc-trainers
    Fluke 87V controls.tw/fluke-87V
    The above links make these videos possible. Please use them!
    Subscribe to our Main channel for How To's ruclips.net/user/TimWilbo...
    Subscribe to our 2nd Channel for Quick Tips www.youtube.com/@TimWilborne2...
    Support these videos by becoming a patron on Patreon: / timwilborne
  • НаукаНаука

Комментарии • 30

  • @unknown_1337
    @unknown_1337 26 дней назад +1

    I always teach people that a multimeter becomes a “fused jumper wire” in amp measurement mode. This can be confirmed by measuring resistance or continuity of the test leads with another multimeter.
    Once the person understands their meter is now a “jumper wire” (with a fuse in series with the test leads), i show them how to use the “jumper wire” to test/force +24vdc inputs to a PLC.

    • @user-it9ew5vz8d
      @user-it9ew5vz8d 7 дней назад

      ruclips.net/video/EsbyXdg_dwk/видео.htmlsi=9Whf-r2bNiq5FRdB

  • @ModStarCrash
    @ModStarCrash 4 месяца назад +5

    WAY more than half the meters out there have that fuse blown 😂

    • @TimWilborne
      @TimWilborne  4 месяца назад +2

      Probably so, they seem to blow them every week I run a training class 😂

  • @RadDadisRad
    @RadDadisRad 4 месяца назад +2

    Super important!!! I’ve seen so many people blow fuses. I have 6 fuses in my meter case, I started with 10 fuses. I’ve had 3 technicians blow fuses while I was there or have blown fuses in their meter.

    • @TimWilborne
      @TimWilborne  4 месяца назад +2

      Happens more often than people realize!

  • @RadDadisRad
    @RadDadisRad 4 месяца назад +3

    We have bought a couple of our facilities A3004 Fluke meters because they are induction meters instead of contact meters.

    • @TimWilborne
      @TimWilborne  4 месяца назад +1

      Nice accessory

    • @RadDadisRad
      @RadDadisRad 4 месяца назад +1

      @@TimWilborne the safety man and bean counters like them for the ability to avoid contact with live terminals.

    • @TimWilborne
      @TimWilborne  4 месяца назад +2

      Plus you don't disrupt the process.

  • @johnneyland3334
    @johnneyland3334 4 месяца назад +1

    Great video Tim !! So helpful !! Thank you !! J

  • @ardentdfender4116
    @ardentdfender4116 3 месяца назад +1

    Very important tip. I hope i can remember.

  • @Vladdimur
    @Vladdimur 4 месяца назад +1

    Yes please for some practical examples of how to use the process meter in the 4-20ma setting :D

  • @user-kq7sg3qp8n
    @user-kq7sg3qp8n 4 месяца назад +1

    Aemc k110 clamp or the milwaukee amp clamp meter. I have a tendency to stick with probe accessories as you can't blow the meter fuses with those

  • @aubreyroche5080
    @aubreyroche5080 4 месяца назад +1

    Awesome !!!! It Happens !

  • @FocusKnob
    @FocusKnob 3 месяца назад +1

    When I'm reading small currents how come switching from the mA port to the A port shows widely different results?

    • @TimWilborne
      @TimWilborne  3 месяца назад +1

      It has to do with the resolution and accuracy on the different ranges. Take the 87V for example, if you look at page 48 of the following manual. On the 60mA range, the resolution is 0.01 mA. On the 10 amp range the resolution is 0.01 A or 10 mA meaning before you even consider accuracy, it is + or - 10mA.
      dam-assets.fluke.com/s3fs-public/80v_____umeng0200.pdf?tKDGTic.KN0dP9_UJVtSyLsuYWEUp3SY

  • @SupremeRuleroftheWorld
    @SupremeRuleroftheWorld 4 месяца назад +1

    if you need to measure 4~20mA signals a lot you are better off getting a meter like the Brymen BM789. it has a special 4~20mA mode that translates the 4~20mA range into percent.

  • @michaelreardon303
    @michaelreardon303 3 дня назад +1

    100% sound like Fix-It-Felix. Not an insult.

  • @davcot3675
    @davcot3675 4 месяца назад +1

    Plus the proper DMM fuse is $30 each but gotta buy proper one

  • @ihatemybosses
    @ihatemybosses 4 месяца назад +1

    Why introduce a term that is not part of any industry standard I have run across? Series and parallel are the terms everyone has agreed on.

    • @TimWilborne
      @TimWilborne  4 месяца назад +2

      Which term did I introduce that you haven't ran across?