Paano mag Compute ng Magnetic Contactor Size | circuit breaker/fuse | size of wire- thermal overload

Поделиться
HTML-код
  • Опубликовано: 6 сен 2024
  • Computation for sizing of magnetic contactor, circuit breaker/fuse, size of conductor and overload relay setting for a motor controller in single phase and 3 phase power supply | Tagalog tutorial
    Thank you for watching guys!
    Please visit our Channel👇👇👇
    / @localelectricianph
    for more electrical installation and controls video tutorials.
    FB Page: Electricians Guide
    Direct message on our FB page for other questions. Thanks!!
    OTHER USEFUL VIDEOS 👇
    MANUAL OFF AUTO MOTOR CONTROL
    • MANUAL-OFF-AUTO Motor ...
    FLOAT SWITCH wiring and diagram
    • Float Switch wiring an...
    3GANG SWITCH wiring
    • 3 Gang Switch Wiring t...
    HOW TO USE MEGGER / insulation tester
    • HOW to use MEGGER Insu...
    3-WAY SWITCH Wiring Tutorial
    • 3 Way Switch - tagalog...
    WYE DELTA MOTOR CONTROL
    • WYE DELTA STARTER Wiri...
    Stop Start Wiring Control Circuit and Diagram
    • Stop Start Magnetic Co...
    FORWARD REVERSE STEP BY STEP
    • FORWARD REVERSE Motor ...
    On Delay Timer Wiring Diagram
    • ON Delay Timer Diagram...
    FLOATLESS RELAY WIRING
    • Floatless Relay Wiring...
    Stop Start with Overload Relay Connection
    • Magnetic Contactor Sto...
    • Overload Relay ( therm...
    OVERLOAD RELAY Function tutorials. tagalog
    OHMS LAW
    • OHMS LAW - Voltage Cur...
    24 HOUR TIMER FUNCTIONS
    • HOW TO SET 24 HOUR CLO...
    • Multimeter Paano guma...
    How to use MULTIMETER tagalog video
    STOP START w/ INDICATOR LAMP
    • STOP START w/ INDICATO...
    • HOW TO SPLICE A WIRE -...
    How to Splice a Wire video
    MAGNETIC CONTACTOR PARTS AND FUNCTIONS
    • Magnetic Contactor Par...
    VOLTAGE TESTER
    • VOLTAGE TESTER NEON SC...
    HOW TO COMPUTE ELECTRIC BILL
    • Electric Bill Computat...
    7 WAYS TO REDUCE ELECTRIC BILL
    • HOW TO LOWER ELECTRICI...
    POWER FORMULA
    • POWER CURRENT VOLTAGE ...
    HOUSE WIRING TUTORIAL
    • HOUSE WIRING TUTORIAL-...
    PHOTOCELL with Magnetic Contactor
    Wiring/Diagram-street lights
    • PHOTOCELL w/ Magnetic ...
    Magnetic Contactor VS Mechanical Relay
    Uses and Function
    • Magnetic Contactor VS ...
    SUBMETER INSTALLATION
    • SUBMETER INSTALLATION ...
    MECHANICAL RELAY WIRING
    • RELAY WIRING TUTORIAL ...
    Music:
    Tuff Data | Vans in Japan
    No Copyright claim.
    • Video

Комментарии • 214

  • @simpaticovlog4743
    @simpaticovlog4743 2 года назад +3

    Mag kaiba po ang FLC at FLA
    FLC po makikita sa table sa PEC yan po gagamitin sa pag kuha ng size of wire (FLC x 1.25)( FLC x 2.5) nmn po sa CB.FLA po gamit sa pag kuha ng OL FLA a makikita sa name plate of the motor

    • @LocalElectricianPH
      @LocalElectricianPH  2 года назад +1

      Salamat sa Inputs Sir 👍👍

    • @arindar4310
      @arindar4310 Год назад

      boss bkt po napansin ko maliit lng nag wire compara sa rating ng CB??

