HVAC Service Call: LG MULTI V IV Not Cooling/Heating (LG Multi V 5 Error Code CH26/Error Code 261)

Поделиться
HTML-код
  • Опубликовано: 17 окт 2024
  • HVAC Service Call: LG MULTI V IV Not Cooling/Heating (LG Multi V 5 Error Code CH26/Error Code 261) LG Error Code CH21 / LG Error Code 211 / LG Error Code CH26 / LG Error Code 261 / LG Error Code CH29 / LG Error Code 291 / LG HVAC Training / LG HVAC Troubleshooting / LG VRV / LG VRF / LG Heat Recovery Heat Pump / LG Heat Pump / #HVAC #LG #HEATPUMP #JUMPERMANTECH
    Veto Pro Pac TECH MC
    amzn.to/3gURJyZ
    Fluke 902 FC HVAC True-RMS Clamp Meter
    amzn.to/39wvwiK​​
    Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
    amzn.to/3VNYXDv
    Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
    amzn.to/3FcWElQ
    Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
    amzn.to/3E4W0Fr
    Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
    amzn.to/3mi8Fih
    Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
    amzn.to/3FbDufQ
    Milwaukee M12 2-Tool Combo Kit 2598-22
    amzn.to/3CtCRNC
    Milwaukee Cut 1 Dipped GLOVES L
    amzn.to/3s8H18O​
    Milwaukee 2351-20 M12 LED Stick Light
    amzn.to/3rVJKEK
    Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
    amzn.to/3e53ygW
    Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
    amzn.to/3qazJkC
    Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
    amzn.to/32fxC6I
    Milwaukee 4932459097 Billet Torpedo Level
    amzn.to/30Dh6Nw
    Milwaukee Wide Blade Magnetic Tape Measure 16 FT
    amzn.to/3yEN7kL
    Milwaukee Fine Pt. Markers Black
    amzn.to/3e4fH5W
    Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
    amzn.to/320XiEF
    Klein Tools 11-in-1 Screwdriver / Nut Driver
    amzn.to/3s3o8ql
    Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
    amzn.to/3e4ur4x
    Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
    amzn.to/321n4bW
    Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
    amzn.to/3J11hS1
    Klein Tools 32581 4-in-1 Electronics Screwdriver Set
    amzn.to/3yEj3WC
    Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
    amzn.to/3yRUiGJ
    Yellow Jacket 18975 Charge Tool
    amzn.to/3J4pfvJ
    Yellow Jacket 60613 Service ratchet Wrench
    amzn.to/3E8iYeZ
    Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
    amzn.to/3q0TQ4M
    Gerber Gear 30-000469N Dime Mini Multitool Keychain
    amzn.to/32ekMG6
    LEATHERMAN Style PS Keychain Multitool
    amzn.to/3sdGdSB
    SOG Flint Survival & Defense Tool Safety Whistle, Fire Starter, Glass Breaker (FT1001)
    amzn.to/3mhy63p
    3 Pieces Telescoping Inspection Mirror
    amzn.to/3e6tubS
    Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
    amzn.to/3e0USrY
    Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
    amzn.to/3qqKlw7
    Crescent 4" Adjustable Cushion Grip Wrench
    amzn.to/3J4qsmL
    Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
    amzn.to/30EQmw5
    Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
    amzn.to/3H9iYAu
    KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
    amzn.to/3e3IEi7
    KNIPEX Tools - Long Nose Pliers With Cutter
    amzn.to/3gUSE2i
    KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
    amzn.to/3p6lFsZ
    KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
    amzn.to/3mh8K5U
    KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
    amzn.to/3F1VScb
    KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
    amzn.to/3sftr5Q
    KNIPEX Tools 3 Piece Cobra Pliers Set
    amzn.to/3FbRwy7
    KNIPEX Tools Pliers Wrench 3-Piece Set
    amzn.to/3nnRLfW
    Empire Level 2783 Brass Pocket Caliper
    amzn.to/3FcqCGp
    Diversitech GG-1 Drain Gun for A/C Condensate Lines
    amzn.to/32cuYib
    Diversitech Corp 16G CO2 Drain Gun Cartridges GGC-12
    amzn.to/3J0O8IP
    CPS Solenoid Valve Magnet Tool TLMKC18
    amzn.to/3E6rX07

Комментарии • 78

  • @HVAC544
    @HVAC544 Год назад +10

    Cool to see more VRF content. We've had a bunch of issues with the gen v units losing compressors. I'd assume most of it was install/commission issues more than anything. We cut one open and the scroll was shattered.

