LINE TO GROUND TWO 2 POLE BREAKER JUMPER WIRE - HIWALAY ANG ILAW AT OUTLET SA ISANG BREAKER EP 11.1

Поделиться
HTML-код
  • Опубликовано: 26 ноя 2024

Комментарии • 94

  • @practicalelectrical3837
    @practicalelectrical3837  3 года назад +4

    Sa paggamit ng panelboard or ECB, make sure na ang ampacity ng grounded conductor (neutral) ay pasok sa load na kailangan.

  • @Mr.Alberttv
    @Mr.Alberttv Год назад +1

    Napaka informative Ng MGA video nyo ser. AKO hirap AKO explain SA tutorial ko Yan. Congratulation po 👏👏👏👏

  • @EngrAimTV
    @EngrAimTV 3 года назад +3

    walang butas na presentation, always backed up by PEC... really admired your video presentation sir! ang galing...

  • @kurtsalgados2815
    @kurtsalgados2815 6 месяцев назад

    1:05 Legit yung aklat na yan😊 dami kong natutunan mula pa nung nag aaral ako ng E.I.M...😊😊😊😊

  • @practicalelectrical3837
    @practicalelectrical3837  3 года назад +4

    0:00 - Intro
    0:48 - Fajardo Book Recommendation
    1:38 - Number of Breakers per Service Entrance
    2:23 - 2 Pole Breaker para sa ilaw at outlet
    3:48 - NEC Handbook diagram
    4:15 - Double tapping sa breaker
    6:23 - Koten Breaker 2 Pole
    7:04 - Approval ng Electrical inspector
    8:50 - PEC violation
    10:53 - IEC breaker
    15:58 - Double tapping Schneider
    16:57 - Double tapping ABB
    17:41 - Splicing sa Service Entrance conductors
    20:52 - Workmanship ng splicing
    21:26 - Bakit sabi ng mga Beterano...

  • @jonacholo8908
    @jonacholo8908 Год назад

    Perfect ang presentations Sir. Sobrang detailed w/ reference talaga. Ito ang tunay na practitioner. 👏👏👏👏

  • @UnitFerminBDauag
    @UnitFerminBDauag Год назад

    galing niyo idol sir tama lahat ang mga paliwanag niyo marami akong natutuhan sa inyo

  • @bigdaddyjr201
    @bigdaddyjr201 2 года назад +2

    Very informative...
    God bless for sharing...

  • @RickSancheeze
    @RickSancheeze 2 года назад +2

    Thanks for the info sir. Continue to share this knowledge to all our fellow engineers and electricians.
    Very good presentation and very clear explanation.
    looking forward for another videos.

  • @JeffersonedeJesus0323
    @JeffersonedeJesus0323 3 года назад +2

    another yet premium content. kudos!

  • @renzofficial2435
    @renzofficial2435 2 года назад +1

    thanks sa pag share ng kaalaman sir mabuhay po kayo

  • @jonereytech349
    @jonereytech349 3 года назад +1

    Ganyan din wiring ko sa Bahay nang papa ko..sa probinsya line to neutral..

  • @carlmixeddiyvlogs1897
    @carlmixeddiyvlogs1897 Год назад

    Napaka solid ng mga content mo sir..sana marami mo pa ma iShare para marami pa Namin matutunan..

  • @tommylungay647
    @tommylungay647 Год назад

    Marami akong na toroman sayo master

  • @ohmware2020
    @ohmware2020 3 года назад +1

    wow! cant wait sir!

  • @opecons
    @opecons 9 месяцев назад

    15:33 yung double tapping ay sa mga branch circuit at mayrong main circuit breaker. At pwede ang tapping na example ng Schneider kasi may main circuit. Pero ang 2pole na tapping sa drawing ni engr ay hindi pwede kasi ito magiging 2 branch circuit na so kilangan ng main circuit breaker .