    • @LocalElectricianPH
      @LocalElectricianPH  Год назад

      Ito po sagot Sir. New video natin ruclips.net/video/icOiQXh6D3E/видео.html

    • @TeamArVes
      @TeamArVes Год назад +1

      @@LocalElectricianPH No offense sir Working naman sir yung computation nyo good job and it will work sa real situation pero base sa PEC FLC ang ginagamit sa computation sa Size ng Wire and inverse time CB

    • @LocalElectricianPH
      @LocalElectricianPH  Год назад +1

      @TeamArVes ues Sir FLC po talaga lalo pag planning and designing Sir kasi d pa ho kita ang actual nameplate ng motor..pero f meron napong nameplate Sir. Pwedi po mg refer sa nameplate. Since ito naman po ay tanggap internationally ay nka saad dn po sa PEC na internatinal standards may use

  • @moromagstv6295
    @moromagstv6295 3 года назад +1

    Napakalinaw ng computations thanknyou for sharing kapatid

  • @aveghellavandero4447
    @aveghellavandero4447 3 года назад +1

    Marami rin ako natutunan sa mga video nyo thank you sir

  • @gonfrics3157
    @gonfrics3157 3 года назад +1

    Thanks nang marami mAster...

  • @bobbymanerbandilla5110
    @bobbymanerbandilla5110 8 месяцев назад

    Salamat sir gets kuna

  • @felixalburo622
    @felixalburo622 2 года назад +1

    thank you sir

  • @jomarbelludo9704
    @jomarbelludo9704 3 года назад +1

    Salamat master

  • @jmtolentino6397
    @jmtolentino6397 10 месяцев назад +2

    yung FLA sa contactor ng main ng 3 phase na dinivide na sa 1.732 para makuha didivide mo ulit sa 1.732? (multiplied by 58% same as 1/1.732)

  • @dibgrol5759
    @dibgrol5759 Месяц назад

    Nice video very informative, base on motor nameplate aling voltage ang ggamitin pg compute, yung 230v or yung 380v? Sana masagut lodi Thanks

  • @junexcuarentas8519
    @junexcuarentas8519 2 года назад +1

    Salamat boss

  • @helcurtbulatao1625
    @helcurtbulatao1625 Год назад +1

    ayus yan boss

  • @mhelvinmanalo3140
    @mhelvinmanalo3140 3 года назад +1

    Sir,baka pwede gawa rin kayo ng tamang pag compute ng capacitor pag singe phase motor,ty

  • @genrosetvchannel6914
    @genrosetvchannel6914 3 года назад +1

    Sir suggestion lang Po dapat may PEC refference table po kayo para hindi po malilito ang mga beginers.

  • @johnwilliampolicarpio
    @johnwilliampolicarpio 3 года назад +2

    Correct me If im wrong db yung FLA ay karaniwan nasa nameplate nman sya at yung FLC naman nya nasa PEC book

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад

      Yes sir. FLA ay nasa name plate po ng motor at ang resulta ng actual test ng ibat ibang manufacturer sir.

  • @HariHari-jr5pg
    @HariHari-jr5pg 3 года назад +1

    ISATISFIED VERY MUUCH. THANK YOU .BUT GIVE THE DETAIL FOR DOL & ATS& RRS STARTERS.

  • @ryanraybusoy422
    @ryanraybusoy422 2 года назад +1

    Hi sir .. good tutorial.. hoping and praying na marami pa Po kayung matulongan....
    Tanong ko lang Po ..always Po ba .08 Ang power factor nag motor? Or nag depende Po sa electric motor?

  • @arnilbardelosa2451
    @arnilbardelosa2451 2 года назад +1

    FLA is being used for thermal overload computation, FLC you need to check the PEC for Cable and CB computation fyi..

  • @dayveaguilar8638
    @dayveaguilar8638 2 года назад +1

    Ung mga formula and computation mo sir Naka base yan sa Philippine electrical code thanks

    • @LocalElectricianPH
      @LocalElectricianPH  2 года назад

      Actual ratings at ohms law lang yan sir. Pero meron nka pin comment article sa PEC sir kung saan mo makikita ang standard flc rating.

  • @JoseLeslieMontecillo
    @JoseLeslieMontecillo Месяц назад +1

    Sir ano po reference natin at san po nang galing ang 58% for the main at delta contactor at 33% for the wye contactor? Thank you!

