Sir txv ka clockwise and counterclockwise ghumane per discharge pressure and subcool temp me kya kya hoga cooling load increase karna kiya evaporator inlet temp kitna range ma rakhe sir
Thanks Dear brother for your valuable comments, TXV to koyi bi ho bs evaporating temp: ki range se dekhi jati hai awr lagayi jati hai, But capillary tube ka taluq mass flow se hai, Ap 0.059 ki capillary tube 24 inch two capillary tubes laga sakte hain...
Brother 1 khas limit tk flow barhany se cooling increase hoga awr temp: decrease hoga, but hr unit me limit different hota hai. Uss khas limit me flow barhany ka matlab evaporator me more refrigerant maujood hota hai, awr more BTUs absorb honge. Agar ap flow bahut zyada barhayenge Jo ke evaporator design se zyada hoga to usss surat me evaporator me temp: halka sa barhega jis ka matlab cooling km hota Jayega .
Thank u so much sir sir good expension valve me expension valve se output me ice formation hoga ki naiii hoga sir example k liya chiller cold storage refrigeration system me use expension valve me
Ye depend karta hai refrigerant ke pressure pr... Agar refrigerant Ka pressure TXV se Aage Yani evaporator me ap zyada rakte hain to only NAMI hogi...but agar evaporator pressure ap km rakte hain to TXV se Aage ice hoga
Sorry brother for late reply, Agar bellows adjustment karna ho to suction pr gauge laga kr screw ko tight awr loose kiya jata hai, JB suction normal ho jaye i-e 20 se 25 Psig ho Jaye to adjustment complete hogi. Agar superheat adjustment me issue to phir suction line pr sensing bulb ko Aage peeche Le Jaye to suction pressure gauge pr khud bakhud ho jayi
@@FKmechofficial sir central Africa se hn mere pas frozen refer container ha jis ka temperature -20⁰ tak jhata ha Kuch dino se temperature kafi decrease ho rha ha hr cheze ok ha ager valve ko adjusting kr dun TU kitni degree farq pare ga,6 ton ki unit ha plz rply
Thanks for your sharing....👍👍👍
You are welcome Dear
Very informative video
@@Hvactechnicalmaster thanks Dear brother ❤️
Nice Information ❤🎉
Thanks Dear brother ❤️
Nice sir👌👍
Thanks Dear brother
Waw great video Sir
Thanks Dear
Sir apke sare video bahot hi jankari purn hai age bhi aise hi video banate rahe ❤ 👍
Thanks Dear brother for your valuable comments 👍
Aoa farman bahi bht achi video ha mashallah
Thanks Dear brother ❤️
Masallah masallah kya baat h aap ki aap ka samjane bhot badya h Allah hafiz
Bahut Shukarya Bhai ❤️
Very well explained
Thanks Dear brother ❤️
Very nice teacher
Thanks
valuable information
Shukarya Bhai ❤️
Excellent sir
Thanks Dear brother ❤️
Bahot he badhiya bhaya❤
Thanks Dear Sir for your valuable comments ❤️
Great great explanation.
Thanks Dear brother for your valuable comments ❤️
Thanks sir 😊
You are welcome Dear ❤️
Good experts.
Thanks Dear brother ❤️
Boss your City? I am from Chittagong, Bangladesh.
@@jahangiralam-qr9px thanks Dear brother from Bangladesh,,,
I am from Pakistan
Thanks 👍
Very nice nice
Thanks Dear brother
Sir txv ka clockwise and counterclockwise ghumane per discharge pressure and subcool temp me kya kya hoga cooling load increase karna kiya evaporator inlet temp kitna range ma rakhe sir
Brother, cooling load maintain Karne kelie hr refrigerant ke pressure ranges different hote hain
+ temp wale me evapotor me temp maintain karne k liya txv output temp kitna set kiya sir
Sir Walkin chiller ka same ex value new replaced kiya fir bi ex value ka out let me icing horaha hai kya reason hai gas pressure pura sahi hai
Refrigerant kam ho sakta hai,
Refrigerant ka pressure km adjustment ki waja se,
Super heat adjustment problem
Nice
Thanks
Goodsar
جزاكَ اللّٰه
Shukarya Janab ❤️
wow 😮
Sir agar 5ton ke package ac me txv installation karna ho to capillary ka size aur length kitna hona chahiye
Thanks Dear brother for your valuable comments,
TXV to koyi bi ho bs evaporating temp: ki range se dekhi jati hai awr lagayi jati hai,
But capillary tube ka taluq mass flow se hai, Ap 0.059 ki capillary tube 24 inch two capillary tubes laga sakte hain...
From Adjusting screw gas is leaking after opening the cap. Is that normal or have some problem.
Sir ji Danfoss TEX 55 (R22)ke exponsal valve k bare me bataye
Ok Dear Soon Insha Allah ❤️
Refrigerant flow barhany se tou cooling increase aur temp kam hona chahye. Idher ulta kese ho rha plz explain
Brother 1 khas limit tk flow barhany se cooling increase hoga awr temp: decrease hoga, but hr unit me limit different hota hai.
Uss khas limit me flow barhany ka matlab evaporator me more refrigerant maujood hota hai, awr more BTUs absorb honge.
