Daikin VRV | Troubleshooting indoor and outdoor unit communication problem | Error U4

Поделиться
HTML-код
  • Опубликовано: 25 ноя 2024

Комментарии • 100

  • @johnnyroxannebautista2063
    @johnnyroxannebautista2063 2 года назад +2

    Your video is so informative and very helpfull to every technicians around the globe.
    Thank you for sharing this.
    You're the man Sir Bon.

    • @BonMj
      @BonMj  2 года назад

      Thanks bro

  • @chandansahani8242
    @chandansahani8242 2 года назад +1

    He bon I want to take training with you only vrf and vrv please🙏 because you are a great teacher

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @johnsonchirayat.4454
    @johnsonchirayat.4454 2 года назад +1

    Very grateful Experience from you Bon

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @brandonle4930
    @brandonle4930 2 года назад +1

    Great Video Bon! Thank you sir.

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @nguyenthechung
    @nguyenthechung 2 года назад +1

    Thanks you so much! You're good men.

    • @BonMj
      @BonMj  2 года назад

      Welcome

    • @nguyenthechung
      @nguyenthechung 2 года назад +1

      @@BonMj I just learned through the Internet, but you are like a teacher to me. I am very grateful to you! Wish you good health to work!

    • @BonMj
      @BonMj  2 года назад

      @@nguyenthechung 👍thanks

  • @rajasekaran8420
    @rajasekaran8420 8 месяцев назад +1

    Great👍👍👍 job sir

    • @BonMj
      @BonMj  8 месяцев назад

      Thanks

  • @aureliancioroiu8178
    @aureliancioroiu8178 2 года назад +1

    Hello Mr Bon.
    Why 2 of 5 indoor units does not have voltage?
    I checked the supply til the branch and I have voltage.
    I have to open the units to look the PCB.
    there is probably something wrong with the high voltage side of the PCB?
    Thanks for you support!

    • @BonMj
      @BonMj  2 года назад +1

      Check indoor fcu incoming power supply

  • @rdenir
    @rdenir 2 года назад +1

    Good work Bon, so the issue was faulty FCU? Was it the indoor board or supply fan motor?

    • @brandonle4930
      @brandonle4930 2 года назад

      The issue is the main power supply going into the FCU. He ran a separate power source temporary powering that FCU.

  • @sv6k0a39
    @sv6k0a39 Год назад +1

    So the power wire feeding that indoor unit was shorted to ground?

  • @BERESHIDA2008
    @BERESHIDA2008 2 года назад +1

    what I dint get is, when you conect the multimer , did you selected continuity or volatage ? that wasent clear?

  • @tamtez5909
    @tamtez5909 Год назад +1

    Hi Mr Bon, your video is very helpful. Could you please guide me how to ban indoor units, VRV4 has 6 indoor units, 1 indoor unit is to be disconnected from the power supply for repair, for the remaining 5 indoor units to still operate normally. Thank you so much for your support!

    • @BonMj
      @BonMj  Год назад

      After disconnect indoor , reset outdoor power supply and long press return button.

    • @tamtez5909
      @tamtez5909 Год назад

      ​@@BonMjThank you for assisting me. Wish you good health to work

  • @karimchiu7527
    @karimchiu7527 2 года назад +1

    thanks sir Bon

    • @BonMj
      @BonMj  2 года назад

      You are the best👍👍
      Thank you very much. 🙏🙏

  • @deshanabeysekara5124
    @deshanabeysekara5124 Год назад +1

    thank you very much for the video sir,I have one question.after cabling we want to give test run agai manually or not?..

    • @BonMj
      @BonMj  Год назад

      Try use remote to on

  • @eduardovargasarancibia2628
    @eduardovargasarancibia2628 Год назад +1

    Hola por favor me ayuda tengo un sistema con el código Uf-01 pero en alguno termostatos me muestra u4-01, ya revise cableado y luz happ

  • @farelgaming3117
    @farelgaming3117 2 года назад +1

    Thank you very much

    • @BonMj
      @BonMj  2 года назад +1

      Welcome

  • @lokeshlokeshkumar2107
    @lokeshlokeshkumar2107 2 года назад +1

    Hai sir.. Good evening

  • @LeeJeff-j2u
    @LeeJeff-j2u 11 месяцев назад

    Hi Bon, do you have FXMQ32PVE motorized valve and C4, C5 thermistor?