  • @ryanraybusoy422
    @ryanraybusoy422 2 года назад +1

    Hi sir good evening...
    Mabuhay Po kayu sana marami pa Po kayung ma eturo sa kagaya namin na nag sisimula....
    May tanong lang ako sir..dba Ang
    Answer nang 100% x FLA
    100% x 29.9
    Convert to decimal Ang 100%
    So .100 x 29.9 = 2.99
    Or 1.0 x 29.9? Yan Po ba?

    • @LocalElectricianPH
      @LocalElectricianPH  2 года назад

      Hindi Sir...100% ng 29.9 is 29.9 dn..wag nyo na po e convert kasicyun napo yon

    • @ryanraybusoy422
      @ryanraybusoy422 2 года назад +1

      @@LocalElectricianPH ahh ok ..salamat po ....Isa Po ako sa subscriber nyo Po.....
      Last question Po .san Po makikita ag amperes nang Isang magnetic contractor?

    • @LocalElectricianPH
      @LocalElectricianPH  2 года назад

      Nasa gilid meron yan nkalagay specs

    • @LocalElectricianPH
      @LocalElectricianPH  2 года назад

      Or sa box pag bibili ka

    • @ryanraybusoy422
      @ryanraybusoy422 2 года назад +1

      @@LocalElectricianPH ahh ok sir Akala ko may computation din....thanks Po godbless 🙏 more blessings Po..

  • @animedc9903
    @animedc9903 3 дня назад

    Sir tanong ko topic 3phase my nameplate motor naka lagay naman ampere mostly...FLA bayan nasa name plate?

  • @alterlaroza6503
    @alterlaroza6503 Год назад +1

    Good day sir, ilang amps po ng C.B. , magnetic contactor at overload relay po ang pwedeng gamitin sa 1 HP na motor? Thanks in advance po sir.

  • @xxsuperacerxx
    @xxsuperacerxx 3 года назад +2

    Sir tanong ko lang po saan po reference ninyo ng table po ninyo? Curios lang po sir

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад +2

      Yan po ay base sa actual formula Sir. Meron din pong standard FLC ratings sa PEC nasa article 4.30.14.2 up to 4

  • @markjoeydavid7992
    @markjoeydavid7992 3 года назад +1

    Sir question lang po. Bale po sa unang part ng presentation nyo po, ang computed wire/conductor size is 8.0 na nasa 40 - 50amps rating tapos po ang computed fuse/cb ay nasa 70 plus. Okay lang po ba na undesize ang wire?

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад

      Ang conductor sizing po kasi sir ay 125% ng full load current. Samantala ang cb o fuse po ay ng range ng 170% to 300%

  • @helcurtbulatao1625
    @helcurtbulatao1625 Год назад +1

    mejo nguluhan ako sa equation nkbraket ung devisor

  • @jumelnonod6849
    @jumelnonod6849 2 года назад +1

    Master tanung q lang po..may control po ung motor namin ng isang start stop n panel..saka isang wye delta n panel..saan po kabilang un sa delay po ba o non delay or sa CB?

    • @LocalElectricianPH
      @LocalElectricianPH  2 года назад

      Y8ng wye delta po sir ang may delay. Sa transistion from wye to delta. Nasa 2 to 4 sec difference

  • @jameszamora2499
    @jameszamora2499 Год назад +1

    Sir question lang po.
    Saan po magbabase ng full load current kapag may Service Factor(SF) po na 1.15 sa nameplate ng motor (Computation po for Circuit Breaker)
    Ex:
    At 15 hp, 230 V, 3 phase motor
    IFL= 41.6 A
    IFL with SF = 47.84 A
    Alin po gamitin ko sa kanila sa pag multiply po ng 250%?
    Thank you in advance, Sir. ⚡

    • @LocalElectricianPH
      @LocalElectricianPH  Год назад

      42A po ang flc ng 15hp base sa PEC Sir. ..so pasok jan ang nasa nameplate na 41.6A

  • @wildfangs-tv8637
    @wildfangs-tv8637 4 месяца назад

    naiba na master explanation mo 3years after netong video mo about sa wye delta connection,naging Overload relay setting= FLA x 125%(maximum) or 115%(minimum)

    • @LocalElectricianPH
      @LocalElectricianPH  4 месяца назад

      125% to 140% payan Sir max dependi sa load and sa minimum naman kahit up to 70% basta di lng mg trip ang pwedi naman po...