Agar ap flow bahut zyada barhayenge Jo ke evaporator design se zyada hoga to usss surat me evaporator me temp: halka sa barhega jis ka matlab cooling km hota Jayega .
@@FKmechofficial thank u so much sir. Kya iss ka koi reference material hai koi book etc
@@ammarmaqsood1493 Exactly apko Google se mil sakte hai Bhai,
Engineer levels ke bhi awr students levels ke bhi
Salam. Sir ye jou temp ap ny consider kiye ye refrigerant k thy ya air k thy jisko cool kerna tha ?
Brother temp: refrigerant ka hai but ye directly air ko bhi effect karega
Sir expansion valve ya filter block hoga tyo discharge pressure ghatega ya badga amp me Kay hota ya
Dear brother Discharge pressure Tora SA barega...awr suction pressure me kafi Kami ayegi...
Amp sir
@@dirajgotame agar compressor rotary hai pir ampr badenge...awr agar compressor piston wala hai to pir ampr drop honge
@@FKmechofficial
Sir wih kiuyon?
Amp tou increase hi hon gay as compressor has to work hard now
@@zuone3573 yes but suction pressure agar low ho jaye, to compressor hard work kaise kr Sakta hai, matlab suction line se flow me kami ho jayegi
Thank u so much sir sir good expension valve me expension valve se output me ice formation hoga ki naiii hoga sir example k liya chiller cold storage refrigeration system me use expension valve me
Ye depend karta hai refrigerant ke pressure pr...
Agar refrigerant Ka pressure TXV se Aage Yani evaporator me ap zyada rakte hain to only NAMI hogi...but agar evaporator pressure ap km rakte hain to TXV se Aage ice hoga
Cold storage minus 12 centrigrade me ice aarahe good he sir
Sir 0 degree centrigrade Upper temp example 3 degree me expension me ice aayaga tyo bad he
@@prakashgotame8875 temp below 0⁰C ki surat me ice ayega...
Agar evaporator coil ki temp 0 se zyada Hoga to ice nhi balke only nami ayigi
OK sir
Sir coldroom ke evaporator ke upar on karte hi thode der me ice araha hai kuch upay bataye please
Check the Expansion valve brother,
I'm sorry for replying late
May you please add subtitles so that students from Africa will understand way better🙏🏿🙏🏿🙏🏿🙏🏿
Thanks Dear for connecting with us...
The subtitles are included in video 🙏
Sir agar valve ki setting bigar jaye to wapas usko set kaise kre? 404 refrigerant use krta hu 5 ton semi hermatic compressor h
Sorry brother for late reply,
Agar bellows adjustment karna ho to suction pr gauge laga kr screw ko tight awr loose kiya jata hai, JB suction normal ho jaye i-e 20 se 25 Psig ho Jaye to adjustment complete hogi.
Agar superheat adjustment me issue to phir suction line pr sensing bulb ko Aage peeche Le Jaye to suction pressure gauge pr khud bakhud ho jayi
Sir valve k adjustment se room temperature pe aser ho ga k ni plz rply
Yes, zaror hota asar kyunke TXV adjustment cooling coil me flow barane ya kam karne pr hota hai
@@FKmechofficial sir central Africa se hn mere pas frozen refer container ha jis ka temperature -20⁰ tak jhata ha Kuch dino se temperature kafi decrease ho rha ha hr cheze ok ha ager valve ko adjusting kr dun TU kitni degree farq pare ga,6 ton ki unit ha plz rply
@@IshfaqKhann Dear, konsa temp: decrease ho raha hai ?
Ambient ya evaporator coil temp: ?
@@FKmechofficial room temperature
@@IshfaqKhann adjustment se tora bahut faraq ho sakta hai. Taqreeban 4 to 5 degrees.
Ap Pakistan se ho ya India se ?
اس میں گیس کتنے کلو ہے جو اپ کا انتظار رہے گا
900 gram Bhai ❤️
Assalamualikum
Mera mins 11 ka chiller hi lekin wo sat nahi ho raha hi plz help
Wa Alaikumussalam
Kiya masla hai uss me brother ?
APNA number send Kary
@@marfan8709 03059126576
Nic
❤
Thanks 👍
ruclips.net/video/vtVBpEzApOE/видео.htmlsi=pVO7T7mYFbSPGEqL
If sensor bellow is break then what happen
Over flow of refrigerant to evaporator
❤❤❤❤❤
Thanks Dear Sir ❤️
Orifice kitna number he
Brother TXV ke orifice Ke number Ka Kiya matlab hai,
Me ne to Kabhi TXV orifice ke number Ka Kabhi nhi suna hai...
Accha bro exprion valve bole to shop vala bolega ki kitne number TXV valve
Krupya Aapka number bhejiye bro
To humko bolna pdega na big bro ki 0 number ki orifice 1 number orifice 2 number orific 3 number orifice
@@baldevbhambhariya1061 brother ye to TOR ke hisab se milti hai,,
Ton of refrigeration ke hisab se
Compressor R404 ka hi
No, The Refrigerant is R22
Sir,When I reduce the refrigerant with txv, more gas will accumulate in the condenser, will not it increase the pressure on the compressor?
@@MIJANURRAHMAN-xr2ew yes it increase burden on compressor if so much pressure accumulate in condenser