Relay Setting in Star Delta Starter | Star Delta Starter relay rating
HTML-код
- Опубликовано: 13 окт 2024
- Queries solved:
1. What is star Delta starter.
2. What is star Delta starting.
3. How to select relay for star Delta Starter.
4. Relay rating Selection.
5. Relay Selection guide.
6. Star Delta Starter relay Selection.
Hello Friends in this video we discussed about how to select relay for star Delta Starter in the simplest way possible.
About Channel:
In this Channel we cover the topics like Machines, Power System and General Electrical in the simplest way possible.
#StarDelta
#Relay
Kindly subscribe.
Thank you.
Good morning sir stardalta motor relay line current me Laguna better he ki phes current me better he
Sir Star ki condition me bhi bataiye and DOL Starter ke Case me bhi suggest kijiye
Sir 2pole or 4pole olr setting same hai?
Please tell me in star delta starter olr setting will be different or not and will be then how much for star and delta
Is fullload current is same in star conncetd motor and delta connected motor for same kw rating?
Yes..
Sir 90 kw motor ka fhul load curent 158 amp he .motor runinig continou to rely setings delta current me hi set hogi 158 amp
Very good f
sir I'm ur fan...
Thank you Rajeev...🙏
Star delta me 6 wire hote he relay main contactor me lagta he to current to 2 bhag me bat jaata he to kya kare....50A motor ka rated current he star delta connection or relay main cont.me laga he 50A tak set karna ho to 25 A par set kare ya 50 A..????
Good Sir i appreciate from Pakistan
Very nice
What if in DOL starter motor winding is delta in that case also we set O/L to 58% of Full load current
sir mere pas 75kw ka motar he or ishame main mpcb 400A ka or sir over load relay face current me laga or muje ae motar daily start stop karna he sir inka relay seting 58% 74.5A pe rakhata hu to starting mehi motar over load ho jata he
Sir 90kw ki motor ka current kam hota he na 160 amp something
For 20 HP, 3 Phase Induction Motor of Submersible Pump, which starter we have to select - 20 HP or 22.5 HP and what will be selection criteria & How ?
Pls reply.
Sir mere Ghar me 7.5 kw ka motor hai Jo ki manul star Delta starter say chal rha tha ,per kuch deno say usme proble aa rha tha ,contect melt ho gye the aor coil bhi hold nhi ho rha tha,to Maine usme mody fykr diya hu ,uske andar 32Amp ka MCB ,,32Amp ka contector aor 20Amp max range ka OLR really install kr ke DOL STARTE me convert kr diya hu ,relay setting 13 Amp me kiya hu ,Kyo ki sir Ghar me mai any time rhta nhi hu aor baaki log non technical hai setting Kam krne per baar baar trip hoga ,es say agar Ghar ke log rest krne jyeng to electrical hazard ke chanses bad jyenge,, to sir Maine sahi Kiya ya galat (selection of breakers/Relay
Sir je please RMU ar alternator ka ak alag si video banaia 🙏 🙏 🙏🙏
Okay Abhijit...
I love your all electric videos. Very usefull
Plz muze apke electric groip me add kardo
Awesome 👍
Good video
Nice
3phase / 1 phase motor ka winding restiance kitana hona chahiye , short winding kase pata kare, multimeter ke kaise check kare..... please support
Very nice explain sir aapka video acch Lagta hai
Thank you Dilip..🙏
Thanks sir,
In your video say drow current in stat only 33% how? Plz explain me.
33% in star not in start..
@@electricalwithabhishekjoshi ok thanks
For star delta starter thermal over load relay range selection is 80% for min range and 120% for max range formula applied ?
Pichhle video me star connections motor adhik current leti hai delta connections ke dikhaya hai sir
Aur yha pr Star 33% aur delta 58% current leti hai full load current ke kaise
Aapka confusion phase current or line current ka hai.
Nice explain sir
Sir plc ke uper video banaye
Thank you
Most welcome Sanjaya...
Nice sir
Nice information sir ji
Thank you Rajeev..
Thanks sir
Sir agar normal motor ko delta me connection karte hain to FLC Ka 80% use karte hain
Aur Star to Delta me 58 % hi kyu
Kyuki Delta ka formula Dono condition me same hi rahta hai
As Line Current = √3 phase current
Fantastic video 👌👌
Thanks sir 🙏
Most welcome KK..
Sir star delta starter me really men contrecror ke output me laga hota hai usme moter ke 3 terminal, baki 3 terminal delta contrecror me to Mera confusion ye hai ampiar kese check hoga moter ka
Hiteshwar, motor mein jo 6 lead ja rahe hai (3 main contactor se aur 3 delta contactor se) usme current check karo..
@@electricalwithabhishekjoshi sir Mera cunfusin ye hai really se 3 terminal baki 3 delta se to really actual current sens kese Karega kya really Ka position tik hai ya mccb brekar ke bad olr really lagana chahiye olr really Ka sahi position kya hona chahiye
Hiteshwar relay ka position sahi hai... 6 leads mein same current hi flow hota hai..
@@electricalwithabhishekjoshi really 90amp me set hoga to really ke output R our delta contrecror ke output R phase me kitne Amp par trip hoga us time. dono R phase me Kitna amper bahega
Abhishek,
Kindly make a video on star to delta shifting time as per motor capacity.