    • @BonMj
      @BonMj  11 месяцев назад

      Dun have, sorry

    • @LeeJeff-j2u
      @LeeJeff-j2u 11 месяцев назад

      @@BonMj it's ok, thanks

  • @matazglb5346
    @matazglb5346 2 года назад +1

    I thank you so much.

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @manikandanmani646
    @manikandanmani646 2 года назад +1

    Hi Bro Good Job 👏

    • @BonMj
      @BonMj  2 года назад

      Thanks bro 🙏🙏🙏

  • @samhaazratechnicalsupport
    @samhaazratechnicalsupport Год назад +1

    Good sir

    • @BonMj
      @BonMj  Год назад

      Thanks and welcome

  • @jiezhang730
    @jiezhang730 2 года назад +1

    Hi Sir,
    May I ask how to check the reason of showing U4 code for daikin RZP100? Thank you

    • @BonMj
      @BonMj  2 года назад

      Check comunication wire, indoor pcb or outdoor pcb + check incoming power supply.

  • @angreentachairconditioning4687
    @angreentachairconditioning4687 2 года назад +1

    Nyc

  • @khaerulanam5581
    @khaerulanam5581 Год назад +1

    Hello master, i have daikin vrv-4 and get trouble UC..?
    How to fix...?

    • @BonMj
      @BonMj  Год назад

      May system controller address duplicate

  • @johnnyroxannebautista2063
    @johnnyroxannebautista2063 2 года назад

    I just want to ask, how long or seconds the BS3 button to press/hold to reset VRV4?

    • @BonMj
      @BonMj  2 года назад +1

      More than 5second

    • @johnnyroxannebautista2063
      @johnnyroxannebautista2063 2 года назад +1

      i watched the video from 1.56 to 2.02 during the reset and its more than 5 seconds
      am i going to wait for the lights off for the reset sir Bon?

    • @BonMj
      @BonMj  2 года назад

      @@johnnyroxannebautista2063 yes..wait the 7 segment light off.

  • @kudteb6
    @kudteb6 2 года назад +2

    Good

  • @josealduenda1186
    @josealduenda1186 2 года назад +1

    Excelente maestro, necesito de su ayuda tengo un problema con un sistema Daikin VRV IV al momento de encenderla la condensadora maestra arranca por unos segundos y marca el error U4-03 me podría ayudar con el significado de este codigo

    • @BonMj
      @BonMj  2 года назад

      Do you check other indoor unit?
      1)may one or more the indoor unit power supply problem or pcb faulty.
      2)may outdoor pcb problem.
      3)or communication wire problem.

    • @josealduenda1186
      @josealduenda1186 2 года назад +1

      @@BonMj como puedo identificar el evaporador que tiene el problema ?

    • @josealduenda1186
      @josealduenda1186 2 года назад +1

      Ya probamos el cable de señal con continuidad y no tiene problemas o recomienda cambiarlo?

  • @samhaazratechnicalsupport
    @samhaazratechnicalsupport Год назад +1

    Sir please tell me how come singapore me please 🙏😘🇮🇳

  • @lesterrivera4154
    @lesterrivera4154 2 года назад +1

    Hi sir bon.. may i ask you how many PSI in VRV 3 R410a in 3 unit indoor thanks

    • @BonMj
      @BonMj  2 года назад

      Difficult to say for the pressure in vrv system.
      For new installation,need to calculate the pipe length and pipe size to add extra refrigerant.

    • @lesterrivera4154
      @lesterrivera4154 2 года назад +1

      @@BonMj sir 25 meters 3/8 liquid line and 5/3 suction. Its ok at 150 psi?

    • @BonMj
      @BonMj  2 года назад

      @@lesterrivera4154 5 hp?