    • @JumpermanTech
      @JumpermanTech  Год назад +1

      Glad you're enjoying the content. A 3rd unit went down today but it was an outdoor fan motor related issue. This place is going to be fun

    • @JumpermanTech
      @JumpermanTech  Год назад +1

      This location has had & still has a bad experience with losing compressors. Any input or advice? Thanks for watching!

    • @HVAC544
      @HVAC544 Год назад

      @@JumpermanTech Never messed with the Gen4 units only experience with the 5's. We have had LG tech support out from Korea. Still waiting for the report back from them. Ducted airhandler airflow was never setup properly at this job. However, I feel that's not going to solve all the issues. We put surge/phase imbalance on the units and still loosing them. We never get any codes from unit prior to the CH21 once it shows a CH21 its mechanically failed.
      Biggest thing to cross off the list first is proper installation and piping along with proper nitro brazing. Obviously it can be hard to view some of the piping once its already installed.
      Other than that just recording the units and going over the data if you see crazy EEV readings or temps that don't make sense investigate. These units are becoming more common in my area seems like yours the last 20. Finding guys that are knowledgeable on this stuff is hard and the manuals only show you so much.

    • @HVAC544
      @HVAC544 Год назад

      @@JumpermanTech We have done 9 compressors and 2 four way valves at one site. We have a system down now but its still at minimum 1.5 days we usually get 2 full days incase of hiccups.

    • @rodgraff1782
      @rodgraff1782 Год назад

      @@JumpermanTech I would check the level of oil in the compressors coming out. I would also check the clarity of the oil, odor, and test for any acid. Flooded starts are the number one killer of compressors. Sounds like you have had multiple compressor failures on some of the units. I would check for proper installation or design problems, or possibly power problems at the site. I wish you luck. Are the compressors out of warranty now? Do you think the inverters are killing the compressors, or do the inverters fail due to grounded compressors? I don’t know much about these systems, but do know a lot about the cause of compressor failures. Those roasted compressor jackets look like their getting hot. Is this a common problem with other buildings? I use AEMC hand crank meggohmeters. I’ve got three. You can’t find them reasonable on eBay. They are industrial quality. Been using them for 25 years. They are analog, and don’t use a battery. Test voltages can be set for 250, 500, or 1000 volts. Also has a built in voltage tester. I don’t like ohmmeters that use 9 volt batteries. I usually test with twice the motor voltage. It will also read high, if there is any moisture or contamination in the system.

  • @arielhernandez2911
    @arielhernandez2911 Год назад +4

    Damn bro putting in that work mad late there and dark you work alll over nyc

    • @JumpermanTech
      @JumpermanTech  Год назад

      Definitely putting in that work right now. Let's get it 🔧⚡️ Thanks for watching!

  • @drewc7479
    @drewc7479 Год назад +2

    Hey man, watched your other vid too and I recently just picked up a LG vrf cleanroom at one of our sites . Just wondering where you got the info on for other checks on it like the other boards and how to check them?
    Lots of vrf lines and getting contracts on all them I wanna be able to actually check things before replacing a compressor and board. Thanks man

  • @josephderusso4594
    @josephderusso4594 Год назад +3

    We have a bunch of those lg garbage in nj ; compressors n board’s going bad also!! We had to keep compressors n boards in stock at sight; tech support sucks! Love ur videos brother keep them coming!!!!

  • @commenter5469
    @commenter5469 Год назад +5

    Liquid refrigerant migration can cause compressor to short out. Maybe even temporarily. That’s why compressors insulation resistance requirement are usually lower than other motors.
    It is usually important for the freezers and coolers - but you are still in a cold weather, you should check crank case heater, whether it’s even installed, and whether it’s still good. And if it’s bad - why board didn’t produce the fault code and didn’t shut down the machine.
    And if the compressor didn’t have heater installed from the beginning - someone who ordered this equipment did screwed up.