  • @tommylungay647
    @tommylungay647 Год назад

    Salamat master

  • @guitarizta7142
    @guitarizta7142 3 года назад +1

    common ito sa mga provincial area

  • @junrex2023
    @junrex2023 Год назад

    Tumpak po Sir. mga tutorials mo.👍👍👍

  • @jillferrer6135
    @jillferrer6135 2 года назад

    thanks for ur sharing...

  • @alienoidmartian1758
    @alienoidmartian1758 3 года назад +1

    Nice po Sir

  • @maestroelectriko
    @maestroelectriko 2 года назад

    Thanks for this info. Master

  • @opecons
    @opecons 9 месяцев назад

    Example ni engr sa 4:03 sa NEC handbook. Tingnan nyo ang amperahi ng breaker at no. ng wire. Possible yan ay main circuit breaker at may mga branch circuit breaker o di kaya circuit breaker ng transformer or motors. Ang example ni engr sa NEC handbook ay hindi maapply sa 2-pole branch circuit breaker tapping.

  • @larry454
    @larry454 Год назад

    Sa tingin ko yung sa Dsquare Na CB ..kapag Copper pwede dalawa .,kapag copper at aluminium isa lang. Kasi nagkakaroon ng Corrosion...bawal pagsamahin yung magkaibang metal..

  • @JilianFernandez-qb9pt
    @JilianFernandez-qb9pt 13 дней назад

    Sir gud a.m ask Klang kung Yung neutral bar ba na insulation or nkabond mismo sa NEMA 3r metal enclosure sir?salamat sa pagsagot po sir

  • @user-xu7op4rd2s
    @user-xu7op4rd2s 4 месяца назад

    Gd eve sir ..wala akong nakuhang rcbo na single pole plus neutral na 100 a ...pwede n gamitin ung double pole...pero line to ground ung supply ....singke lafat sa load side ko

  • @JaJ0001
    @JaJ0001 3 года назад +1

    Ganyan ang system of wiring s ibang mga establishment dito at mga at mga bahay

  • @jaybeefernandez3450
    @jaybeefernandez3450 Год назад

    Sir ask klang yung nuetral bas bar ba insulated ba o nkadikit mismo sa enclosure?

  • @FrancisKevinOdan
    @FrancisKevinOdan 8 месяцев назад

    Sir ano po ang dapat na service wire sa breaker na 150 ampers

  • @haroldafable2584
    @haroldafable2584 2 месяца назад

    sir tatanong lang sana..magtrip kaya yong ganyang set-up..isang pole sa light isang pole sa CO tas labas yong neutral? dba naka design yong koten na breaker or royu para sa 2pole? safe po ba?

  • @ElectricalPinoyTutorialTV
    @ElectricalPinoyTutorialTV 3 года назад +2

    Gud eve ka master pwede ko bang gamiting tong link ng video nyo po para sa vlog ko? Para sa clear explanation ng nga viewers and also promote ko na din kayo sa channel.ko tnx and godbless po master

  • @maelenjunio2152
    @maelenjunio2152 2 года назад

    Hi master,pwd po ba makita ung vedeo ng pag connect ng line to ground sa panel baord na 4 ang breaker i main,isang main 3 elements,?thanks very big po,..master,..

  • @user-xu7op4rd2s
    @user-xu7op4rd2s 5 месяцев назад

    Sir...line to ground sa amin ....pwede ba two pole ung main tapos ung branches two at one pole combination ...pero paanu magkabit ...3wire ung acu ko

  • @dodst.v4833
    @dodst.v4833 2 года назад

    maganda araw po ask ko lng po master mas mura po ba aboitiz power corporation sa meralco

  • @mikemike3293
    @mikemike3293 3 года назад +1

    Master pano po ang wiring connection nito,, meron po ako nema 3R enclosure sa labas ng bahay ko na 60A CB po sa service entrance,,at ang main ko po ay RCBO na 1pole +neutral 63A,, tapos ang mga branches ko po ay MCB na 2pole sa loob ng bahay ok lng po ba yan,,, yan po kasi ang seset up ko sa bahay ko..line to neutral po ang service provider namin dito,,sana po mabigyan nyo ako ng wiring diagram,, salamat po master

  • @archietamayo3128
    @archietamayo3128 2 года назад +1

    sir baka namn pede maka e copy or pdf ng mga book na binabangit mo sa video. or may links ka po ba? share namn.

