Sir, what is the problem of forming ice in indoor unit? Service person 2 times changed my ac gas but still im facing the same issue..can you please share the fix.
Good explanation sir.. I am using LG 1.5ton ac.. Found ice is forming in suction pipe (small pipe) of outdoor unit.. Technician check pani pathutu Condesor change pananum nu solra ru for 4500 around.. But outdoor fan is running.. But gas fill pana again 2/3 days same pblm varum nu solraru. Pls advise me sir..
Bro one doubt.gas suction line la crct ah iruku.but discharge line la konjam kammiyaa iruku.ipdi irukurapoo epdi discharge side gas charge panrathu.because discharge side la liquid apply panna mudiyathu.any other method for gas charging in discharge side
Bro discharge lay gas add panna mudiyadhu and koodadhu Discharge pressure romba adigama irukum gas eradhu and romba danger andha activity panradhu dont try this please Only suction side Dan pannanum
Sir I'm using Samsung 1 ton split Ac stabilizer on pannathum outdoor unit start ayiduthu Ac on pannalana ice form aguthu both pipes la Ac on pannathum ice lam melt ayiduthu but outdoor unit continues ah run ayitey irruku stop agama all temperatures LA Enna pannalam Pls help me
Sir, I have an Hitachi ac. Now am having a problem of ice forming in the big pipe only during night. During day it is working fine and it cools really well. But during night this ice forming problem occurs. AC was recently serviced and cleaned. Can I have your advice pls.
@@lohisya_media it is a 2ton ac and the temperature I maintain is 23. Earlier I used to maintain 16 also but no such issues faced. Another fact is this ac is close to 10 years old.
@@yogeshbala sensor problem, because once 23 below reached in room temperature automatically compressor is cut off. So in this case sensor is not working compressor running continuously. In night time indoor unit is running reaches very cooling , so suction line of outdoor unit is formed in ice.
What is the Refrigerant gas inside 410 A or R 32 If R410 means suction 120 psi and discharge 400 psi range irukanum illana onnu gas ilama irukanum other wise compressor odama irukanum
I have change the gas 2 to 3 times but again the same problem occurred if technician will check and they told same reason gas league but finally the issue again again occurred. This kind of situation what we do?
ஹாய் சார் என்னுடைய சாம்சங் இன்வெர்ட்டர் ஏசியில் 24 டிகிரி டெம்பரேச்சர் வைக்கும் போது அவுட்டோர் யூனிட் கட் ஆஃப் ஆகாமல் தொடர்ந்து ஓடிக்கொண்டே இருக்கிறது என்ன பிராப்ளம் ஆனால் 26 டிகிரி டெம்பரேச்சர் வைக்கும் போது கட் ஆப் வேலை செய்கிறது எனக்கு விளக்கம் தெரியப்படுத்தவும் ப்ளீஸ் சார்
My AC was running fine since I had bought it in 2017. In 2019, the copper connection pipe of my AC was stolen by petty thieves resulting in gas loss. Since then this icing issue has crept with the new pipes. After every 3 to 6 months gas charging is required.
Ji,the discharge pipe as a ice formation the mechanic,removed both the indoor and outdoir to check any leak.then he said leak is in the indoor and he welded. After one day again there is cooling issue is n the room.again there is an ice formation in the discharge,kindly help me on the exact issue.
Bro in discharge line ice issue is gas low issue Mechanic has done good job or not please call a other mechanic and check the gas pressure once u confirmed gas low call the previous mechanic to solve the issue
@@lohisya_media bro first of all to ask you ,whether are you ac mechanic(kindly don't mistake on the word I used are you an ac mechanic),secondly this is my first time on subscribing ,thirdly the person who as done the indoor welding said ,after fixing the indoor and outdoor the compressor is not working.i was shocked and asked asked on the issue he said the complaint was in the indoor not outdoor,but now he says the compressor is not working.
@@lohisya_media I again called the another mechanic saying the issue like compressor not working,he as done another way to make the compressor work and filled the gas.i hoped the problem as been solved .But the rite next day cooling as been reduced,I called the same mechanic checking for the issue he says the first mechanic would have welded properly,each of them blaming eachother,I am fedup,don't know what to do.Again the second mechanic says to change indoor unit.i really don't know were is the issue.😖😞😞
Sir ice formation in outdoor suction pipe and ice in indoor coil during night only , not in day time . Check gas and did water service for indoor but still ice formation . What is the reason ?
Sir,
Good Explain, Easy to Understand . Thank u.
Super Anna a/c மெக்கானிக் padikkuren anna Nalla purijjathu 😘😘😘😘👍👍👍👍
Thank you bro. it's very very useful for me.
Super bro, thanks for your information, I have the issue in my ac with discharge line, because the thin copper pipe is frozen in our ac...
Good explanation, thank you.
Super bro crystal clear explanation
Sir, what is the problem of forming ice in indoor unit? Service person 2 times changed my ac gas but still im facing the same issue..can you please share the fix.
Mikka mukka Nandri. Useful info
is this small line compreesor distarge line or evaporation coil refrigerant flow line?