  • @jrh86
    @jrh86 Год назад

    Excellent tutorial on these LG units, the best.💯👍👍👍

  • @samuelsteffan6987
    @samuelsteffan6987 Год назад +2

    I work with VRV mainly. We have issues with compressors just like any VRF. Most of these issues stem from bleed by on indoor eev's. We've seen proper maintenance through the year greatly reduce bleeding by. With older models such as the lll's, we saw that autocharging prematurely set charges wrong. By doing routine maintenance on outdoor main eev's, you can see that they crack over time. Changing these out are very beneficial to said compressors. We've also had bad luck in past years with aluminum(rough lock) installs. With aluminum, leaks are almost always a certainty. Keep up the good work brother, love the channel.

    • @HVAC544
      @HVAC544 Год назад

      Is that just indoor unit eev's or even the ones in the heat recovery boxes? One of our compressors the scroll shattered almost like it slugged liquid. Was told the unit should catch it before that happens however in theory is not always the results in field.

    • @samuelsteffan6987
      @samuelsteffan6987 Год назад +1

      @asdasda z we've had eevs in the bs boxes flood. But, I believe that's more of a rarity. It does happen, but is rare. We've seen more and more indoor cassette eevs and outdoor eevs bleed.

    • @samuelsteffan6987
      @samuelsteffan6987 Год назад

      @asdasda z also, was the compressor on a VRV 3 or 4?

    • @HVAC544
      @HVAC544 Год назад

      @@samuelsteffan6987 Gen 5 LG unit. I know certain vrf brands and models all have their quirks. The safeties should catch flood back in cooling we have one unit throwing those codes right now.

    • @samuelsteffan6987
      @samuelsteffan6987 Год назад

      @@HVAC544 they all certainly have reasons for bleed by no doubt about that.

  • @johnwalker890
    @johnwalker890 Год назад +1

    Good job Jumper, That roof is scary, and the steps, be careful.

    • @JumpermanTech
      @JumpermanTech  Год назад

      Thank you John! I enjoy the view but not those steps. Those steps are kinda scary & a pain to go up/down all day. Stay tuned for new videos every week!

  • @nicolerennie
    @nicolerennie Год назад +1

    🤯😱 great video, these units are something else

  • @sergioramirez9025
    @sergioramirez9025 Год назад +1

    We're can I find that information. Like the pictures you showed to guide me on troubleshooting

  • @unlimitedmahdi1332
    @unlimitedmahdi1332 Год назад

    I saw a picture of the inverter board checking guide in the video. Where can I get this guide and is there a specific training course that teaches all this stuff?

  • @musakavalci9470
    @musakavalci9470 Год назад +2

    Those LG's are going keep you busy $$$
    Did technical support send you those troubleshooting docs ? Great video 👍🏼

    • @JumpermanTech
      @JumpermanTech  Год назад +1

      They will definitely keep me busy it seems. Another one went down today. That's 3 in 3 weeks😬 They did send me that. They have the better and most accurate troubleshooting docs. Thank you! Stay tuned for new videos every week 🔧⚡️

    • @JumpermanTech
      @JumpermanTech  Год назад +1

      Not a compressor related issue though 😅

  • @kennethlobo4420
    @kennethlobo4420 Год назад +3

    God Bless love ur videos

    • @JumpermanTech
      @JumpermanTech  Год назад

      Glad you love the videos! Stay tuned for new videos every week🔧⚡️

  • @mrbugenhagen3364
    @mrbugenhagen3364 Год назад +9

    Oh no 😰 2 out of 16. Better keep those plastic crates and an umbrella on standby.

    • @lewissaunders2837
      @lewissaunders2837 Год назад +3

      Standard bullshit kit we deal with in the UK unfortunately. Complete junk

    • @briancarlisi2224
      @briancarlisi2224 Год назад +1

      I think this is the 3rd failed LG unit on this roof…

    • @HVAC544
      @HVAC544 Год назад +1

      @@lewissaunders2837 That's good to hear these units have been giving us fits in the states.

    • @JumpermanTech
      @JumpermanTech  Год назад

      Haha that's a good one. Thanks for watching the first one! You'll like tomorrow's new videos then 😂 I might need more umbrellas soon

    • @JumpermanTech
      @JumpermanTech  Год назад

      ​@@lewissaunders2837🤦‍♂️🤦‍♂️🤦‍♂️

  • @stevenpollock6342
    @stevenpollock6342 Год назад

    Great view and video but have u thought about moving to florida ac units a lot easier to work on

  • @coldfinger459sub0
    @coldfinger459sub0 Год назад +3

    You are so lucky you get all the interesting jobs with burnt out compressors on LG units. In the last decade, I have never had an LG unit compressor failure. I must be doing something wrong..
    You should never use the Subco magger resistor Ohm tester on these inverter compressor’s . They will test out BAD often when they are not..