  • @jasperlacap3481
    @jasperlacap3481 2 года назад +1

    Sir...
    Yung overload relay po ba ng 3 phase motor is Min(70%) and Max(125%) parin po ba ng Main Contactor na 58% of FLA?
    Example :
    19.01 yung FLA so ang Main contactor is 11A dahil 58% lang sya ng FLA.
    Mag babase po ba yung Min70% and Max125% ng Overload relay sa 19.01A or sa 11A?
    Salamat po.

  • @gearupracing5588
    @gearupracing5588 3 года назад +1

    Boss ano po amp pwede gamitin na contactor sa 10hp motor phase converter at ilang mfd na capacitor po gagamitin. Salamat

  • @junexcuarentas8519
    @junexcuarentas8519 2 года назад +1

    Sir paanu malaman ang tamang overload para sa isang motor example po sir.fla ng motor ay 3.58.

  • @lofttakobetv1018
    @lofttakobetv1018 2 года назад +1

    Paturo naman mag wiring ng wixim mc with ol para sa float switch.. mahirap Kasi sundan wiring mo dun sa isang video using fuji mc

  • @kilogrammountain3453
    @kilogrammountain3453 3 года назад +1

    Boss tanung lang po halimbawa may gagawin ako start stop DOL tapos gusto ko sya lgyan ng breaker para maging safe yung mga contactor coil mga ilang amps po ang kailangan na breaker para sa control at panu po malalan kung ilan yung amp ng isang contacto coil

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад

      Hindi po kasi given ang amperahe sa coil kung gusto nyo po malaman. Pwedi nyo po sukatin amperahe ng controls nyo sir. Gamit ang clampmeter tpus jan napo kau mg base ng breaker size

    • @kilogrammountain3453
      @kilogrammountain3453 3 года назад +1

      @@LocalElectricianPH ah ok posir slamat sa idea

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад

      Welcome po

  • @Creator-ux9uf
    @Creator-ux9uf 3 года назад +2

    san mo kinuha ang 167 boss?

  • @karmich8648
    @karmich8648 Год назад +1

    Sir panu b malalaman yong isang device kung motor load kpag b may horsepower yon yong babasihan para malaman kung motor load

    • @LocalElectricianPH
      @LocalElectricianPH  Год назад

      Yes po..sa hp po tayo mag base f anong size ng wirr gagamitin..at amperahe na kailangan para sa contactors at breakers po

    • @karmich8648
      @karmich8648 Год назад

      Kpag may horse power ibig sabihin motorload sya.. Salamats po..

    • @LocalElectricianPH
      @LocalElectricianPH  Год назад

      @karmich8648 Sir..horsepower or watts or kilowatts same lang naman po yan Sir..unit ng Power parin yan..1 hp is 746 watts...1 kw is 1000 watts

  • @HariHari-jr5pg
    @HariHari-jr5pg 3 года назад +1

    MAGNETIC CONTACTOR SIZING FOR DOL AND ATS STARTERS

  • @senpaikai278
    @senpaikai278 3 года назад +1

    Master, okay lng ba 7kw booster pump, gamitan ko ng magnetic relay 10A for interlocking controls bukod pa po yung magnetic contactor.

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад

      3 phase po ba? Maliit yan sir

    • @senpaikai278
      @senpaikai278 3 года назад +1

      @@LocalElectricianPH opo master 3phase 220v 19.8FLA booster pump, bale alternate yung dalawang booster pump. Kailangan kasi ng relay for interlocking, mga ilang ampere po ba ng relay ang kailangan?

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад +1

      Ahh ok po..kaya n nyan 10 amps for interlocking sir.