Pump down pannum bodhu compressor blast aaga chances irukka?
Sir incase return sensor if is not working then also ice forming it will happen right
sir i have one doubt in this video you said that discharge side gas flow should be high pressure and temperature could you please explain sir?
Good explanation sir.. I am using LG 1.5ton ac.. Found ice is forming in suction pipe (small pipe) of outdoor unit.. Technician check pani pathutu Condesor change pananum nu solra ru for 4500 around.. But outdoor fan is running.. But gas fill pana again 2/3 days same pblm varum nu solraru. Pls advise me sir..
After serving my ac water droplets from indoor unit. Can u tell me what I do.
Bro suction pipe ice forming aguthu, indoor cline pani potta one week nalla eruku after one week marubadiyam ice forming aguthu Ena panalam bro
For I got new Panasonic AC, after 5 days AC is not Cooling.
Ice is farming in discharge pipe.
Yena issue ah irukum.. ?
Thanks bro very useful
Very good explanation
Bro both pipe ice formation aguthu bro enna problem??
Bro u very good thx for videos.....plz explain ac refil meter
Super....i understood
Super super very very beautiful sir
Super thaliva...
Super thelivana speach
Big pipela ice form aaguthu bro ethanala ethana problem varuma bro
Enaku tavoot bro discharge line and suction line two line num ice faming erunthal enna problem
How much gas need for 1.5ton split ac
Super g explanation good
In our out door unit in suction and discharge lines water droplets are dropping near the valves but no ice forming, is it normal or not. Pls. Reply
It's normal
Good explanation
Very useful bro
Excellent 👍👍👍
Bro one doubt.gas suction line la crct ah iruku.but discharge line la konjam kammiyaa iruku.ipdi irukurapoo epdi discharge side gas charge panrathu.because discharge side la liquid apply panna mudiyathu.any other method for gas charging in discharge side
Bro discharge lay gas add panna mudiyadhu and koodadhu
Discharge pressure romba adigama irukum gas eradhu and romba danger andha activity panradhu dont try this please
Only suction side Dan pannanum
🙏👍குட் ஐடியா நன்றி
Thanks brother
Sir ac 16 la vacha ice kattumaa
Good information
Supper sir thanks
Thank sir
For your support
Room Ton calculation updated me..
Maximum evalo pressure gas ⛽ erukkalam sir
Important subject sir
Super explaint
Sir indoor unit water spray but out door unit ice form illa 10 or 15 minutes water spray
சூப்பர் சார்
Thanks bro
Bro.. How to clear the evaporator coil choke in tower ac
Can a off state ac leak water inside
2 pipe m ice kattuthuna enna problem sir....but gas irukku
Both the lines have formed with ice..what's the issue ?
Anna mi village ekkada okasari nitho konni doubts unnay matladali
Thankyou. Sir
Could you please explain how to solve dust forming issue. We used split AC . Inside room huge dust formed every day
Clean the room everyday...
Thank u sir
Sir
I'm using Samsung 1 ton split Ac stabilizer on pannathum outdoor unit start ayiduthu Ac on pannalana ice form aguthu both pipes la Ac on pannathum ice lam melt ayiduthu but outdoor unit continues ah run ayitey irruku stop agama all temperatures LA Enna pannalam Pls help me
Sensor problem
Sir secution line lice farming. In door already clean &blower working good. But ice forming how to find it ?
Pls check pressure....
Thanks anna❤
Pro enkku split AC la capasitter poiruchu athu eppudi sollu ga
Tq Sir
Sir indoorla evaporated coil la ice aadhikama foam akudhu. What prabulm. Sir.
It’s sensor problems
Sir, I have an Hitachi ac. Now am having a problem of ice forming in the big pipe only during night. During day it is working fine and it cools really well. But during night this ice forming problem occurs. AC was recently serviced and cleaned. Can I have your advice pls.
Will you please tell me wat temperature you are maintain in room and what is the tonnage of your AC
@@lohisya_media it is a 2ton ac and the temperature I maintain is 23. Earlier I used to maintain 16 also but no such issues faced. Another fact is this ac is close to 10 years old.
@@yogeshbala sensor problem, because once 23 below reached in room temperature automatically compressor is cut off. So in this case sensor is not working compressor running continuously. In night time indoor unit is running reaches very cooling , so suction line of outdoor unit is formed in ice.
Chilled brine ice forming sollunga bro
Super bro
Nicely Explained Bro. Keep it up 👍👍
How to remove clogged pipes of split air conditioner panels, please type for me Omid from Iran
Brother . My outdoor unit both small and big pipe has water on it .But no ICE . What does it mean ??
It’s no problems. Running good. Keep the insulation properly covered the copper pipes in atmosphere.
Sir Drain line Block Akividdalum An sir ice pidikkuthu
Super anna
Floor stand lg ac 4 ton section 160, discharge 150 no cooling ena problem eppadi saripandrathu
What is the Refrigerant gas inside 410 A or R 32
If R410 means suction 120 psi and discharge 400 psi range irukanum illana onnu gas ilama irukanum other wise compressor odama irukanum
சார் அவுட்டோர் யூனிட் இரண்டு பைப் லைனிலும் தண்ணீர் துளிகள் வெளியேறுகிறது. இது நார்மல் தானா.ஐஸ் கட்ட வில்லை..