    • @lesterrivera4154
      @lesterrivera4154 2 года назад +1

      @@BonMj12 hp (Daikin VRV 3 Heat pump) model RXYQ12PYLK.

    • @BonMj
      @BonMj  2 года назад

      @@lesterrivera4154 oic..

  • @karaors8970
    @karaors8970 2 года назад +1

    Hi bon 🇹🇷🤳🛠️👍

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @muhamadsani9801
    @muhamadsani9801 2 года назад +1

    Hi Bon can solve my problem aircond split unit, inverter brand york is error code is been detect L5 ? But i done change pcb outdoor still same. Tq

    • @BonMj
      @BonMj  2 года назад +1

      Try check the compressor input voltage or ampere.

    • @muhamadsani9801
      @muhamadsani9801 2 года назад +1

      @@BonMj okey later i check this voltage . but how if i can get same result ?

    • @BonMj
      @BonMj  2 года назад +1

      @@muhamadsani9801 what you mean same result.
      If voltage ok ,should the compressor got problem

    • @muhamadsani9801
      @muhamadsani9801 2 года назад

      @@BonMj yaa . Voltage is normal. Oh Compressor ? But i check quantinity is normal , all terminal compressor is okey. So how i can solve my problem tq.

    • @BonMj
      @BonMj  2 года назад +1

      @@muhamadsani9801 pcb output voltage ok?

  • @agusanwar107
    @agusanwar107 2 года назад +1

    please MR .long Duration videos or Upload

  • @lokeshlokeshkumar2107
    @lokeshlokeshkumar2107 2 года назад +1

    I request daikin dect model cfm calculation plz videos

  • @hitmankingdom825
    @hitmankingdom825 2 года назад +1

    E2-02 VRV AC ERROR CODE WHAT IS THE PROBLEM

    • @hitmankingdom825
      @hitmankingdom825 2 года назад +1

      I also change all pcb and sensor as well but machine is showing e2-02

    • @BonMj
      @BonMj  2 года назад

      @@hitmankingdom825 check high pressure sensor

  • @StarClub993
    @StarClub993 Год назад +1

    How to slove error HJ-04

    • @BonMj
      @BonMj  Год назад

      May thermal storage water level sensor

  • @monojnath8446
    @monojnath8446 Год назад +1

    Hi boos

  • @АлишерИдаганов-с1з
    @АлишерИдаганов-с1з 2 года назад +1

    Привет,класные и полезное видео,помогите устранить ошибку "UA" Daikin VRV 3

    • @BonMj
      @BonMj  2 года назад

      Check indoor and outdoor power supply.
      Or wrong connect model

  • @TanveerAhmad-is4uc
    @TanveerAhmad-is4uc 2 года назад +1

    Please urgently help 4way cassette and 1 side cooling and 3other side air through and pcb changing and electronic expention valve change please which use settings for cooling remote number BRC1C62-9

    • @BonMj
      @BonMj  2 года назад

      I side cooling should insufficient gas to FCU.
      How is the gas pressure

    • @TanveerAhmad-is4uc
      @TanveerAhmad-is4uc 2 года назад

      @@BonMj back pressure 140 pai and discharge 450 psi

    • @BonMj
      @BonMj  2 года назад

      @@TanveerAhmad-is4uc model? Running amps?

    • @TanveerAhmad-is4uc
      @TanveerAhmad-is4uc 2 года назад +1

      @@BonMj VRV X model no RXYQ20ARY6 17 ampere take 1 indoor only start.

    • @BonMj
      @BonMj  2 года назад

      @@TanveerAhmad-is4uc you only on 1fcu?

  • @eduardovargasarancibia2628
    @eduardovargasarancibia2628 Год назад +1

    Hola por favor me ayuda tengo un sistema con el código Uf-01 pero en alguno termostatos me muestra u4-01, ya revise cableado y luz happ

    • @BonMj
      @BonMj  Год назад

      UF try check the indoor unit thermistor

    • @Mangashraf02
      @Mangashraf02 5 месяцев назад

      Mis kalo PCB outdoor U4-01dan termostat indor u4 apa masalahnya ya🙏🏻