    • @senpaikai278
      @senpaikai278 3 года назад +1

      @@LocalElectricianPH sige master maraming salamat po

    • @senpaikai278
      @senpaikai278 3 года назад +1

      Akala ko kasi if anong rating ng magnetic contactor eh ganun din sa magnetic relay.

  • @aveghellavandero4447
    @aveghellavandero4447 3 года назад +1

    Yan din poh ba ang formula sa multiple motor example sa ricemill

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад +1

      Yes sir f individual..pero f multiple tapus my main breaker kayu. Iba po computation ng main feeder

    • @aveghellavandero4447
      @aveghellavandero4447 3 года назад +1

      Pwedi poh maggawa poh kau video kasi sa ricemill may 2 main breaker ung 1st breaker malaki ung 2 breaker ma's maliit NG kaunti. All motor nasa 300hp kung minsan lahat lahat ang hp NG mga motor

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад +1

      Anong control po gamit nyo sir. Soft starter?

  • @engr.mathik1392
    @engr.mathik1392 2 года назад +1

    Sana may reference kayo sa PEC.

  • @eugeniogozon7440
    @eugeniogozon7440 7 месяцев назад

    Sir, deep well water pump motor, 1/2hp 1-phase , SF 1.6 , SFA 5.3 at 230V. Paano malaman ang FLA?

    • @LocalElectricianPH
      @LocalElectricianPH  7 месяцев назад

      Pwedi nyo po w base sa nameplate or base sa PEC table po

    • @eugeniogozon7440
      @eugeniogozon7440 7 месяцев назад

      May link po ba kayo sa PEC table? Walang FLA sa nameplate.

    • @LocalElectricianPH
      @LocalElectricianPH  7 месяцев назад

      @eugeniogozon7440 pm po sa fb page sir

  • @bobbymanerbandilla5110
    @bobbymanerbandilla5110 8 месяцев назад +1

    Sir San Po b yang 8.0 para sa Fedder Po b Yan o papunta sa load

  • @benjohntombado4960
    @benjohntombado4960 10 месяцев назад +1

    Pano naman sir pag compute ng required current rating ng time delay relay?

    • @LocalElectricianPH
      @LocalElectricianPH  10 месяцев назад

      Time delay fuse po yata nasa video Sir...para saan po gagamitin ang time delay relay?

    • @benjohntombado4960
      @benjohntombado4960 9 месяцев назад

      @@LocalElectricianPH on delay ng automatic pump motor after blackout sir

    • @LocalElectricianPH
      @LocalElectricianPH  9 месяцев назад +1

      @benjohntombado4960 controls lng naman po ang time delay Sir..as is napo ang computation sa motor power coonections and supply..meron ako video sa channel playlist about time delay controller sir pki visit lng po

    • @benjohntombado4960
      @benjohntombado4960 9 месяцев назад +1

      @@LocalElectricianPH bale pag sa control circuit yung aux. contacts nya di sya affected ng FLA ng motor?

    • @LocalElectricianPH
      @LocalElectricianPH  9 месяцев назад +1

      @benjohntombado4960 di po..power circuit lng ang apectado ng FLA n syang recta ng switch ng motor..ang control ckt mga coil ng contactor at relay at indicator lamps lng load nyan

  • @kalikotpangmasa301
    @kalikotpangmasa301 4 месяца назад +1

    Ano Po Ang gagamitin na magnetic contactor (ampheres)sa walong ilaw na halogen 4,000watts Ang isa

  • @jhonemmirabuenos1490
    @jhonemmirabuenos1490 Год назад +1

    Paano po e compute ang wire size ng auxilliary contact?

  • @dynamokingtv6144
    @dynamokingtv6144 Год назад +1

    Boss magandang araw, ang 2hp 230v single phase 9.4amps, max load 12.9amps na waterpump boss ano kaya pwede gamitin na ampere ng contactor at overload, di kase ako marunong mag compute..

  • @bobbymanerbandilla5110
    @bobbymanerbandilla5110 8 месяцев назад +1

    Sir sa nkuha Yung 167

  • @zaldybuenaobra1781
    @zaldybuenaobra1781 2 года назад +2

    Idol tanong ko lng po saan po b gling Yung 167?

