Daikin VRV3 troubleshooting outdoor unit not working (error UO)not producing cold air.

Поделиться
HTML-код
  • Опубликовано: 12 сен 2024
  • Brand : Daikin VRV3
    error : error history UO
    Symptom : Outdoor unit not working,indoor no blinking and no error.
    Cause : Gas leak
    Error : UO
    Method of Malfunction Detection
    Short of gas malfunction is detected by discharge pipe temperature thermistor.
    Malfunction Decision Conditions
    Microcomputer judge and detect if the system is short of refrigerant.
    *Malfunction is not decided while the unit operation is continued.
    Supposed Cause
    ^Out of gas or refrigerant system clogging(incorrect piping)
    ^Defect of pressure sensor
    ^Defect of outdoor unit PC board (A1P)
    ^Defect of thermistor R2T or R4T
    Wire remote control model : BRC1C62
    #bonmj #daikin #vrv

Комментарии • 46

  • @servemainaircool1447
    @servemainaircool1447 2 года назад +1

    If leak not found on pipe work or refnets if fitted try indoor unit expansion valves or coils in general if fan coils have been fitted remove drain bungs ( obviously holding a bucket underneath you should see or feel signs of oil from the offending unit

  • @patrociolacic6088
    @patrociolacic6088 Год назад +1

    MERCI 🤓

  • @rdenir
    @rdenir 2 года назад +1

    Good Video again Bon,,
    Did you find the leak and where was it if you did?

    • @BonMj
      @BonMj  2 года назад +2

      Not yet.just summit quote.
      Thanks for your support .

    • @rdenir
      @rdenir 2 года назад

      @@BonMj Good Luck,,
      Keep us updated

  • @mdtaslimalam8595
    @mdtaslimalam8595 2 года назад +1

    Good information 👍👍👍👍 sir

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @linaung127
    @linaung127 2 года назад +1

    Thanks for your sharing

    • @BonMj
      @BonMj  2 года назад

      Welcome

  • @manikandanmani646
    @manikandanmani646 2 года назад +1

    Hi Bro Waiting for Next video 😉

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @HVACSystem
    @HVACSystem 2 года назад +1

    Good job 👌 sir

    • @BonMj
      @BonMj  2 года назад

      Thanks master.

  • @Idiophones
    @Idiophones Год назад +1

    My 4 units, no error, not geting on out door units only AHU are working

  • @agusanwar107
    @agusanwar107 2 года назад +1

    mantap master HVAC

    • @BonMj
      @BonMj  2 года назад

      Terima kasih master.

  • @goparismail9727
    @goparismail9727 2 года назад +1

    sukses selalu bos ku good👍👍👌

    • @BonMj
      @BonMj  2 года назад

      Terima Kasih master

  • @วีระนรินทร์รัมย์

    ผมเป็นช่างแอร์ประเทศไทย ผมได้ความรู้จากเทคนิดคุณดีมากขอบคุณครับ

  • @karaors8970
    @karaors8970 2 года назад +1

    Hı Bon nice Job bro+1

    • @BonMj
      @BonMj  2 года назад

      Thanks bro

  • @ffsurajityt7313
    @ffsurajityt7313 2 года назад +1

    Liquid ot gas line thermistor temperature different

  • @mdafsarkhan9278
    @mdafsarkhan9278 2 года назад +1

    How to find out master out door

    • @BonMj
      @BonMj  2 года назад +1

      Led 3 on is master

  • @azribasri7281
    @azribasri7281 2 года назад +1

    hello bon if vrv3 daikin if j1 whats the problem its say sensor

    • @azribasri7281
      @azribasri7281 2 года назад +1

      can u help me tq

    • @azribasri7281
      @azribasri7281 2 года назад +1

      cause indoor unit is still running but outdoor not running

    • @BonMj
      @BonMj  2 года назад

      @@azribasri7281 do you check gas pressure?

    • @azribasri7281
      @azribasri7281 2 года назад +1

      @@BonMj gas i check low psi

    • @azribasri7281
      @azribasri7281 2 года назад

      do you have whatsapp or facebook for me to easy contact you?

  • @FullyAirconditioned
    @FullyAirconditioned 2 года назад +1

    Ain’t got no gas in it

  • @OK-pt6bo
    @OK-pt6bo 2 года назад +1

    Hi
    Hello brother, does your company need a working man? I want to learn to work from you

    • @BonMj
      @BonMj  2 года назад

      Yes.are you Singaporean or PR

    • @OK-pt6bo
      @OK-pt6bo 2 года назад +1

      @@BonMj I am from Bangladesh

    • @BonMj
      @BonMj  2 года назад

      @@OK-pt6bo i need PR or Singaporean.

    • @OK-pt6bo
      @OK-pt6bo 2 года назад +1

      @@BonMj ok If there is any critical problem in my work place, I will let you know. Please give me your solution 🙏 I see your video & learning

    • @BonMj
      @BonMj  2 года назад

      @@OK-pt6bo Thanks