  • @monmon-sx5cj
    @monmon-sx5cj 3 года назад +1

    very professional ang pagdiscuss. engineer ka po ba ??

  • @joebertartuz1857
    @joebertartuz1857 Год назад

    Sir Ilan po ba pwide ilagay na outlet at ilaw sa line to neutral na connection. Salamat po. Paki sagot naman.

  • @AnonyMous-fj2uv
    @AnonyMous-fj2uv 3 года назад +3

    Sir goodmorning, kindly answer po, may mga ngsasabi na iisa lng ang tripping element ng koten breakers kya d daw advisable ung jumpering ng live wire dhl d daw magtitrip ung isang pole if na short sya dhl sa kabilang pole lng may tripping element at un lng magtitrip, kya hati parin ang iba if OK ba ang jumpering sa cb or not, may I ask if pwede nyo pong gawan ng video like in actual na may both live wire ung bawat pole ng koten then try to short the wire coming from the right pole if mag trio lng sya mag isa and ganun din sa wire coming from left pole if magtitrip din sya at d damay ung kabila sir? Bale in that case is naalis na ung kulay blue na holder ng both pole, bilang debunk nrn sana if totoo bang working ang 100% safe ung ganyang style dto sa province, thanks po in advance

    • @practicalelectrical3837
      @practicalelectrical3837  3 года назад +2

      Hi sir yes tama ang iyong sinabi. Kung tutuusin pag sinabi naten 2 pole na mcb (tho not applicable sa mga mccb), may independent single pole pa rin sila pero dahil sa mechanical interlock na handle tie (yung blue), pag nagtrip ang isang pole damay ang isa.
      Pero kung tatanggalin mo sir ung blue na handle tie niya, yes hiwalay at individual na ang tripping niya independent sa isa't isa.
      Maraming gumagawa na tinatanggal ang handle tie with is technically parang ginawa mong single pole lng ang breakers. 👍

  • @markjoshuaeduardo8192
    @markjoshuaeduardo8192 2 года назад

    Sir paano poba nalalaman kung anong AF gagamitin sa isang Circuit breaker pag sa service entence?

  • @gerryboypanot7344
    @gerryboypanot7344 3 года назад +1

    Sir ikaw ang bagong Fajardo.....

  • @mackeyboytv9492
    @mackeyboytv9492 2 года назад

    Master excuse po, bago lng po ako, ang connection po s amin is line to ground,master pwdi po s main circuit breaker n 20 ampers don nlng po ako mag jumpers ng 15 ampers n breaker para s ilaw at 20 amperes n breaker para s outlet,, oky po b un master, zlmat po god bless

  • @mannydeguzman79
    @mannydeguzman79 2 года назад

    Pwede po bang naka ground lang sa lupa kahit walang breaker or rcbo?ano po posibleng mangyare?

  • @mannydeguzman79
    @mannydeguzman79 2 года назад

    Sir kung gfci outlet pwede sir kahit walang rcbo?

  • @cvelasquez4205
    @cvelasquez4205 2 года назад

    Sir question 😂 paano pala pag pinadaan ko sa breaker yung ground wire. Violation ba yun or ok lang?

  • @carmelaluzong7679
    @carmelaluzong7679 2 года назад

    Idol... natural lng ba na normally close ang line two connection ng breaker sa panel board kht line to line ang connection...

  • @noellejadezamora3546
    @noellejadezamora3546 2 года назад

    Good pm Sir., Dito sa Amin line to line po Ang kuryente pwede kopo ba gawin yan jumper nalang, Hindi poba violation sa PEC?

  • @shalehaquindimatingkal5876
    @shalehaquindimatingkal5876 Год назад

    pag sa mga probincya po sir line to ground eh wla na po bang neutral?