  • @guitarone71
    @guitarone71 3 года назад +1

    Sa single phase section sir 8.0mm ang wire which is 40ampacity pero sa CB is 80Ampere. Ok lang ba yun sir undersize ang wire na 8.0mm sa 80amp breaker?

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад +1

      Delicado yan sa sunog sir. Dapat po match

    • @guitarone71
      @guitarone71 3 года назад +1

      @@LocalElectricianPH Ah so lahat ng computation ang wire size sa motor control naka match lang sa CB tama ba sir?

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад

      Match sa wire. cb. at full load current ng motor sir

    • @guitarone71
      @guitarone71 3 года назад +1

      @@LocalElectricianPH Ok sir mali lang ako pagkakaintindi sa video. maraming salamat

    • @humbeym9069
      @humbeym9069 2 года назад +1

      @@guitarone71 tama ka po sir, okey lang po na #8 ang wire mo at 80amps ang breaker kase nga kaya mataas ang breaker para hindi mag trip kase may starting current tapos after ilang seconds mag nonormal na ang current kaya kayang ihandle ng #8 na wire ang running current

  • @jovindejesus8076
    @jovindejesus8076 Год назад +1

    Saan po nakuha Yun 499.6 n sagot?

  • @jeromecarullo66
    @jeromecarullo66 Год назад +1

    Baliktad computation mo sa nontime and time delay fuse.

  • @kentlybaguin.eteeap7434
    @kentlybaguin.eteeap7434 3 года назад +1

    Sir sa Sizing ng Conductor diba FLC Dapat as per NEC 430,22

  • @leonardoso4301
    @leonardoso4301 2 года назад +1

    Sir San po nakuha ang 167? 220/167? And .8 and 95%... ty

  • @ricafordvestidas3709
    @ricafordvestidas3709 Год назад +1

    Ask lg sir nka depende pla sir ang size nang breaker protection sa type nang breaker.ask lg sir ang miniature circuit breaker po ilang percent po sya at saan sa na belong sa time delay,non time delay or normal cb lg ba?salamat sir sana matugunan mo.😊

    • @LocalElectricianPH
      @LocalElectricianPH  Год назад

      Miniature cb at cb ay same lng yan Sir 250% pinagkaiba lng ng miniature ay hqnggang 100A png pinaka mataas nyan..

    • @mecoulyssescumpio9145
      @mecoulyssescumpio9145 Год назад +1

      Mayron Ng 125A mcb Po sir

    • @LocalElectricianPH
      @LocalElectricianPH  Год назад

      100A lng po max ng mcb

    • @ricafordvestidas3709
      @ricafordvestidas3709 Год назад +1

      ​@@LocalElectricianPHsir ask lg po about wye delta starter ang pag sizzing nang breaker nya same D.O.L parin ba applications sir?thank you po sa pagsagot sir.

    • @LocalElectricianPH
      @LocalElectricianPH  Год назад

      Hindi po..3 phase kc wye delta. Kalimitan sa dol 1 ph

  • @busraahmed1708
    @busraahmed1708 2 года назад +1

    please english subtitle

  • @janjanboquia6738
    @janjanboquia6738 3 года назад +1

    Sir pano po mag determine ng wire size na gagamitin sa control circuit.,? Ano po formula?

  • @hatchiretchi1955
    @hatchiretchi1955 3 года назад +1

    idol pwede po patulong, ilang ampere po ba yung magnetic contactor para sa 2hp na motor? Paano po e calculate yun master? At pwede po oa example idol Salamat po 🙏

  • @mikelife714
    @mikelife714 3 года назад +1

    master plano ko mag run ng 50 units 3000w each kakayanin ba ng residential to? any tips

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад

      Yes sir. Gamit lng po kau ng magnetic contactor na higher sa 3000 w ang capacity sir

    • @mikelife714
      @mikelife714 3 года назад +1

      @@LocalElectricianPH kahit ilang unit po sir? bale sa 50 units po sir, gamit lang po ako ng tigiisang magnetic contactor na may 3000w capacity? di naman po 3000w yung unit exacto nasa 2600w lang po

    • @mikelife714
      @mikelife714 3 года назад +1

      kaya po yung nung entrance wiring from post to metro kahit ilang unit sir?