.what will be the line current of 5kw motor if it s conntected in star nd what will be the current in delta if tha same motor s connted and connection are changed
Pls
Hemant I will release this video today evening..
Sir star delta starter se chalne Vali motor ka flc kese nikale
Nice explation sir,
If star delta starter power on without any load then what happen?
Sir kindly reply me what is iph
Thanks❤❤❤ sir
BUT if we used DMPR or OLR just after the MCCB then wiring the star , delta and main contactor tab to 80% rakhna parega na sir
Yes
@@kavyasingh815 Are u experienced or fresher ?
I have one year experience
I saw a video on these topic electrical dost channel
@@kavyasingh815 Oh , i also have 4 years of experience.
Great
Great work sir 👍👍👍
Thank you Faisal..
Thanks bro
Sir continuity kya hota hai electrical mein batayiyena please
Mein ek biginar huu please Sir batayiyena
Thanks
Awesome videoo
Thank you Samvedna..
Good one thank u so much
Thanks Abhishek
Awesome video 👍👍👍
Thank you..🙂
Pl suggest how to set time range of star delta timer
Great great great great
Nice video sir
Thank you..
Good knowledge thank you sir
Most welcome Teg Bahadur.
Also watch playlist for videos related to Drawing, Calculation, Motor, Transformer, Power Factor Correction and many more.
In Star delta star timer setting for star to deta change over time plzz
12 sec..
But sir there are 1OLR in star delta srater how i can change OLR seeting in star 33% and delta 58%
Nice mes 👍
Sir lag rha hai ye Corona job kha jyegi
Ap 58% of FLC bol rahe ho. Ye obviously Iph hoga na?
Over load relay Phase me lagaya to hi ye apply hoga.
Incase line me over load lagaya to full load ampere set Krna hoga
Mpcb 400amp ki sating kse kre
Thanku sir ♥️
Kw se kitaneka relay lagasakate
How to calculate Amp. in star delta drive , as it have 6 wire connection ?
Nitesh, are you talking about Full load current??
@@electricalwithabhishekjoshi Yes Sir
Nitesh Maine star Delta starter ka full load current pe video banaya hai. Aap wo dekh sakte hai.
@@electricalwithabhishekjoshi sir i already watch that video,but matter is not clear to me.
Suppose 250kw motor is running with star delta and i have to take full load current with "tounge tester ", how i will calculate full load , as star delta have 6 nos. of lead ?
Nitesh the current you take with fluke meter is running current not a full load current. All the 6 lead draw same amount of current. But that current is a running current.
90 kw motor sir 156 amp legi....ok
3RB2283-4AA1 RELAY PR AK VIDEO BNAO SIR
sir star delta starter phase relay setting,please clearly
Sir 90kw motor ka full load current 160amp hotahe
It's depend on PF and Efficiency
Vai 90 kw motor me FLC current 180amp? Kaise?
90÷.746=121hp then, 121 *1.5= 180 amps
@@satyamjaiswal5561 vai not 1.5 tum is formula ko savi motor me apply nahi kar sakte . Kuki motor ka PF or uski efficiency vi depends karti he us motor ki FLC ke upar.
Max current I =power/ √3×V×cos¢×effeciency
Tum total power of motor / 500 To 550 se devide karoge to near about result milega.
@@satyamjaiswal5561 90KW =90000watt
90000÷500= 164 amps
Ye chutiya banate hain
Delta full load current 58% kaise hits hai
In delta IL=root 3 x Iph hota hai.
So, Iph = 1/1.732= 57.7
In Industries we normally take 58 for Calculation
@@electricalwithabhishekjoshi sir d.o.l starter me bhi to motor runining condition me delta me conect rahti he ....or star delta starter me bhi runing me motor delta conect hoti he ....phir kyo?...80% or 58%....pls expln sir ji
Video banata hu
Sir,not add servise factor.
Sir ब्लैकबोर्ड में समझाओ ना
सर आपने अपनी वीडियो में 90 किलो वाट का मोटर का फूल लोड करंट 180 amp बताया है
Aap Aisa Kyun Bata rahe hain
Where is 58% has come from..I mean how we made the calculation of 58%
Line current=√3 phase current
Iph kya he
Phase current
90 kw motor ka FLC 180 kaise ho jayega sabhi log batao .
Ek video kuchh aur hote Hain aur dusri video mein kuchh aur bolate.
Kripya gumrah na Karen😅
Why only 58%
1/1.732 ka percent nikalo.. its 57.7%
Phase current is 1/1.732 time of line current. Video mein bataya hai.
Sir, Why take only 33% in star. When voltage reduce the current increase.?
Practically we see when motor starting time current take more the full load. Plz reply..
Sandeep, it is true that when voltage increases current decreases and vice versa. I think you have doubts that voltage will decrease in star then how current will decrease as they are inversely proportional. Right?
But Sandeep, you are comparing phase voltage with line current.
In star, phase voltage will reduce not the line voltage.
Hope you got the point..
@@electricalwithabhishekjoshi thanks
Thank u sir
Most welcome Hemant..