  • @opecons
    @opecons 9 месяцев назад

    20:05 ang exhibit na yan ay hindi natin maimkumpara sa tinukoy ni engr na 2-pole cb jumpering...magkaiba po.

  • @RRR-zh6hm
    @RRR-zh6hm 3 года назад +1

    sir pag nagkashort circuit ba yung para sa ilaw at kasabay dn ng pag trip ng para sa outlet dahil sa mechanical interlock. hindi pa rin magagamit ang line para sa outlet kaht ibaba at itaas ulit natin ang breaker ng outlet?

    • @practicalelectrical3837
      @practicalelectrical3837  3 года назад

      Magagamit sir kung temporary lng yung short circuit naten sa circuit ng ilaw pero kung permanent na ang short circuit niya duon, magtritrip ulit ang breaker naten kaya need na naten icheck ang wiring system fault sa ganung case

  • @aljoncastidades8657
    @aljoncastidades8657 3 года назад +1

    Sir. Pwede bang 3 Pole lang ang Manual Transfer Switch sa 3 phase 4 wire system?

    • @practicalelectrical3837
      @practicalelectrical3837  3 года назад +1

      Yes, pero take note pag ganun ang ginawa mo, hindi na considered as separately derived ang generator mo kaya hindi mo pwedeng iground ang neutral terminal ni generator.
      May video tayong gagawin about dyan master debunk naten ang myths sa wiring niya 👍

  • @jaysiapno659
    @jaysiapno659 2 года назад

    Ser...bkt ung vlogger sa u tube... nagbubukas ng service meter...kase save nya electrician daw sa munipyo nla...ser dba violation ung... ser paki explain naman... ser sana masagot nyu po.... thynx

  • @RRR-zh6hm
    @RRR-zh6hm 3 года назад +1

    sir kung #8 na wire mula sa breaker papuntang metro. anung number ang gagamitin na wire sa pagjumper sa breaker? #8 din ba or pwede na 12?.

    • @practicalelectrical3837
      @practicalelectrical3837  3 года назад

      Kung tutuusin pwede ang number 12 pero hindi ko iaadvise dahil ang wires sa lineside ng breaker ay considered pa rin as "service entrance conductors" kaya naman min. Size pa rin ay number 8.
      Sa kadahilanang ang mga wires sa lineside ng cb ay unprotected from overload and short circuit kaya need mo ma satisfy yung sinasabe sa PEC na minimum size na kayang isustain yun for long period of time.
      Marami ring obo inspector na irerequire ang number 8 sa lineside ng cb.

  • @RodSniperVlogTv
    @RodSniperVlogTv 3 года назад +1

    Parang di nga pasa Yan bro sa PEC may proper cb panel Tayo para sa Line to ground system..kung Hindi Ako nagkakamali pero kung Mali Ako bro comments mo dto sa comments ko para sa kaalaman ko thanks.

  • @jamzryder4638
    @jamzryder4638 2 года назад

    paano boss pag sa 5 jaws na line to ground.. sana mapansin mo

  • @markjosephdeluna
    @markjosephdeluna 3 года назад +2

    Master ung 100AT ung AT po ba jan ampere trip ? ee ung 100AF ? AF - ampere fault po ba ?

    • @bloomberg4865
      @bloomberg4865 3 года назад +3

      Ampere frame meaning ung laki ng breaker .

    • @markjosephdeluna
      @markjosephdeluna 3 года назад +1

      @@bloomberg4865 salamat master 🙏

  • @darviemandras44
    @darviemandras44 3 года назад +1

    Sir saan po ka po makaka bili nang PEC book reviewer?

  • @chrisigop4471
    @chrisigop4471 3 года назад +1

    nkalagay b sa pec na kailangan may breaker ang ground wire?

  • @ohmware2020
    @ohmware2020 3 года назад +1

    sir, yung normal na circuit breaker is nagtritrip ba during ground fault? lets say may proper ground fault wiri g ang bahay, kc sabi ng iba walang ground fault protection ang karaniwang circuit breaker

    • @bloomberg4865
      @bloomberg4865 3 года назад +2

      Hindi bro ,kaya gagamit ka ng rcbo

    • @ohmware2020
      @ohmware2020 3 года назад +2

      @@bloomberg4865 thank you po, sna nabanggit ni sir sa video...