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад

      Pwedi naman po sir kaso napaka laking load po nyan. Kailangan nyo po mag palit ng service entrance conductor. Mas mainam po ipa compute nyo lng po sa regìstered electrical engineer sir para sure at safe sir

    • @LocalElectricianPH
      @LocalElectricianPH  3 года назад

      Hindi sir number 8 lng po yan sa minimum residential service entrance up to 32 amps lng po kaya nyan..yong sinasabi nyo sir ay aabot yun ng up to 652 amps

  • @btmachinist6085
    @btmachinist6085 3 года назад +1

    Sir ano po size ng contactor saka thermal relay para sa motor na 2.2kw

  • @paulosalenga34
    @paulosalenga34 2 года назад +1

    Panu po kunin ung efficiency.?

    • @LocalElectricianPH
      @LocalElectricianPH  2 года назад

      Output/inputx100

    • @paulosalenga34
      @paulosalenga34 2 года назад +1

      @@LocalElectricianPH saan nman po mkikita ung input output.?

    • @LocalElectricianPH
      @LocalElectricianPH  2 года назад

      Power po in watts..nasa name plate ng motor. Convert hp to watts

    • @paulosalenga34
      @paulosalenga34 2 года назад +1

      @@LocalElectricianPH salamat po kita ko na po..😊

    • @paulosalenga34
      @paulosalenga34 2 года назад

      Ang hp ng motor ko ay 30hp ang kw po kw po ay 22 ang nkuha ko pong efficiency ay 1017 tama po ba.?

  • @shadshad2851
    @shadshad2851 Год назад +1

    paano nakuha ang 499.62 sa 3phase kasi compute ko mali man dimo kasi sinasabi kung paano nakuha

  • @jeffersonacosta6030
    @jeffersonacosta6030 2 года назад +1

    sir Hindi ko gets San galing Ang 499.62 sir sa 3phase

  • @bryanblanks8042
    @bryanblanks8042 2 года назад +1

    AyOs.

  • @jhunanario6075
    @jhunanario6075 2 года назад +1

    Sir sorry paano naging 167 ang sagot

  • @jonathantalirongan3830
    @jonathantalirongan3830 3 года назад +1

    Boss saan kinuha ang 167?

  • @bambi7872
    @bambi7872 Год назад

    Anong nangyari Dyan 14 amp lang Ang gagamitin na contactor sa 10 HP na motor sunog Yan gaya Ng sa air compressor 10 HP Ang nakakabit 35 amp...paki sagot po

  • @joristylegaspi9413
    @joristylegaspi9413 3 года назад +1

    San galing yung 167 sir

  • @jessiejalimbawa9966
    @jessiejalimbawa9966 10 месяцев назад

    I=5000/220v*.8*.95 = 17.5 po lumalabas sken bakit po ganun

  • @Korn-7005
    @Korn-7005 2 года назад +1

    Sir mali po yung sequence ng computation nyo ng FLA...i-apply nyo po yung PEMDAS iba po yung magiging resulta ng sagot...salamat😊

    • @LocalElectricianPH
      @LocalElectricianPH  2 года назад

      Salamat lods.

    • @rhadcliff5556
      @rhadcliff5556 2 года назад +1

      Parang wala namang mali.

    • @Korn-7005
      @Korn-7005 2 года назад +1

      @@rhadcliff5556 sir pansinin mo yung ginamit n symbol ( / ) slash represent division pr P/V dapat (----) fraction n symbol pr P
      _______
      V x pfxn

    • @Korn-7005
      @Korn-7005 2 года назад +1

      Dahil kung PEMDAS yung i-aapply natin una mong idi-divide yung P/V kasunod yung multiplication

    • @Korn-7005
      @Korn-7005 2 года назад +1

      Dahil yung division ay ns left side

  • @jessiejalimbawa9966
    @jessiejalimbawa9966 10 месяцев назад

    hindi po lumalabas 167