It's normal bro
Super sir my ac fully cleaned and gas filling after 1 week ice formed in discharge line and inner unit coil whats the oroblem sir pl solution
gas leak welding paaunam indoor coil
Sir please tell the wiring connection about Split Ac
Sir ac room how to masher ptu
Thx sir
Pro vrv mechinea no pannanum athu eppudi sollu ga pro
Sir எங்கள் வீட்டில் indoor laகொஞ்சம் ice form achu , அப்புறம் தண்ணீர் ஒழுகியது என்ன பிரச்சனை சொல்லுங்கள்
So many reasons
Enga veettilum
I have change the gas 2 to 3 times but again the same problem occurred if technician will check and they told same reason gas league but finally the issue again again occurred. This kind of situation what we do?
Gas leakage issue has to check with Soap water and pressure test who is the technician
Actually a good technique will find where is the leak without knowing the leak technician cannot fill the gas
Sir window AC la 2 copper pipe freeze aguthu what may be the problem no cooling
Already explained in video
Bro randulaium ice pudikudhu apo enna problem Bro
Super. Sir
Bro explain the malti split AC function
ஹாய் சார் என்னுடைய சாம்சங் இன்வெர்ட்டர் ஏசியில் 24 டிகிரி டெம்பரேச்சர் வைக்கும் போது அவுட்டோர் யூனிட் கட் ஆஃப் ஆகாமல் தொடர்ந்து ஓடிக்கொண்டே இருக்கிறது என்ன பிராப்ளம் ஆனால் 26 டிகிரி டெம்பரேச்சர் வைக்கும் போது கட் ஆப் வேலை செய்கிறது எனக்கு விளக்கம் தெரியப்படுத்தவும் ப்ளீஸ் சார்
Check Indoor temperature sensor. If faulty replace.
நியாந்தானே
Bro help me on my issue.
Anna suction and discharge line rendume ice form aagudhu
Bro VRF outdoor pathi videos podunga pls
Indoor coil sotting related video podunga brother
Suber bro
Anna outdoor unit la water leakage aguthu so good or bad....
No issues bro suction line ah
@@lohisya_media ila anna outdoor ku base la small holes iruku athula than varuthu line la water leakage ila anna
My AC was running fine since I had bought it in 2017. In 2019, the copper connection pipe of my AC was stolen by petty thieves resulting in gas loss. Since then this icing issue has crept with the new pipes. After every 3 to 6 months gas charging is required.
gas welding pannum leak prabalam bro
Purge unit process paththi sollunga bro
Indorelea ice form aguthu ethanalea
Super
👍
big pipe ice formation leads to blast?
No
@@lohisya_media THANK YOU FOR IMMEDIATE REPLY
AND WHAT TO DO FOR YEAR FACING THIS PROBLEM
AND WHAT WILL B CHARGE FOR THIS PROBLEM
Ji,the discharge pipe as a ice formation the mechanic,removed both the indoor and outdoir to check any leak.then he said leak is in the indoor and he welded. After one day again there is cooling issue is n the room.again there is an ice formation in the discharge,kindly help me on the exact issue.
I don't know whether the mechanic as solved the issue,kindly help me on the issue.
Bro in discharge line ice issue is gas low issue
Mechanic has done good job or not please call a other mechanic and check the gas pressure once u confirmed gas low call the previous mechanic to solve the issue
I think some other area gas may be leak
After welding pressure test has done or not please tell
@@lohisya_media bro first of all to ask you ,whether are you ac mechanic(kindly don't mistake on the word I used are you an ac mechanic),secondly this is my first time on subscribing ,thirdly the person who as done the indoor welding said ,after fixing the indoor and outdoor the compressor is not working.i was shocked and asked asked on the issue he said the complaint was in the indoor not outdoor,but now he says the compressor is not working.
@@lohisya_media I again called the another mechanic saying the issue like compressor not working,he as done another way to make the compressor work and filled the gas.i hoped the problem as been solved .But the rite next day cooling as been reduced,I called the same mechanic checking for the issue he says the first mechanic would have welded properly,each of them blaming eachother,I am fedup,don't know what to do.Again the second mechanic says to change indoor unit.i really don't know were is the issue.😖😞😞
Bro automatic gas vacuum pokkuth
pleace more troubleshoot videos update sir
Sir ice formation in outdoor suction pipe and ice in indoor coil during night only , not in day time . Check gas and did water service for indoor but still ice formation . What is the reason ?
I have same issue how to clear that problem.
@@selvaganapathy4524 what brand ac ?
@@selvaganapathy4524 sensor problem
👍🏿
Today my office room air conditionerle ithe problem irunthathu evaporator fullaa clean. Pannaange ac technician
Evaporator na edhu bro
Evaporator edhu bro
@@abbastom1176 indoor ula coil than athu
Two line also ice formation anna