    • @practicalelectrical3837
      @practicalelectrical3837  3 года назад +2

      Yes sir, ang normal na typical CB ay walang ground fault protection. Only overcurrent at short circuit current protection. Kaya required ni PEC na mayroon tayong return ng ground fault gamit ang equipment grounding conductor upang masiguro na mababa ang impedance ng ground fault current naten para mapatrip naten ang breaker naten. May discussion tayo sir nun sa past videos.

    • @alienoidmartian1758
      @alienoidmartian1758 3 года назад +1

      @@practicalelectrical3837 Sir baka pwede paki reply po ng link, salamat po

    • @ohmware2020
      @ohmware2020 3 года назад +1

      @@practicalelectrical3837 kahit my proper ground fault wiring ang bahay sir kung normal cb ang gamit then hindi parin gagana na mgtrip ang breaker?

  • @RRR-zh6hm
    @RRR-zh6hm 3 года назад +1

    sir paano po kung walang akong pang grounding na mababaon sa lupa?

    • @practicalelectrical3837
      @practicalelectrical3837  3 года назад

      Steel rebars or steel foundation sir allowed din ni code. 👍

    • @majnaawah2344
      @majnaawah2344 3 года назад +1

      @@practicalelectrical3837 Sir pwede po ba sa dagat nakabaon o nakalagay yong grounding? Dito po kasi sa Tawi-Tawi nasa dagat yong pinagtayuan ng bahay. Sana po masagot nyo, TIA.

    • @practicalelectrical3837
      @practicalelectrical3837  3 года назад

      @@majnaawah2344 mukhang magandan scenario yan. Yung bahay ba mismo ay lumulutang sa bahay o may poste o struktura na bakal pa rin ba siyang kinakapitan bilang suporta?

    • @majnaawah2344
      @majnaawah2344 2 года назад +1

      @@practicalelectrical3837 yes po as in dagat talaga, Bali may poste/column po yari sa cemento at minsan kahoy na nkabaon sa buhangin sa ilalim ng dagat. Para po mas malinaw kung ok lang po sa inyo check nyo po area namin kaht sa youtube...Sitangkai, Tawi-Tawi known as "Venice of the South" bago lang po kasi nagkaroon ng Service provider ang ilaw dito. Thanks po master

    • @practicalelectrical3837
      @practicalelectrical3837  2 года назад +1

      @@majnaawah2344 since tubig dagat, I will assume sir na mababa ang resistance ng pagkakabaon ng steel column or rebars sa lupa sa dagat. In that case sir, pwede mo gamitin yung poste na yun na may direct contact sa lupa sa ilalim ng dagat. Mukhang malabo na kasi ang pagbabaon ng ground rod sa case niyo.

  • @zubzerho_1085
    @zubzerho_1085 Год назад

    stantard ng pilipinas pagdating sa electrical behind talaga. kaya maraming nasusunog na bahay.. paaano hind consider yan e safety ang klaseng breaker na MCB

  • @ElectricalPinoyTutorialTV
    @ElectricalPinoyTutorialTV 3 года назад +2

    Sr. Ito na po ung link. Salamat po sr.
    ruclips.net/video/znSutEQroZU/видео.html

  • @practicalelectrical3837
    @practicalelectrical3837  3 года назад

    🔗PRACTICAL PHILIPPINE ELECTRICAL WEBINAR SERIES FULL PLAYLIST
    ruclips.net/p/PLO4MWmSMQe6Z56GgD5IkGBzHMvW0u_Tqe

  • @arnoldlabastida6852
    @arnoldlabastida6852 3 года назад +1

    Ano ba talaga ang tama line to neutral or line to ground?

  • @zubzerho_1085
    @zubzerho_1085 Год назад

    koten panget na klaseng breaker hindi nayan ginagamit namin dito.. misan hindi pa nagtritrip kahit sa ligthing