  • @joeshearer1247
    @joeshearer1247 Год назад

    You don’t have to take the wiring off the board when you were doing those checks?

  • @electroshed
    @electroshed Год назад

    The converter board is nothing more than a glorified bridge rectifier 3ph to DC board with a bank of capacitors to smooth the DC right out, also those two black square things I imagine are contactors - when you first apply power these should remain open while the capacitors are charged, slowly by some resistors, then after a few seconds, the contactors close to put the rectifier directly on line - without this, the inrush current to charge the capacitors would pop the breaker. If the breaker pops immediately on power up - check for welded /failed contactors on this board. Also the brown deposits on the boards look like flux from having things like the IGBT module replaced, I think you said these are refurbished but approved boards?

  • @2facefigures
    @2facefigures Год назад

    What app are you using??

  • @clentcliffordespera3892
    @clentcliffordespera3892 Год назад

    Hey jumper man tech i have question for you how many indoors unit in Multi V5 both slave and master

  • @mflettre6711
    @mflettre6711 Год назад

    How many hours does it take to check all of the boards?

  • @kleinerc.s7667
    @kleinerc.s7667 Год назад

    11:44 could it be that you need to change the thermal paste?

  • @zekenzy6486
    @zekenzy6486 Год назад

    Great Video. What is mean invert board , convert board ? Thank you for sharing

    • @STONEDay
      @STONEDay Год назад +2

      Inverters convert DC to AC. Inverting the polarity to form a sinusoidal AC waveform.

  • @thesilentonevictor
    @thesilentonevictor Год назад +1

    Good content jmt

  • @andrewmartinez5287
    @andrewmartinez5287 Год назад

    A trane vrf had us going in circles recently. First it was the inverter board then another board and then a leak. Not sure what happened but without a laptop, tech support, and proper training I decided to stay out of it and let my lead handle it

  • @paramboytv7378
    @paramboytv7378 Год назад

    where we can find the file of the image you are showing to us??

  • @shine-cg9uf
    @shine-cg9uf Год назад +1

    👍🇺🇸💪❄️

  • @xanmancan
    @xanmancan Год назад +1

    Bra just on the roof 😂😂😂😂

  • @abdullah_q8171
    @abdullah_q8171 Год назад +1

    Why always in vrf the compressor damage ?

  • @sharifakber5197
    @sharifakber5197 Год назад

    I m chillers repairing troubleshooting technicaion . I need a job vacancy at any place you have, please share me.

  • @lewissaunders2837
    @lewissaunders2837 Год назад +1

    My M500 has never been wrong

    • @JumpermanTech
      @JumpermanTech  Год назад

      I always liked that tool. So easy to use. I did just pick up a megohmmeter with an LCD display that gives you an actual number. Solid & for a good price. The Klein tools ET600. Someone in the comments recommended it

    • @JumpermanTech
      @JumpermanTech  Год назад

      Thanks for watching!

  • @vahyae
    @vahyae Год назад +1

    Gasoline

    • @JumpermanTech
      @JumpermanTech  Год назад +1

      Is overpriced, yes. Thanks for watching!

  • @JuanTodoli
    @JuanTodoli Год назад +1

    Another 😲

    • @JumpermanTech
      @JumpermanTech  Год назад

      Yup. 2 in 2 weeks. I just started working here 4 weeks ago! Looks like things are going to get fun

    • @JumpermanTech
      @JumpermanTech  Год назад

      Another unit went down today but for another reason 😬

    • @JumpermanTech
      @JumpermanTech  Год назад

      3 for 3

    • @JuanTodoli
      @JuanTodoli Год назад +1

      @@JumpermanTech We have here an UNUSUAL rate of inverter PCBs overcurrent issues, control PCBs burnt & shorted compressors.

    • @JumpermanTech
      @JumpermanTech  Год назад

      @JuanTodoli I've only dealt with these machines a handful of times here and it's the exact same issues you are experiencing. This happens alot according to the people that work there. These units have been a problem since the beginning. Wow. Any advice?